Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.1 LAccepted-AOC KOIL KOIL PULWAMA PULWAMA JAMMU KASHMIR 192301 | PULWAMA | JAMMU AND KASHMIR | 192301 | ₹39.1 L | L1 | Accepted-AOC Accepted being L1 bidder. |
| 2 | L2₹39.7 L+₹53,450 (1.37%)Rejected-Finance | ₹39.7 L+₹53,450 (1.37%) | L2 | Rejected-Finance Rejected being other than L1 bidder |
| 3 | L2₹47.9 L+₹8.8 L (22.4%)Rejected-Finance | ₹47.9 L+₹8.8 L (22.4%) | L2 | Rejected-Finance Rejected being other than L1 bidder |
| 4 | L3₹40.2 L+₹1.1 L (2.68%)Rejected-Finance | ₹40.2 L+₹1.1 L (2.68%) | L3 | Rejected-Finance Rejected being other than L1 bidder |
| 5 | L4₹40.7 L+₹1.6 L (3.96%)Rejected-Finance | ₹40.7 L+₹1.6 L (3.96%) | L4 | Rejected-Finance Rejected being other than L1 bidder |
| Sl No | Description | Qty | Unit | FG CONSTRUCTION L9 | CHINAR CONSTRUCTION TRADERS L2 | L-7 Primewave Communications L6 | ALCO Engineers Private Limited L12 | Electromech Engineers L8 | M/S BASHIR AHMAD AND SONS L10 | M/S ABBAS M. ENTERPRISES L4 | M/S ZAHOOR AHMAD KHAN L7 | ANIKET TRADERS L11 | M/S Bali Agencies L5 | M/s Gh Qadir and Sons L1 | KHAJURIA ENGINEERS L3 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of silent Diesel Engine Generating set comprising of Diesel Engine liquid cooled (latest CPCB- IV+ norms compliance) and alternator of capacity not less than 100 KVA, 3 phase, 415 Volt, 50 HZ, 0.8 power factor at 1500 RPM, both coupled and aligned on a common base frame complete with standard accessories like MS Fuel Tank AVM pads fitted on common base frame Control Panel and outdoor type AMF panel mounted on common trolley (DG + AMF) with digital measurement devices, alongwith acoustic enclosures conforming to latest IS 10002, ISO-3046, BS 5514 and complete in all respects including lubricant oil filled in engine, DG Set Manual and cold start kit suitable for (-15 degree Celsius) temperature.
Prime Mover:- Prime mover suitable for driving alternator 100 KVA capacity having suitable BHP at 1500 RPM for rated output for alternator in accordance with latest BE/IS specifications with electric starting device with all standard fittings and 1 Nos batteries of 12 Volt suitable AH or equivalent with battery charger built in AMF panel with one set of connecting leads of proper size copper cable. Engine over speed safety mechanism shall be incorporated. The DG Set should also comprise remote monitoring system for tracking genset health, operation parameters, genset utilisation and live performance tracking.
The Engine shall be equipped
ENGINE INSTRUMENT AMF PANEL:- All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lubricating oil pressure, coolant temperature, battery charging ammeter, RPM, Hour meter and starting switch etc. The auto start and auto stop panel consisting of line voltage monitoring 24 volts 10 Amps battery charger.
FUEL TANK:- Suitable capacity with inlet and outlet arrangement, air vent and drain plug arrangement. | 2 | Each | 19,25,500 ₹38,51,000 | 18,00,000 ₹36,00,000 | 18,25,000 ₹36,50,000 | 21,25,000 ₹42,50,000 | 16,70,000 ₹33,40,000 Lowest | 18,50,000 ₹37,00,000 | 17,50,000 ₹35,00,000 | 17,27,000 ₹34,54,000 | 18,40,000 ₹36,80,000 | 18,49,000 ₹36,98,000 | 17,00,000 ₹34,00,000 | 19,50,000 ₹39,00,000 |
| 2.00 | M&L and fabrication of trolley to accommodate 100 KVA DG Set with having sufficient space all around the DG Set comprising of 04 wheel of size 7.50x16, toeing hook, triangular draw bar detachable type made of MS Channel of suitable thickness, spring loaded steel towing hook of suitable thickness around turn table made of heavy duty thick plate with ball bearing, manual locking brake system with suitable leaf spring, manual slid and landing jack with pin lock fitted on all four corners complete with spray painting having carrying capacity 05 to 06 ton for mounting 100 KVA DG Set . Trolley should comprise of 04 Nos of Earthing spike with 2.5 sqmm copper cable of length 10 metre each along with hammer.
Note:- The trolley should be such designed that there is cable holding manual operated drum provision to accommodate 70 sqmm XLPE LT cable and trolley can be moved to and fro in any direction. | 2 | Each Job | 2,75,000 ₹5,50,000 | 1,70,000 ₹3,40,000 | 1,85,000 ₹3,70,000 | 2,50,003.5 ₹5,00,007 | 4,10,000 ₹8,20,000 | 3,80,000 ₹7,60,000 | 2,80,000 ₹5,60,000 | 3,25,000 ₹6,50,000 | 3,99,000 ₹7,98,000 | 1,85,000 ₹3,70,000 | 2,50,000 ₹5,00,000 | 50,000 ₹1,00,000 Lowest |
| 3.00 | Supply, lay, connect test and commissioning of LT cable XLPE insulated screened PVC tape inner sheathed, armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional area of 70 Sqmm 3.5 Core confirming to IS:7098 Part-I laid in cable drum mounted on trolley complete including lugs all as directed. | 50 | RM | 750 ₹37,500 | 569 ₹28,450 | 1,550 ₹77,500 | 800 ₹40,000 | 500 ₹25,000 | 350 ₹17,500 | 200 ₹10,000 Lowest | 775 ₹38,750 | 666 ₹33,300 | 315 ₹15,750 | 300 ₹15,000 | 400 ₹20,000 |
Tender Value
₹43.7 L
EMD Value
₹87,400
Closing Date
11 May 2026, 6:00 pmClosed
GE (AF) AWANTIPUR
GE (AF) AWANTIPUR C/o 56 APO PIN-937208
PROVN OF DG SETS AND ALLIED WORKS AT CERTAIN LOCATIONS AT AF STN AWANTIPUR
2026_MES_761061_1
GE (AF) AWA-01/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) AWANTIPUR
AS PER NIT AND TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE (AF) AWANTIPUR
₹87,400
Yes
9 Sept 2026
20 Apr 2026
13 May 2026
20 Apr 2026
11 May 2026
4 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| - | Supply, installation, testing and commissioning of silent Diesel Engine Generating set comprising of diesel enaine liauid cooled (latest CPCB - IV+ norms compliance) and alternator of capacity not less than 100 KVA, 3 phase, 415 volt, 50 HZ, 0.8 power factor at 1500 RPM, both coupled and aligned on a common base frame complete with standard accessories like MS fuel tank AVM pads fitted on common base frame Control panel and outdoor type AMF panel mounted on common trolley (DG + AMF) with digital measurement devices, along with acoustic enclosures conforming to latest IS 10002, ISO - 3046, BS 5514 and complete in all respects including lubricant oil filled in engine, DG Set Manual and cold start kit suitable for (-15 degree celsius) temperature.
Prime Mover:- Prime mover suitable for driving alternator 100 KVA capacity having not less than 130 BHP at 1500 RPM for rated output for alternator in accordance with latest BE/IS specifications with electric starting device with all standard fittings and 1 Nos batteries of 12 volt 100 AH or equivalent with battery charger built in AMF panel with one set of connecting leads of 35 sqmm size copper cable. Engine over speed safety mechanism shall be incorporated.The DG Set should alsc comprise remote monitoring system for tracking genset health,operation parameters,genset utilisation and live performance tracking.
The Engine shall be equipped
ENGINE INSTRUMENT AMF PANEL:- All relevant parameters shall be conventionally displayed on complete panel thereby providing easy monitoring of lubricating oil pressure, coolant temperature, battery charging ammeter, RPM, Hour meter and starting switch etc including 4 Nos GI Strip size of 25x4mm complete for DG set at site. The auto start and auto stop panel consisting of line voltage monitoring 24 volts 10 amps battery charger.
FUEL TANK:- The 100 Itr capacity with inlet and outlet arrangement, air vent and drain plug arrangement. | - | Each | - | - |
| - | M&L and fabrication of trolley to accomodate 100 KVA DG Set with having sufficient space all around the DG Set comprisina of 04 wheel of size 7.50x16, toeing hook,triangular draw bar detachable type made of MS Channel 100x50 mm, spring loaded steel towing hook of 36mm around turn table made of heavy duty thick plate with ball bearing,manual locking brake system with suitable leaf spring,manual slid and landing jack with pin lock fitted on all four corners complete with spray painting having carrying capacity 05 to 06 ton for mounting 100 KVA DG Set . Trolley should comprise of 04 Nos of Earthing spike with 2.5 sqmm copper cable of length 10 metre each along with hammer.
Note:- The trolley should be such designed that there is proper space for holding LT Cable and trolley can be moved to and fro in any direction. | - | Each Job | - | - |
| - | Supply, lay, connect test and commissioning of LT cable XLPE insulated screened PVC tape inner sheathed, armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional area of 70 Samm 3.5 Core confirming to IS:7098 Part-I laid in cable drum mounted on trolley complete including lugs all as directed. | - | RM | - | - |
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
Tender01.pdf
Tender Documents • 1.61 MB
BOQ_852491.xls
BOQ • 1.18 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .