Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹10.5 L+₹57,150 (5.77%)Rejected-Finance 10 2 NARAYAN BAG INDORE M P | L2 | Rejected-Finance Being L2 |
| Sl No | Description | Qty | Unit | Sameer Auto Engineers L1 | S.S. Engineers L2 |
|---|---|---|---|---|---|
| 1.00 | Repairing/overhauling of existing outdoor-type LT panel boards/feeder pillar boxes of any size/type, fixed on PCC blocks, including cleaning with compressed air; tightening of all electrical connections to bus bars and switchgear; refixing of loose doors with proper fixing and locking arrangements, including necessary welding work as required; replacement of worn-out/burnt/rusted/loose lugs, door locks, nuts, bolts, hinges, washers, and internal wiring with suitable size (minimum 1.5 sq mm) PVC insulated copper conductor wire; repair to PCC work as required at site; and including disconnection of all cables from the bus bar, insulating the naked portions of Al/Cu conductors, and reconnecting the same after repair of the panel, along with proper connection of the main earth wire/lead to the panel body using lugs, complete all as specified and directed. | 15 | Each Job | 200 ₹3,000 Lowest | 200 ₹3,000 Lowest |
| 2.00 | Repairing/overhauling of existing indoor-type LT panel boards/bus bars/V-TPN DBs of any size/type, fixed on building walls, including cleaning with compressed air; tightening of all electrical connections to bus bars and switchgear; refixing of loose doors with proper fixing and locking arrangements, including necessary welding work as required; replacement of worn-out/burnt/rusted/loose lugs, door locks, nuts, bolts, hinges, washers, and internal wiring with suitable size (minimum 1.5 sq mm) PVC insulated copper conductor wire; repair to plaster work as required at site; and including disconnection of all cables/sub-mains from the bus bar, insulating the naked portions of Al/Cu conductors, and reconnecting the same after repair of the panel, along with proper connection of the main earth wire/lead to the panel body using lugs, complete all as specified and directed. | 8 | Each Job | 300 ₹2,400 Lowest | 300 ₹2,400 Lowest |
| 3.00 | M&L for preparing doors of existing LT panels/feeder pillar boxes with locking arrangements and gaskets, made of 2 mm thick CRCA sheet, including hinges and necessary welding work, complete all as specified and directed. | 6 | Sqm | 600 ₹3,600 Lowest | 600 ₹3,600 Lowest |
| 4.00 | Checking and identifying defects/fault points in LT/HT cables using a cable fault locator machine or by manual excavation, including taking out bricks from the trench up to the fault point along the cable route and re-laying the same using old bricks/sand, including refilling and making good the surface after rectification of the defect, complete all as specified and directed, for the following cable length:-
(a) 0 -200 m | 10 | Each Job | 2,500 ₹25,000 Lowest | 5,000 ₹50,000 |
| 4.01 | (b) 0 - 350 m
Note for item No 4.00 and 4.01: The cable fault locator machine, along with all T&P required for identifying the fault location, shall be arranged by the contractor, and the cost thereof shall be deemed to be included in the unit rate for fault detection using the machine or manually as directed by the Engr-in-Charge . | 15 | Each Job | 3,000 ₹45,000 Lowest | 6,000 ₹90,000 |
| 5.00 | Dismantling and taking out defective LT PVC/XLPE cables from trenches, including cutting and removing defective portions, and supply and making of cable joints using straight-through, cold-shrink type joints, including making connections of LT cables, megger testing, and restoration of electric supply, complete, including jointing materials, for the following sizes of cables. Joint :-
(a) 25 sqmm 3.5 core to 95 sqmm, 3.5 core | 14 | Each Job | 800 ₹11,200 Lowest | 1,000 ₹14,000 |
| 5.01 | (b) 120 sqmm 3.5 core to 300 sqmm 3.5 core | 10 | Each Job | 1,000 ₹10,000 Lowest | 1,200 ₹12,000 |
| 6.00 | Disconnecting and dismantling of damaged/unserviceable cables of any type/make, and supply and laying (in replacement) of XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, heavy-duty 1100 volts grade electric power cables with stranded aluminium conductors, including providing and fixing lugs at both ends of the cable, wrapping PVC tape over XLPE insulation, and testing, complete all as specified and directed, for the following sizes:-
(a) 25 Sqmm 4 core
Note: Excavation and earthwork, sand cushioning, brick protection, and GI pipe (where required) shall be measured and paid for separately. | 280 | RM | 250 ₹70,000 Lowest | 250 ₹70,000 Lowest |
| 6.01 | (b) 50 Sqmm 3.5 core | 180 | RM | 400 ₹72,000 | 350 ₹63,000 Lowest |
| 6.02 | (c) 95 Sqmm 3.5 core | 150 | RM | 700 ₹1,05,000 | 620 ₹93,000 Lowest |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
28 May 2026, 6:00 pmClosed
GE (MIS) Mhow
Garrison Engineer (Maint) Infantry School Mhow (MP) - 453441
REPAIR MAINT OF EXTERNAL ELECTRIC LT INFRASTRUCTURE ALONGWITH CONNECTED ITEMS UNDER GE MIS MHOW
2026_MES_759170_2
8900/GE (MIS)/Mhow
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (MIS) Mhow
All as per Tender document
8 documents required · 8 mandatory
₹500
GE (MIS) Mhow
₹20,000
Yes
3 Aug 2026
14 May 2026
30 May 2026
14 May 2026
28 May 2026
21 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Repairing/overhauling of existing outdoor-type LT panel boards/feeder pillar boxes of any size/type, fixed on PCC blocks, including cleaning with compressed air; tightening of all electrical connections to bus bars and switchgear; refixing of loose doors with proper fixing and locking arrangements, including necessary welding work as required; replacement of worn-out/burnt/rusted/loose lugs, door locks, nuts, bolts, hinges, washers, and internal wiring with suitable size (minimum 1.5 sq mm) PVC insulated copper conductor wire; repair to PCC work as required at site; and including disconnection of all cables from the bus bar, insulating the naked portions of Al/Cu conductors, and reconnecting the same after repair of the panel, along with proper connection of the main earth wire/lead to the panel body using lugs, complete all as specified and directed. | 15 | Each Job | - | - |
| 2 | Repairing/overhauling of existing indoor-type LT panel boards/bus bars/V-TPN DBs of any size/type, fixed on building walls, including cleaning with compressed air; tightening of all electrical connections to bus bars and switchgear; refixing of loose doors with proper fixing and locking arrangements, including necessary welding work as required; replacement of worn-out/burnt/rusted/loose lugs, door locks, nuts, bolts, hinges, washers, and internal wiring with suitable size (minimum 1.5 sq mm) PVC insulated copper conductor wire; repair to plaster work as required at site; and including disconnection of all cables/sub-mains from the bus bar, insulating the naked portions of Al/Cu conductors, and reconnecting the same after repair of the panel, along with proper connection of the main earth wire/lead to the panel body using lugs, complete all as specified and directed. | 8 | Each Job | - | - |
| 3 | M&L for preparing doors of existing LT panels/feeder pillar boxes with locking arrangements and gaskets, made of 2 mm thick CRCA sheet, including hinges and necessary welding work, complete all as specified and directed. | 6 | Sqm | - | - |
| 4 | Checking and identifying defects/fault points in LT/HT cables using a cable fault locator machine or by manual excavation, including taking out bricks from the trench up to the fault point along the cable route and re-laying the same using old bricks/sand, including refilling and making good the surface after rectification of the defect, complete all as specified and directed, for the following cable length:-
(a) 0 -200 m | 10 | Each Job | - | - |
| 4.01 | (b) 0 - 350 m
Note for item No 4.00 and 4.01: The cable fault locator machine, along with all T&P required for identifying the fault location, shall be arranged by the contractor, and the cost thereof shall be deemed to be included in the unit rate for fault detection using the machine or manually as directed by the Engr-in-Charge . | 15 | Each Job | - | - |
| 5 | Dismantling and taking out defective LT PVC/XLPE cables from trenches, including cutting and removing defective portions, and supply and making of cable joints using straight-through, cold-shrink type joints, including making connections of LT cables, megger testing, and restoration of electric supply, complete, including jointing materials, for the following sizes of cables. Joint :-
(a) 25 sqmm 3.5 core to 95 sqmm, 3.5 core | 14 | Each Job | - | - |
| 5.01 | (b) 120 sqmm 3.5 core to 300 sqmm 3.5 core | 10 | Each Job | - | - |
| 6 | Disconnecting and dismantling of damaged/unserviceable cables of any type/make, and supply and laying (in replacement) of XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, heavy-duty 1100 volts grade electric power cables with stranded aluminium conductors, including providing and fixing lugs at both ends of the cable, wrapping PVC tape over XLPE insulation, and testing, complete all as specified and directed, for the following sizes:-
(a) 25 Sqmm 4 core
Note: Excavation and earthwork, sand cushioning, brick protection, and GI pipe (where required) shall be measured and paid for separately. | 280 | RM | - | - |
| 6.01 | (b) 50 Sqmm 3.5 core | 180 | RM | - | - |
| 6.02 | (c) 95 Sqmm 3.5 core | 150 | RM | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.22 MB
BOQ_857049.xls
BOQ • 0.43 MB
Tenderandspecialcondition8900.pdf
Tender Documents • 0.51 MB
ParticlularSpecifications8900.pdf
Tender Documents • 0.50 MB
ListOfMake8900.pdf
Tender Documents • 0.39 MB
DetailsOfWorkInAndInHand.pdf
Additional Documents • 0.10 MB
Amendment2.pdf
PDF • 0.01 MB
Amendment1.pdf
PDF • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .