EE PWD Elec Dn Ajmer
EE PWD Elec Dn Ajmer
Air Conditioner Work under construction of Drug Ware House at JLN Medical College, Ajmer
2026_CEPWD_575895_11
NIT10 2026-27 EE PWD Elec Dn Ajmer
Open Tender
Electrical Works
Percentage
180 days
Ajmer
Refer NIT Documents
4 documents required · 4 mandatory
₹500
Egras Challan EE PWD Elec Dn Ajmer 7820
₹19,060
Yes
31 Jul 2026
19 Jul 2026
24 Jul 2026
19 Jul 2026
24 Jul 2026
19 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 2Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. | |||||
| 2.1 | 4.0 Sq. mm | - | - | - | - |
| 2.2 | 4 core | 15 | Mtr. | 315.06 | ₹4,725.9 |
| 3Supply , Installation, Testing and Commissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Min 5 year Original Equipment Manufacturer (OEM) warranty of both compressor and Printed Circuit Board (PCB). | |||||
| 3.1 | Cooling capacity 5000-5300 Watt, ISEER not less then 3.8 , ( 1.42 Tr to 1.5 Tr ), 3 star | 5 | Each | 43,449.96 | ₹2,17,249.8 |
| 3.2 | Cooling capacity 6800-7000 Watt, ISEER not less then 3.8 , ( 1.93 Tr to 2.00 Tr ), 3 star | 11 | Each | 59,713.9 | ₹6,56,852.9 |
| 4Supply, installation, testing and commissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 with 7 mil Glass Cloth and 3 coats of anti UV paint (on area which is exposed to weather) including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. | |||||
| 4.1 | 15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) | 10 | Mtr. | 1,144.6 | ₹11,446 |
| 4.2 | 6.4 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) | 10 | Mtr. | 428.34 | ₹4,283.4 |
| 5Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. | |||||
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.83 MB
Tendernotice_2.pdf
PDF • 0.37 MB
Tendernotice_3.pdf
PDF • 23.83 MB
Tendernotice_4.pdf
PDF • 4.91 MB
BOQ_1024017.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .