Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹75.6 LAccepted-AOC 17 1 ABHOY HALDER LANE KOLKATA | KOLKATA | L1 | Accepted-AOC Accepted | |
| 2 | L2₹80.9 L+₹40,120.51 (0.50%)Rejected-Finance 00 DEY ENTERPRISE SODEPUR 9 10 PITS COLLIERY ASANSOL BARDHAMAN WEST BENGAL 713372 | PASCHIM BARDHAMAN | WEST BENGAL | 713372 | L2 | Rejected-Finance Rejected | |
| 3 | L3₹81.5 L+₹99,883.32 (1.24%)Rejected-Finance 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L3 | Rejected-Finance Rejected |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
26 Apr 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, BMD, PHE, Dte
Office of the Executive Engineer. Bankura Mechanical Division. P.H.E. Dte. Ailakundi, PO Kenduadihi, Bankura 722102.
Providing and installation of pumping machinery and other electromagnetically accessories for Augmentation works Chinabari (Zone - H) under Saltora- Chhatna Water Supply Scheme PWS Scheme under Bankura Mechanical Division PHE Dte.
2024_PHED_679487_12
WBPHED/EE/BMD/NIeT- 32 OF 2023-2024
Open Tender
MECHANICAL
Item Rate
120 days
Bankura
Please refer Tender documents.
6 documents required · 6 mandatory
₹1.8 L
Yes
25 Nov 2024
11 Mar 2024
29 Apr 2024
11 Mar 2024
26 Apr 2024
11 Mar 2024
Amount
PART-A
Supply, delivery of clear water vertical wet type submersible pump suitable for bore well conforming to IS:8034(and as amended threreafter) with standard MOC for potable clear cold water and BEE 3star(minimum) rated capable with a continuous rated-2 pole suitable wet type vertical squirel cage induction motor conformoning to IS: 9283(and as amended threafter) suitable for operation in AC Three phase 415V, 50Hz(category Bmotor) as per NIT
a) Discharge-22 M3/Hour, Total head -22 Mtr
Supply, delivery and storage at site 80 mm dia M.S. E.R.W. column pipe, 4.85 mm thickness with both end threaded including one socket and threaded protector painted with anti corrosive paint
a) 1.5 Mtr. Long
b) 3.05 Mtr. Long
Supply, delivery at site M.S fabricated T/W top cover (flange type)suitable for 200 mm dia tube well made of 12 mm thick M.S. plate with centrally welded 80mm dia M.S Socket(Heavy type) and 40 mm dia socket at side for 40 mm dia G.I. Pipe (for cable entry) & fitting fixing the heavy type G.I pipe specials & nut bolt including welding all joints and supplying all 80 mm dia shorts pieces, bends. flanges, sockets, enlargers etc. & 40 mm dia G.I. pipe, bend, union, joints, elbows as required for complete the job as per direction of EIC.
Supply & delivery of M.S. suspension clamp with necessary nuts, bolts & washer etc suitable for 80mm dia pipe (Size-300 mm x 80 mm x 8 mm each)
Supply, Delivery and storage at site of Horizantal Split cashing Centrifugal Pumping Machinary with base plate flexible coupllng, coupling guard, foundation bolt etc. other Accessories etc. having the following specification and as per technical Specifications given in NIT N.B- H-Q curve has to be submitted during the delivery (1W+1S) Dicharge-45m3/hr, Head-48mtr
Supply, Delivery and Storage at site of suitable capacity Horizontal Foot Mounted solid shaft Induction Motor (IE 4 type) suitable for the pump duty mentioned above with adequate margin as per detail technical specification given in NIT. N.B-No load as well as short-circuit Test Certificate of induction motor during test run has to be submitted during the delivery.
Supply & delivery at site following Valves
Supply & delivery at site & storage CIDF single door swing check NRV (P.N.–1.0) rating as per IS:5312 Part – I, and as per technical Specifications given in NIT
i) DN 80 mm (for Submersible delivery header)
ii) DN 80 mm (for H/L individiual delivery header)
CIDF non-rising Sluice Valve (P.N-1.0) generally conforming to IS 14846 as per technical Specification given in NIT
i) DN – 100mm (for H/L Suction site)
ii) DN – 80mm (for Common delivery header)
Supply and delivery of three phase actuator operated wafer type butterfly valve (PN-1.0) as per Bs-5155 and as per technical Specification given in NIT
i) DN 80 mm (for H/L individual delivery header)
Supply, delivery & storage and installation at site M.S. fabricated dismantling joints with rubber compression ring and adjustable follower flanged complete assembley with galvinised stud and nuts, as per technical Specifications given in NIT
i) DN:100mm (P.N–1.0) (for Suction header line)
ii) DN:80mm (P.N–1.0) (for H/L individual & Common delivery line )
Supply, delivery & storage at site M,S Pipes for individual pump suction & delivery line from pump discharge upto common delivery header, M.S flanges, bends, specials, etc. as required to make the installation of delivery and common delivery header of pumping machineries complete in all respects up to the satisfaction of E.I.C.and as per technical Specifications given in NIT
Supply delivery and storage at site of Electromagnetic Flow Meter with remote indicator cum totalizer unit and cable between the meter and indicator as per technical specification
i) DN: 80 (for H/L Common Header header)
Supply, delivery & storage of Gleeserine type pressure gauge, cast Al. dial along with DN-15 GI impulse line with valve.
i) (0 – 7 Kg.) 102 mm dia for individiual delivery header
ii) (0 – 7 Kg.) 150 mm Ф for Common Header
Supply, delivery & storage of Gleeserine type Compound gauge, cast Al. dial along with DN-15 GI impulse line with valve.
i) (+1 – 1 Kg.) 102 mm Ф for individiual Suction line
Supply, delivery and storage at site of following L.T cables
50 Sq. mm 3.5 core, 1.1 KV grade, Al. Ar XLPE cable conforming to IS : 7098 (Part – I). From Meter to PDB cum MCC throught Voltage Stabiliser
16 Sq. mm 3 core, 1.1 KV grade, Al. Ar, XLPEA cable conforming to IS : 7098 (Part – I). a) 2 nos motor x 20mtr =40 mtr
10 Sq. mm 3 core, 1.1 KV grade, Al. Ar, XLPEA cable conforming to IS : 7098 (Part – I). b) 5nos Sub mersible motor starter x 500mtr =2500 mtr
1.5 sq mm , 12 core , 1.1 KV Grade PVC insulated Copper Armoured control cable as per relevent IS. i) For H/L 2 nos actuater x 15 mtr= 30mtr ii) For H/L 5nos actuater x 100 mtr= 500 mtr
4 Sq. mm 2 core, 1.1 KV grade, Al. Ar, XLPEA cable conforming to IS : 7098 (Part – I). For MCC to Chlorine machine
2.5 sqmm 3core, 1100 Volt grade copper water proof PVC insulated submersible flat submersible cable,Conforming To IS : 694 As Amended Up To Date.
N.B- Purchase of all cables should be as per actual site requrement
Supply, Delivery and Storage at Site 2 mm. thick CRCA Sheet Steel Enclosed Cubical type Indoor Floor Mounted 415 Volt PDB cum MCC Panel having required Feeders as per technical Specifications given in NIT
Supplying delivery of 200 Amps 415 Volt TPN Sheet steel enclosed HBC Fuse type Heavy Duty Double Break Main Switche with Sidet handle operated For receiving WBSEDCL power
Supply delivery and storage at site of Ultrasonic type continuous level measuring unit with provision of 4 to 20 mA analogue signal, indicator and recorder for continuous level monitoring as well as 5 nos. relay out put for sensing high, low, low - low level in suction sump as per technical Specifications given in NIT
Supply, delivery and storage at site of automatically controlled Plunger type chlorinator dosing pump with Flow Rate 100 Ltr./Hr. and Max pressure of 10kg/cm2) with all accessories for pump motor, foundation Bolt, suction and discharge flange and with storage tank of dosing solution of 100 Ltr. capacity and the prime mover to be coupled with pump of 0.5 HP 3 Phase 1450 RPM squirrel cage TEFC induction Motor, Motor will be IE3 (Make of Machine: As per attached vendor list of P.H.E Dte.)
Supply and delivery 50KVA Oil Coolling type Voltage Stabiliser, having unbalance 200 - 500 V input voltage, and 415(±1%) out put voltage , Auto/manual servo voltage stabilizer with U/V,O/V,O/L protection with contactor at out put side, input MCB, Ammeter Bell etc. as per I.E rules and as per tecnical specification given in NIT N.B.:- Manufacturer Test Certificate for Stabilizer, core material, winding copper & oil should be produced at the time of delivery
Supply and delivery of out door 18SWG CRCA sheet steel fabricated cubical type Cable Termination Box size with inside fitted 8 nos Incomming & Outgoing terminals and hinged type front door, with painted powder coated anticorrosive paint as per IP 55 as per direction of E.I.C
Supply & delivery at site horizontal type centrifugal self priming non-clog dewatering pump with horizontal type 415V ,50 Hz , three phase squirrel cage Induction motor including supply of channel base frame ,coupling and coupling guard complete set Discharge capacity : 5.7 M3/hr Total Head : 10 mtr. Suction/delivery- 40mm/35mm
Supply and delivery at site 40mm dia G.I pipe. With fittings i.e- Elbow, Union, Nipple. G.M Ball valve. C.I Foot valve etc for making suction and delivery line for dewatering pump.
PART-B ( Intallation)
Installation and commissioningof all items mentioned as in PART A (Exepet item no-17.2,17.3 21 & 26) including supply of all erection items, as required for installation of Submersible pumping machineris & Centrifugal pumping machineris , all valves, delivery pipe line, PDB cum MCC panel, Voltage Stabiliser, cable tray, indoor & outdoor light, laying of cable on cable tray including supplying all necessary items i.e- nut & bolt wather rubber gasket, with painting, jointing of cables termination cable soketing by suitable rated sockets, jointing the delivery header with H/L & L/L rising main, suporting piller and paining anticorrosive paint etc. including cost of gas cutting, welding etc. as required for complete the installation as per Hydraulic standard & IE rules in compliance by engaging skilled technician all complete as per Technical specification and upto entire satisfaction of EIC.
Installation & commissioning of above chlorinator with supplying & drawing of suitable length 1.1Kv grade 3x36/03(2.5Sqmm) single core standard FRLSh PVC insulated unsheathed copper wire(approved make) from installed panel board through 20mm size PVC rigid conduct FR(Precision make) incl. necessary fittings as required and continuous earthing from nearest earth grid. This includes the cost of making required height brick foundation base with neat cement finishing by supplying all required materials and testing the entire set as per direction of E.I.C(Height of tank foundation shall be higher than that chlorine machine)
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as required complete. (a) Depth of excavation not exceeding 1,500 mm. size of the trenches (W-1000mm, D-750mm L-300mtr)
Laying of 5 nos x 10 sq mm Al, Ar cable in an underground trench in single tier formation (horizontal), the trench size : W-1000 mm x 750 mm average depth, and minimum 200mm gap in between two cable also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed as per direction of E.I.C [300 mtr x 5nos = 1500mtr]
Laying of Al Ar cable through with fixing & laying of Cable along the lenth of River Bed 150mm dia GI delivery pipe line by the above supplyed M.S Clamp and G.I Wire as per direction of E.I.C a) 10 Sqmm 3 Core Al, Ar Cable (5nos x 200m = 1000m)
Supply, delivery Fixing at site G.I cable tray for laying of power cable and G.I Perforated cable tray for laying of control cable at Pump House having proper M.S. structural support as per technical Specifications given in NIT
Earthing & lightning protection for Pump House, electrical installation as per ISS and IE rules and as per technical Specifications given in NIT (2 nos Earth pit for each intallation)
Earthing of cable jointing box with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.incl GI bolts, double nuts, double washers . GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside)and CI hinged inspection cover of 36.56 cm x 35.56 cm with locking arrangement, and connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised strip By ISI-Medium GI pipe as per NIT Specification
Lighting and luminaries arrangement at the head works site including internal illumination of pump house building. as per technical Specifications given in NIT
Supply delivery and installation at site and storage of safety equipment like 6kg capacity Fire Extinguisher , sand bucket with bracket , rubber mats, shock treatment chart and first aid box, complete as per technical Specifications given in NIT
Cost of supply and delivery at site of calcium hypochlorite granule minimum CI content 60%-65% in air plastic jar (3kg each) as per direction of EIC. (Make PHE approved)
Supply and delivery of 2(Two) nos Colored cast Plastic Chair & 1(one) nos rectangular foldable potable table as per technical specication given in NIT
Providing & Installation of Solar Photo Voltaic Panels (Mono/Poly Crystalline) as per MNRE and NIeT Specification for size of solar plant with necessary PV array mounted on independent steel structure of suitable height & in a suitable direction to optimize panel use and withstand the wind pressure up to 200 Km /hour including necessary 3 phase inverter, cable, switch/circuit breaker/connector/junction box, earthing, lightening arrester, installation & commissioning with 5 year CMC. (a) The PV Modules should be mounted on hot dip galvanized metallic structure of adequate strength and as per drawing given in NIT (b) Components & parts used in the solar system including the metallic structure (MS) should confirm to the BIS (c) The rates of solar system includes compressive maintenance contract(CMC) for 5 years .
Construction of RCC foundation for mounting Steel structure for installation of Solar panel Array including earth excavation, sand filling, brick soling etc and as per speecification given in NIT.
Trial run of pumping machinery, through PLC / Automatic panel also operation of Pumping machineris, Chlorinator, Voltage Stabiliser etc. including operation of valves if required and guarding of installation as per direction of E.I.C.( for 90 days) for 2persion
Supply and delivery and storage of the following at site
Supply of swaged / stepped type steel tubular pole of 9 m long (410‐SP‐26) conformed to IS : 2713-1980. The length of bottom section shall be 5.0 mtr, middle section shall be 2.0 mtr & top of 2.0 mtr. The bottom section of the pole shall be 114.3 x 4.50mm dia, middle section of the pole shall be 88.9 x 4.05 mm dia & the top portion shall be 76.1 x 3.25 dia, 1.5 mtr. long MS bracket made out of 40 mm dia MS pipe shall be fixed on top of the pole for fixing light fiottings. The MS mounting bracket shall be fixed on top of the pole weight approx 92 Kg Make- Calcutta Pole/India Pole/jindal/Any approved make N.B- Certificate of Pole from manufacturer should be produce at the time of delivery
a) Single Arm
Supply delivery & fitting fixing of Operating Voltage 140V-270 V AC 50Hz ,LED light fixture having LM6 pressure die cast Al. housing pot optical reflector and heat resistant toughened Polycarbonate/ Glass cover complete set. M.No-BRP409 LED115 CW SLC FG PSU GR V2 of Philips make or equivalent model)
Supply and delivery of 6 sq.mm. 2 core PVC insulated XLPE Ar. AL conductor cable, As Per IS-7098 (Part 1) 2011 with Up To Date Amendment
Earth work in excavation of foundation trenches or drain in all sorts of soil ( including mixed soil but excluding laterite or sand stone) including removing spreading or stacking the spoil with in a lead of 75 m as directed .The item includes necessary a) Depth of excavation for additional depth beyond 1,500 mm. and upto 3,000 mm. but not requiring shoring.
Yard lighting
Erection of Single tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportionand dimension indicated below), having 600 x 600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finishand GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly Upto 9.0 mtr. Size 0.6x0.6x1.70 mts
Extra on items 1 & 2 above, for providing CC (6:3:1) base block (around the pole) dimension 0.60 x 0.60 x 0.76 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) suitable for alkathene/ polythene pipe entry as directed for street light wiring, incl. S & F 25cm x 25cm x 10cm GI Loop box, 16SWG & incl. drilled hole in pole
Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. where necy. incl. painting 250 x 250 x 100mm
Supply and inter connection of power line from light fixture to jointing box by the 1.5 sq mm x 2 nos pvc insulated HRFR 1.1 kv grade copper flaxible cable
Supply and fitting fixing of 20mm dia GI pipe Medium quality (TATA) from muffing to Joint box
Laying through Underground Trech Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed
Laying on Wall / surface with Saddles / clamps Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F M S saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : For 2 core 6 sqmm cable
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : i) 2 core 6 sqmm cable
Painting of Steel Tubular Pole of lengths and no. of coats of paint,as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint Upto 9.0 mtr. long pole
i) One coat of red lead/Zinc chromate priming
ii) 1st coat of synthetic enamel paint over the primer
ii) 2nd coat of synthetic enamel paint over the 1st coat
Excavation of soil for installation of Earth Electrode and filling & ramming. i) For Soft Soil
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
a) Supplying and fixing 240/415V MCB Isolator on din rail of existing DBs and necessary connection. i) 40Amp DP Make-Havels/L&T/Legrand/Any Approved make
b) Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection A) 16 A (SPN) Make-Havels
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment a) 2+4 way Make-Havells Enclosure (DHDPSNODRW04)
Add: 18% GST
Add: 1% Cess
DEY ENTERPRISE
WEST BENGAL ENGINEERING CO.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .