Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.1 LAdmitted-Finance | ₹5.1 L | L1 | Admitted-Finance |
| 2 | L2₹5.4 L+₹28,090 (5.51%)Admitted-Finance | ₹5.4 L+₹28,090 (5.51%) | L2 | Admitted-Finance |
| 3 | L3₹5.6 L+₹53,552 (10.5%)Admitted-Finance | ₹5.6 L+₹53,552 (10.5%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical 2ND FLOOR 208 D BLOCK AJNARA COMPLEX VIVEK VIHAR DELHI 110095 | SHAHDARA | DELHI | 110095 | - | - | Rejected-Technical Technically Not Qualified |
| Sl No | Description | Qty | Unit | SUPER MOTOR WINDING & REFRIGERATION WORK L3 | vinay electric works L2 | BUDHIRAJA ENTERPRISES L1 |
|---|---|---|---|---|---|---|
| 1.00Supplying and drawing following size of FRLS/ HFFR PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit etc. as required. | ||||||
| 1.10 | 3X1.5sq.mm | 95 | Mtr. | 126 ₹11,970 | 150 ₹14,250 | 110 ₹10,450 Lowest |
| 2.00Supplying and fixing 5A to 32A rating, 240/415V, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | ||||||
| 2.10 | Single Pole | 12 | Each. | 170 ₹2,040 | 250 ₹3,000 | 150 ₹1,800 Lowest |
| 3.00 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. | 698 | Mtr. | 19 ₹13,262 Lowest | 20 ₹13,960 | 20 ₹13,960 |
| 4.00Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. | ||||||
| 4.10 | 4 X 16 sq. mm (28mm) | 7 | Each. | 250 ₹1,750 Lowest | 350 ₹2,450 | 325 ₹2,275 |
| 4.20 | 4 X 10 sq. mm (28mm) | 7 | Each. | 240 ₹1,680 Lowest | 300 ₹2,100 | 300 ₹2,100 |
| 5.00 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).
Supplying, Installation, Testing & Commissioning of 100watt LED Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5sq mm FRLS/ HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | 6 | Each. | 2,800 ₹16,800 Lowest | 2,800 ₹16,800 Lowest | 3,050 ₹18,300 |
| 6.00 | Making RCC foundation of size 450mm x 450mm x 1200mm with 1:2:4 (1cement, 2 coarse sand, and 4stone aggregate of 20mm) complete with 8mm dia MS bar for reinforcement along with centering & shuttering. Providing & fixing of with pole base plate dimensions 4no. 16X400mm S.S/G.I bolt with proper tighten with double nuts, spring and plain washers, 40mm dia HDPE flexible pipe including excavation & refilling of soil, with ramming, curing etc. as required. | 6 | Each. | 6,000 ₹36,000 | 4,000 ₹24,000 Lowest | 4,300 ₹25,800 |
Tender Value
₹7.2 L
EMD Value
₹14,467
Closing Date
2 Jul 2026, 3:00 pmClosed
Executive Engineer
Executive Engineer (E)-II, Works Department, Room No MZ-108, Main Building IIT Delhi, Hauz Khas, New Delhi - 110016.
Provision of lighting arrangement for children park (Park No-3 and 4) Near Vaishali reservoir and new campus area in west campus at IIT Delhi
2026_IIT_914768_1
IITD/WORKS (SP-5328)/2026
Open Tender
Miscellaneous Works
Works
45 days
Indian Institute of Technology Delhi Hauz Khas
As per tender documents
12 documents required · 12 mandatory
₹0
₹14,467
27 Jul 2026
25 Jun 2026
3 Jul 2026
25 Jun 2026
2 Jul 2026
25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying and drawing following size of FRLS/ HFFR PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit etc. as required. | |||||
| 1.1 | 3X1.5sq.mm | 95 | Mtr. | - | - |
| 2Supplying and fixing 5A to 32A rating, 240/415V, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | |||||
| 2.1 | Single Pole | 12 | Each. | - | - |
| 3 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. | 698 | Mtr. | - | - |
| 4Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. | |||||
| 4.1 | 4 X 16 sq. mm (28mm) | 7 | Each. | - | - |
| 4.2 | 4 X 10 sq. mm (28mm) | 7 | Each. | - | - |
| 5 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).
Supplying, Installation, Testing & Commissioning of 100watt LED Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5sq mm FRLS/ HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | 6 | Each. | - | - |
| 6 | Making RCC foundation of size 450mm x 450mm x 1200mm with 1:2:4 (1cement, 2 coarse sand, and 4stone aggregate of 20mm) complete with 8mm dia MS bar for reinforcement along with centering & shuttering. Providing & fixing of with pole base plate dimensions 4no. 16X400mm S.S/G.I bolt with proper tighten with double nuts, spring and plain washers, 40mm dia HDPE flexible pipe including excavation & refilling of soil, with ramming, curing etc. as required. | 6 | Each. | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.79 MB
BOQ_961327.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .