Ex Engineer
Ex Eng MID Ang HQ Awantipora
Creation of 100 kVA electric substation and allied works at LIS Narwah Ratnipora.
2023_IFC_202002_1
51/MIDA of 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
30 days
Narwa Ratnipora
Creation of 100 kVA electric substation and allied works at LIS Narwah Ratnipora.
2 documents required · 2 mandatory
₹500
Yes
Ex Engineer MID Ang HQ awantipora
₹10,023
Yes
25 Jan 2023
9 Jan 2023
25 Jan 2023
9 Jan 2023
24 Jan 2023
9 Jan 2023
Amount
Supply , installation , commissioning and Creation of pole mounted , outdoor type 100 KVA Electric Sub Station as per the technical specifications given here under - Specifications conforming to IS : 1180 (Part 1) 2014 with latest amendments . Type: HT/LT Transformer Type of cooling: ONAN. Operating conditions: Input =11000 volts Output =433 volts AC supply in 3- phase. Terminals: Input=3 No. HT bush rods with insulators, washer, nuts etc. Output=4 No. LT bush rods switch insulators, washers, nuts etc. Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved. The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals , conservator with oil level indicator , explosion vet and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS:1180 (Part 1) 2014 with latest amendments. The job also includes providing/fitting of MS angle iron belt ISA 50×50×6 mm for holding of transformer firmly & securely NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment and agreement for permanent connection with the concerned department. The testing and commissioning shall be completed only after obtaining above certificate.
Providing and fitting G.I Channels /Angle/ Flats of iron for cross, braces of sizes including clamps.
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs.
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing , Station Type .
Supply, Installation, Testing and commissioning of 11KV polymer Fuse set Horn Gap 3-phase 200 A suitable for vertical installation .
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm
Supply, installation, erection of 9 mtrs long H.T pope of specifications ST- 410 (SP-33) compete is base plate. The job further includes drilling of holes for installation of various accessories wherever required the job further includes G.I wire earthing of pole as per REC standard.
P/F of Galvanized nuts, bolts of various sizes as per site requirement.
P/F Danger Plate with clamps
Providing and fixing G.I Barbed wire for anti climbing/ anti-climbing devices
Painting of poles Red oxide
Painting of poles Aluminum paint
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq.mm ACSR (Galvanised steel reinforced) for fitment of various accessories
Supply, Installation and Testing of 35 Sq mm XLPE Aluminum H.T cable (ABC type ) of 11 KV grade with following specs. Size (cross sectional area in sq mm) = 3×35 Phases: Red, Yellow, Blue
providing and fitting of Anchoring clamps comprising clamp body , plastic wedge, steel bill bracket , straps and buckles or nuts and bolts required for holding of 3 – Core , 35 Sq. mm H.T AB Cable.
P/F of 11 KV cable termination kit for connecting 35 Sq mm XLPE cable (ABC type) with the existing HT line near tapping point and HT transformer.
Providing and fitting of LT Distribution box for H.T transformer with MCCB (200 A – 4 pole) For incomer and SFU for outgoing circuits. the capacity of H.T Transformer is 100 KVA
Earth work in excavation by manual means in trenches for foundation , drains ,pipes , cables (not exceeding 1.5 m in width ) and for shafts , wells , cesspits and the like not exceeding 10 sqm on plan , including dressing of sides and reaming of bottom lift upto 1.5 m , including getting out excavated earth and disposal of surplus excavated earth as directed. all kinds of soil.
Providing and laying of soling stone including manual compaction
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering . all work upto plinth level with 1: 1.5 : 3 mix ( 1 cement , 1.5 coarse sand , 3 graded stone aggregate 20 mm nominal size)
Providing & fitting of 3-phase prodigy meter (whole current meter) of following specification complete with all fixtures required at site. Type: 3 plase, 4 wire Measurements offered : KWh, KVARh, KVAh Range: 40 Amp to 200 Amp Battery: Lithium The Prodigy meter shall be enclosed in a strong steel box of appropriate size and thickness and suitable for mounting on pole and complete in all fixtures. The box shall have locking arrangement
Chemical Earthing for 100 KVA electric substation comprising of company fabricated earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (complete with insulator boots and accessories) as per relevant standards. Safe earthing electrode size : 80 mm dia , Length : 2000 mm Back fill compound : 30 kg
Providing and Fitting of 3.5-Core, XLPE, 1.1KV grade 300 square mm Armoured Aluminium Cable conforming to IS: 7098 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc.
FAYAZ AHMAD DAR
M/S MIR ELECTRICALS and MECHANICAL ENG WORKS
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .