| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹15.6 LAccepted-AOC | 1 | Accepted-AOC Lowest bidder | |
| 2 | 2₹19.4 L+₹3.2 L (19.4%)Rejected-AOC A 93 SECTOR 36 GREATER NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201308 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201308 | 2 | Rejected-AOC 2nd | |
| 3 | 3₹23.4 L+₹7.2 L (44.1%)Rejected-AOC | 3 | Rejected-AOC 3rd | |
| 4 | 4₹29.3 L+₹13.0 L (80.1%)Rejected-AOC | 4 | Rejected-AOC 4th | |
| 5 | 5₹33.0 L+₹16.8 L (103.0%)Rejected-AOC | 5 | Rejected-AOC 5th |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
29 Sept 2022, 6:00 pmClosed
GE AF TUGHLAKABAD
GE AF TUGHLAKABAD SANGAM VIHAR PO NEW DELHI 110080
REPAIR/MAINT OF LT CABLES, ACB PANELS, DC RECTIFIER AND CONNECTED ACCESSORIES IN TECH AREA AT 7 BRD, (AF) UNDER GE (AF) TUGHLAKABAD
2022_MES_541034_1
GE/TKD-39/2022-23
Open Tender
Civil Works - Others
Item Rate
180 days
GE AF TUGHLAKABAD
MES contractor enlisted having deposited Standing Security with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
8 documents required · 8 mandatory
₹500
GE AF TUGHLAKABAD
₹80,000
13 Dec 2022
1 Sept 2022
1 Oct 2022
8 Sept 2022
29 Sept 2022
15 Sept 2022
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc complete all as specified and directed by Engr-in-charge.
M&L for sand cushioning in trenches for protection of LT underground cable including watering and consolidation complete all as specified and directed by Engr-in-charge.
Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete all as specified and directed by Engr-in-charge.
Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete all as specified and directed by Engr-in-charge.
Returning filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed by Engr-in-charge.
Supply and lay in replacement or fixing or passing through pipe cable XLPE (FRLS) with aluminium conductor with heavy duty stranded,1100 volts of following size. Note: XLPE insulated PVC sheathing (heavy duty) armoured cable with aluminium conductor for working pressure up to and including 1100 volts to IS -7098 (Part-I) for pvc insulated cables complete all as specified and directed by Engr-in-charge.
25 Sqmm, 3½ Core .
95 Sqmm, 3½ Core .
35 Sqmm, 3½ Core .
Supply & Fixing in replacement MCCB 630 Amps 3 Pole breaking capacity 50 kA, 415 V, ICS=100 % of ICU Adjustable type suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
Supply & Fixing in replacement MCCB 630 Amps 4 Pole breaking capacity 50 kA, 415 V, ICS=100 % of ICU Adjustable suitable for existing LT panel type complete all as specified and directed by Engr-in-charge.
Supply & Fixing in replacement MCCB 400 Amps 4 Pole breaking capacity 50 kA,415 V, suitable for existing LT panel Adjustable type ICS=100 % of ICU complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB four pole , 415V , fixed thermal and magnetic setting of capacity 125Amp, breaking capacity 25 kA, ICS=100 % of ICU complete suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB four pole , 415V , fixed thermal and magnetic setting of capacity 100Amp, breaking capacity 25 kA, ICS=100 % of ICU complete suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB four pole, 415V, fixed thermal and magnetic setting of capacity 200Amp, breaking capacity 25 kA, ICS=100 % of ICU complete suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB four pole, 415V, fixed thermal and magnetic setting of capacity 250Amp, breaking capacity 25 kA, ICS=100 % of ICU complete suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB four pole , 415V , fixed thermal and magnetic setting of capacity 63 Amp, breaking capacity 36 kA, ICS=100 % of ICU complete suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in repairs of automatic transfer switch of capacity 400 Amp 4 pole, AC-31 A, 50 HZ, 415 V automatic/manual with inbuilt time delay complete all as specified and directed by Engr-in-charge.
S&F in repairs of automatic transfer switch of capacity 200 Amp 4 pole, AC-31 A,50 HZ,415 V automatic/manual with inbuilt time delay complete all as specified and as directed by Engr-in-charge.
Supply and fixing in replacement street light panel 3 phase, frame size 1, complete including mounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted on ground complete all as specified and as directed by Engr-in-charge. Make: Havells Cat Part No IHXTSI03060 or equivalent in Standard/Legrand
S&F in repairs of digital Voltmeter of range 0-500 Volts single phase, Class 01 of size 96 x 96mm suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
S&F in repairs of digital Amp meter with CTs 0-300 Amps single phase, class 01 of size 96 X 96mm suitable for existing LT panel complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement HRC fuse link RH type of capacity 63 Amp 415 Volt complete all as specified and directed by Engr-in-charge. Make: Cat part No IHHRH00063 of Havells or equivalent in Standard/Legrand
Supply and fixing in replacement HRC fuse link DIN type of rating 250 Amp 415 Volt complete all as specified and directed by Engr-in-charge. Make: Cat part No IHHCD01250 of Havells or equivalent in Standard/Legrand
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. Shall be dust and vermin proof, protection class (IP-42) and made of 2.00 mm thick CRCA Sheet & suitable frame work/ support made out of 40 x 40 x 5 mm Aluminium, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 Sqmm complete all as specified and directed by Engr-in-charge. Note: The scope of work also comprising of the following. (Location:……………………….. )
The panel manufacturer should have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-54 2. CPRI Short Circuit withstand strength should be 50kArms for 1.0 Sec with initial peak of 105kA 3. CPRI Certification Rated current for short circuit not less than 4000 A with rated insulation voltage 660V 4. ISO 9001 CERTIFIED
S&F in repairs of 3 pole power contactor MNX 325 2 NO + 2 NC of AC rating 325 Amps & AC rating 400 amps complete all as specified and directed by Engr-in-charge. Make: Cat Part No. CS94143 of L & T or equivalent in Havells.
S&F in replacement of APFC 100 KVAR panel cubical consist of sheet metal steel enclosure of 2 mm thick totally enclosed dust proof duly painted with powder coated (shade no 7035 Siemens grey) fully wired up and ready to connect lead & control lines complete all as specified and directed by Engr-in-charge comprising the following:
S&F in replacement of APFC 150 KVAR cubical consist of sheet metal steel enclosure of 2 mm thick totally enclosed dust proof duly painted with powder coated (shade no 7035 Siemens grey) fully wired up and ready to connect lead & control lines complete all as specified and directed by Engr-in-charge comprising the following:
Supply & Fixing in replacement and testing of cable jointing kit complete for 11 kv grade cable for Indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sq mm to 185 Sqmm complete all as specified and directed by Engr-in-charge.
All as per Sl item No 26.00 above but of size 240 Sqmm to 300 Sqmm complete all as specified and directed by Engr-in-charge.
All as per Sl item No 26.00 above but of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engr-in-charge.
M&L for supply, installation and testing for Maintenance free Grounding (Earthing) system complete buried directly in ground vertically (Earth pit not less than 10 feet below ground level) by making bore hole of 100 mm dia for inserting 01 No - 17MM dia Molecular copper bonded high tensile low carbon steel circular earth electrode of 3 mtr length with avg copper thickness of 100 microns alongwith Akaltech Environmental friendly grounding enhancing compound and heavy duty (HDPE) PVC pipe cap all in below the ground level and connected to copper earth wire 2 mm dia by means of same metal bolts, nuts and washers etc including protection pipe of of GI 15 mmm bore med grade upto 7.5 meter length and connection of earth lead to main distribution/LT panel board with copper lugs complete all as specified and directed by Engr-in-charge. Note: Necessary earth work, PVC pipe and all materials supplied by the contractor is deemed to be included in quoted rate).
S&F in replacement Energy saving 150 Watt environmental friendly, long life, exclusive innovative die cast aluminium IP65 flood light in LT pole with high power LEDs as light source, suitable for highlighting architectural features complete with all electrical accessories complete all as specified and directed by Engr-in-charge.
S&F in replacement, LED street light fitting of capacity 60 watt, cool white, complete with drivers and all accessories & making all necessary connection complete all as specified and directed by Engr-in-charge. Make: Havells Cat Part No. LHETBXU7PA6J060 or equivalent in Surya/Bajaj/Halonix.
S&F in replacement of galvanised Pipe of dia 100 mm, 'light grade' with all fitting, laid in trenches for passing of cable etc. complete all as specified and directed by Engr-in-charge.
S&F in replacement of LED Bulb two pin type suitable for fixing in lamp holder of capacity 5 Watt complete all as specified and directed by Engr-in-charge. Make: C&S cat Part No CHANDRA/5W or eqvt in Philips/Havells/Bajaj
S&F in replacement of Aluminium tube terminal of capacity 25 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 35 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 50 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 70 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 95 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 120 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 150 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 240 Sqmm complete all as specified and directed by Engr-in-charge.
S&F in replacement of Aluminium tube terminal of capacity 300 Sqmm complete all as specified and directed by Engr-in-charge.
Deepak Electricals
M/s Prakash Enterprises
Bluemax Associate
Surjit and Sons
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .