Tender Value
₹21.8 L
EMD Value
₹43,600
Closing Date
23 Jan 2020, 6:00 pmClosed
CWE AF Borjhar
Commander Works Engineers AF Military Engineer Services Borjhar PO Borjhar Airport Guwahati 15 Assam Pin 781015
REPAIR/PERIODICAL MAINTENANCE OF TRANSFORMER, VCB, RMU, HT CABLE AND OTHERS CONNECTED WORKS AT AIR FORCE STATION BORJHAR, GUWHATI UNDER GE (AF) BORJHAR
2019_MES_301958_1
CWE (AF)/BOR/TOKEN-22 OF 2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BORJHAR
All contractors enlisted with MES in Class E and above and category b ii having deposited Standing Security of Rs 50000 with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
8 documents required · 8 mandatory
₹500
GE AF Borjhar
₹43,600
Yes
29 Jan 2020
28 Nov 2019
24 Jan 2020
28 Nov 2019
23 Jan 2020
12 Dec 2019
Amount
SCHEDULE 'A' PART-I (B/R PORTION)
Disconnecting all in coming and outgoing cables, removing the 400 to 500 KVA 11000/433 Volt distribution transformer from the platform / two pole structure / floor and loading it in the vehicle carefully using crane and transporting it to the contractor's workshop, carry out the required repairs and transport the transformer back to the site , install it, reconnect all the incoming and out going cables by properly crimping using lugs of suitable size lugs, taping the bushes / bus bars, using insulation tape and testing complete all as directed.
All as per serial item No. 01 above but for distribution transformer of capacity 200 to 315 KVA 11000/433 Volt
All as per serial item No. 01 above but for distribution transformer of capacity 100 to 150 KVA 11000/433 Volt. (Note for seral item No. 1,2 and 3:- Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side , rewinding, dehydration of oil shall be measured and paid separately as supply only under respective items.)
Draining out all the transformer oil ,dismantling and inspection of transformer core and winding including taking out burnt out winding/insulation of LV / HV strips/coils , Reassembling of core and winding, drying out in vacuum chamber till specified IR values are obtained and providing new insulation materials, gasket, nuts , bolts, checking of leakages and rectifying the same by welding etc and replacement of silica gel for transofomer of 400 to 500 KVA 11000/433 Volt capacity all as directed. Note: (i). All new materials required such as winding wire, LV/HV bushes, Silica gel breather etc shall be measured and paid for separately as supply only under respective items. (ii) Cost of trnasformer oil for cleanaing by hoisting down shall be deemed included in the rate quoted. (iii) Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side and air horn surge arrester for replacement shall be measured and paid separately as supply only under relevant item.
All as per serial item No. 04 above but for distribution transformer of capacity 200 to 315 KVA 11000/433 Volt
All as per serial item No. 04 above but for distribution transformer of capacity 100 to 150 KVA 11000/433 Volt.
M&L for winding of 11/0.433 KVHV coils,using new copper wire/strip of proper size including insulating materials (double insulation)as per existing size of core of transformer including heating , varnishing complete all as directed.
M&L for winding of 11/0.433 KV LV coils coils,removing U/S insulating materials, double reinsulation with insulating papers using same copper strip and rewinding as per existing size of core of transformer including heating , varnishing complete all as directed.
Supply only breather assembly of approved make filled with silica gel suitable for transformer of capacity 100 to 150 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 09 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 09 above but for transformer of capacity 400 to 500 KVA 11000/433 Volt.
Supply only brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformer of capacity 400 to 500 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 12 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 12 above but for transformer of capacity 100 to 150 KVA 11000/433 Volt.
Supply only brass spindle for terminal on LT side threaded complete with nut, washers etc of suitable dia for transformer of capacity 400 to 500 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 15 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 15 above but for transformer of capacity 100 to 150 KVA 11000/433 Volt.
Supply only ceramic bushing and Gaskey on LT side of transformer of capacities 400 to 500 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 18 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 18 above but for transformer of capacity 100 to 150 KVA 11000/433 Volt.
Supply only ceramic bushing and Gaskey on HT side of transformer of capacities 400 to 500 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 21 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt
All as per serial item No. 21 above but for transformer of capacity 100 to 150 KVA 11000/433 Volt.
Supply and fixing complete gasket (Cock sheet) 6 mm thick of transformer of capacity 400 to 500 KVA 11000/433 Volt including conical rubber bush complete all as directed.
All as per serial item No. 24 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 24 above but for transformer of capacity 100 to 150 KVA 11000/433 Volt.
Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 35 to 40 KV at 2.5 mm gap in existing position of transformer of any capacity and transformer oil for topping up at various sub station complete all as directed. ( NOTE: The contractor has been submit test report for dielectric strength. Transformer oil used for TOP UP measured and paid separately under respective item)
Supply and pouring of new transformer oil to achieve a di-electric strength up to 60 KV in 4 mm gap conform to IS-335-1983 with sealed barral contains each 210 litre complete all as directed. Make : Sabita/Golf/Power Oil.
M&L for painting of transformer after cleaning the surface of transformer by rubbing with emery paper to remove oil stains, dust etc and applying one coat of snthetic enamel paint by spray paint including writing SM No/MES No , for the capacity of transformer of 400 to 500 KVA 11000/433 Volt complete all as directed.
All as per serial item No. 29 above but for transformer of capacity 200 to 315 KVA 11000/433 Volt.
All as per serial item No. 29 above but for transformer of capacity100 to 150 KVA 11000/433 Volt.
Shifting of transformer 100/250 KVA from one SUB-STATION to another after disconnection of LT & HT Side Connections, Installation, Commissioning and connecting LT & HT Side including loading to in the vehicle and unloading and trasporting complete all as directed.
S&F in repair aluminium earthing lead of size 32 x 6 mm including all fixing accessories complete all as directed.
M&L for broken stone or boulders hardcore of gauge not exc. 63mm, deposited, spread and levelled in layers not exc. 150 mm thick, watered and rammed to a true surface, complete all as specified and directed.
M&L for PCC (1:3:6) type C2 (using 40 mm Graded cushed stone aggregate) as in foundation of poles, stays, etc. including formwork if required complete all as specified and as directed.
M&L for PCC (1:2:4) type B1 (using 20 mm Graded crushed stone aggregate) as in coping of poles, etc. including formwork if required complete all as specified and as directed.
M&L for brick work with Sub Class 'B" bricks straight or curved on plan exceeding 6 meter mean radius in cement mortar (1:4) complete all as specified and directed.
M&L for rendering 15 mm thick in Cement Mortar (1:4) on fair faces of brick work or concrete surface finished even and smooth (without using extra cement) complete all as specified and directed.
S&F mild steel screw bolts (Machine Made) with hexagonal head at one end and screwed the other ends, each screwed end to be fitted with washers and one hexagonal nut, diameter of Shank 5 to 100 mm length of bolt exc 100 mm but not exc. 150 mm, complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and n exc 1.5 mtr in depth and getting out in soft/ loose soil for laying of cables / GI pipe, foundation of pole, stay etc complete all as specified and directed.
All as per item No 41 above but exc 1.5 mtr and not exceeding 3.00 mtr depth .
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm in soft / loose soil complete all as specified and directed.
Removing surplus excavated soil n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed.
Supply and spreading dry sand of approved quality for cushioning of UG cable laid in trenches all as specified and directed. (NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only shall be Measured and Paid for).
Supply and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed.
All as per item No 45 above but using old serviceable concrete cable cover.
Dismantling and taking down unserviceable MS cross arms bracings and supports, clamps nut bolts complete all as directed.
Material and labour for mild steel cross arms, bracing, supports, clamps and back plates fabricated from structural steel section including nuts,bolts washers,welding,bending cold or hot , drilling holes for bolts in any shape/size as directed including painting with two coats of synthetic enamel paint of approved colour over a coat red oxide primer complete all as specified and directed.
Dismantling and taking down of unserviceable HT insulators any size/type/capacity and keeping aside for safe custody for further disposal complete all directed.
Supply and fixing Pin type Porcelain vitreous white brown or green insulator including one galvanized mild steel spindle two galvanized iron washers and one galvanized iron nut 150mm height 150 mm dia for 11000 volts grade including dismantling old insulator complete all as specified and as directed.
Supply and fixing Single Disc type insulator assembly porcelain vitreous for tension with tension clamps for conductors working pressure 11000 Volts including dismantling old insulator complete all as specified and as directed.
Taking out / down faulty serviceable 11KV, HT UG cable in existing trenches/duct/on HT poles of nominal cross sectional area from 95 to 185 Sqm, 3 core including disconnecting, PCC covers, GI Pipe etc. of any descriptions, including segregation of serviceable materials viz PCC cable cover, GI Pipes etc. and tracing the location of fault and keep in safe custody for re-use complete all as directed NOTE : (i) Earth work shall be measured and paid for separately under relevent items (ii) Serviceable cable covers will be kept aside for re-use (iii) Serviceable GI pipe will also be kept aside for re-use
Supply, laying jointing & testing HT electric cable heavy duty 11 KV(E) grade, XLPE insulated screened , with sound compacted aluminium conductor, conductor screening with extruded semi- conducting layers insulation screening with copper tape covers laid up with PVC (ST-2) extruded inner sheathing galvanized steel strip armored PVC (ST-2) outer sheathed cable conforming to IS-7098 ( Part-II) amended of size 95 Sqmm, 3 core laid in trenches/ cable duct complete all as specified and as directed .
All as per serial Item No. 53 above but for 11KV (E) grade cable of nominal cross sectional area of 185 sqmm, 3 core
Laying only serviceable HT cable obtain from serial itme No 52 above XLPE insulated with aluminium conductor of size from 95 to 185 sqmm, 3 core, 11000 volts grade complete all as directed.
M&L for PCC cable route marking of size 150 x 50 x 600 mm for Under Ground cable complete all as specified and directed.
Dismantling & taking out the old steel tubular HT poles complete all as directed.
Supply and erecting steel tubular swaged welded pole type 410 SP-55 (11 mtr long) including cast iron Base plate Final Taper Plug Cap Mild steel bolts Nuts Screws etc including applying two coat of black Bituminous Paint internally and externally up to Planting Depth and applying with two coats of aluminium Painting over a coat of red oxide primer including writing MES LT Pole and Blue marking reflector strip with synthetic enamel paint (first Grade quality ) including dismantling old poles complete all as directed. Note: Earth work and PCC work will be measured and paid separately
S&F in repair Lightning arresters expulsion type with all fittings, transmission class, discharge capacity 65 kilo amp for 11000 V complete all as specified and directed.
Dismantling of ACSR conductor, service feeder or distributor span from its existing position complete all as directed.
Supply, stringing and fixing on existing/new poles, ACSR conductor of any type/ size including fixing to insulators with binding wire complete all as specified and directed.
M&L for Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered complete all as directed.
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 25x20cm size complete all as directed.
S&F in repair Triple pole switch air break gang operatd device, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 amps for 11000 volts complete all as specified and directed.
Supply and fixing in repairs Polymer based dropout fuse unit complete set suitable and including for 11 KV, HT outdoor and dropout type of capacity 200 Amps including jumper connections with copper flexible designed jumper and testing and commissioning complete all as directed.
M&L for detecting carefully the fault location of HT UG cable of size 95 sq mm to 185 sq mm 3 core either HT cable fault locator machine or any other method and taking out the/remove the faulty portion of cable from undergound /over all length respectively inc meggering /connecting/testing on completion all as directed by EIC. (i) Excavation & earth work shall be deem to be included in the unit rate of this item of work.(ii) Stright throught joint for HT cable shall be measured and paid seperatly under respective item of this schedule (iii) Actual detected fault shall be paid under this item. Dummy located trail shall not measured & paid under this item
S&F in repair straight through Cable joining kit for 11 KV (Earthed) grade cable for Indoor termination Cold shrink type joint complete with joining material and accessories suitable for 120 Sqmm to 185 Sqmm, 3 core XLPE armoured aluminium conductor cable complete all as specified and directed.
All as per serial Item No. 67 above but for straight through Cable joining kit for 11 KV (Earthed) gradecable of nominal cross sectional area of 50 sqmm to 95 Sqmm, 3 core
All as per serial Item No. 67 above but for out door end termination Cable joining kit for 11 KV (Earthed) gradecable of nominal cross sectional area of 120 sqmm to 185 Sqmm, 3 core
All as per serial Item No. 67 above but for out door end termination Cable joining kit for 11 KV (Earthed) gradecable of nominal cross sectional area of 50 sqmm to 95 Sqmm, 3 core
All as per serial Item No. 67 above but for in door end termination Cable joining kit for 11 KV (Earthed) gradecable of nominal cross sectional area of 50 sqmm to 95 Sqmm, 3 core
M & L for Light grade GI pipe of size 100 mm dia with all fitting for cable protection complete all as specified and directed
S&F in repair chain Link Fencing 100 X 100mm Mesh or Cages with 3.15mm dia Mild Steel Galvanised Wire, lapped, Straining and Binding with including Mild Steel Wire (annealed) not less than 0.9mm dia, complete all as specified and as directed.
Horizontal boring holes under road, hardstanding by trenchless techonology using ultra sound techinique/mechanical process in soft/loose soil suitable for insertion GI pipe 100 mm bore dia complete all as directed.
Servicing, calibration, trouble shooting, repairing & adjusting of over current relay, earthfault relay, connected accessories, master control display, LED indicator, thermostate, cleaning all contacts with CRC spray of 11 KV Ring main unit, 50 Hz by qualified technical personnel to make functional in all respect including identifying the defective parts including replacement of defective parts complete all as directed Note:- Spare parts shall be paid under relevant item as "Supply only". Make of RMU: CG
Supply only self power relay CGI 14 S for RMU complete all as directed.
Supply only HT 11 KV triping coil suitable for over load, Earth fault and under voltage complete all as directed.
Supply only R-Y-B healthy indication lamp complete all as directed.
S& Fixing Voltmeter of rating 0-1300 volt complete all as directed.
Supply only drop out (swing out ) fuse element is an expulsion type of rating 10 Amp complete all as directed. Make : RMCO/Shivon Electrical
Supply only drop out (swing out ) fuse element is an expulsion type of rating 20 Amp complete all as directed. Make : RMCO/Shivon Electrical
Supply only drop out (swing out ) fuse element is an expulsion type of rating 30 Amp complete all as directed. Make : RMCO/Shivon Electrical
Supply only drop out (swing out ) fuse element is an expulsion type of rating 40 Amp complete all as directed. Make : RMCO/Shivon Electrical
Opening of VCB 11 kV of capacity 400 Amps to 800 Amps of any Make for servicing, cleaning, tightening of loose mechanical mechanism, greasing inspection of busbar, CTs/PTs, internal wiring of control panel, indicators, measuring of IR value, calibration of relays, replacement of unserviceable spare parts, testing of tripping system and removing all type of dust and settled dirt by mechanical means including testing complete all as directed. Note: -Spare parts except wiring shall be measured & paid separately.
M&L for painting steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint complete all as directed.
Repairs to drop out fuse unit upto 400 Amps, 11 KV capacity including replacement of worn out nut bolts,washers,of suitable size /unserviceabele spares and jumper connections for smooth functioning of the devices all as directed. Note :- (i) Minor spares / consumeable items deemed to be included in the quoted rates (ii) Unserviceable spares such as fix top / lower contact, insulators replaced will be measured and paid seprately as"Supply only" under respective items
Supply only fix top contact/L contact for drop out fuse complete all as directed.
Supply only Fix lower contact for drop out fuse complete all as directed.
Supply only Post insulators of drop out fuse complete all as directed.
M&L for ACSR conductor(Ferret) jumper connections of length exceeding 0.75 metre but not exceeding 1.50 metre both ends secured with suitable aluminium lugs or one end with aluminium lugs and other end plain for binding with conductor encased with polythylene pipe, RYB colours of suitable dia complete all as directed.
All as per serial item No. 90 above but for length exceeding 1.5 mtr length but not exceeding 2.5 metre.
All as per serial item No. 90 above but for length exceeding 2.5 mtr length but not exceeding 3.00 metre.
Dismantling 11KV air break gang operated switches of 400 Amps current rating, vertical / horizontal mounted including insulators and operating mechanism for insulators and operating mechanism for repair / replacement of broken / worn out components and insulators etc. or carrying to store yard for safe custody for further repair and refixing of the same complete all asdirected. Note :- Unserviceable spare/components for replacement will be measured and paid separately under respective Sch 'A' items as "Supply only"
Supply only male contact/moving contact blade of gang operated AB switch devices suitable for 11 KV complete all as directed.
Supply only female contact /fix contact jaw for gang operated AB switch devices complete all as directed.
Supply only tinned copper flexible jumper 400/200 Amps complete all as directed.
Supply only post top Polymer insulators of gang operated AB switch devices complete all as directed.
Supply only middle post Polymer insulators of gang operated AB switch devices complete all as directed.
Supply only bottom post Polymer insulators of gang operated AB switch devices complete all as directed.
Supply only MS jumper carrier complete all as directed.
Supply only back connector plate complete all as directed.
M&L for triming of tree branches( touching HT/LT OH line ) upto 10 cm girth at any height carefully after taking proper shutdown including suitable disposal of cut of tree branches complete all as directed. Note : Tool & plants incuding safety measures equipment like belt ladder & ropes etc ahall be arranged by the contractor at his own cost
Earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level sorrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt fliing in alternate layers etc and connected to and including 32 x 4 mm GI strip upto 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 20 mm dia GI pipe connected to main control board and GI pipe medium grade 40 mm bore for watering and including funnel, wire mesh, charcoal salt etc RCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate) including excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009
M/s Nice Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .