| 1 | L1₹41.4 LAccepted-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | L1 | Accepted-AOC being lowest | |
| 2 | L2₹50.3 L+₹8.9 L (21.5%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹50.5 L+₹9.2 L (22.1%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹50.6 L+₹9.2 L (22.3%)Rejected-Finance | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹51.5 L+₹10.2 L (24.6%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
27 Jun 2023, 6:00 pmClosed
AJIT KUMAR,IDSE
GE U ELECTRIC SUPPLY,DELHI CANTT
REPAIR MAINTENANCE LT PANEL, ACBS, MCCBS, EARTHING AND CONNECTED ITEMS AT ARJAN VIHAR, NEW PRATAP CHOWK, PRATAP CHOWK, ASSU, AHPU AND RRRC, AEPTA AND ADJOINING AREA OF AGE(U) ELECT SUPPLY NO-II UNDER GE (U) ELECT SUPPLY DELHI CANTT-
2023_MES_601102_1
GE/ELEC/D-42/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹84,000
Yes
17 Jul 2023
8 Jun 2023
29 Jun 2023
8 Jun 2023
27 Jun 2023
22 Jun 2023
Amount
(b) Outgoing (i) MCCB 4 pole , 250 Amps, 50 Hz,415 Volts, 25 KA with thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 200 Amps, 50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos (iii) MCCB 3 pole , 63 Amps,50 Hz,415 Volts, 16 KA with thermal magnetic release - 04 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Supply and fix in replacement Digital Multifunction Transducer/Meter (Accuracy class 0.5) with LCD/LED display for measurement of current, voltage, power, power-factor, energy parameters, Total Harmonic Distortion and Maximum Demand Indication etc and shall have RS-485 port for communication of data on Modbus protocol including associated wiring using 1.5 Sqmm FRLS copper wire complete all as specified and directed.
Supply and Installation of LT CT operated Trivector Meter with the following specifications:- (a) Meter Type: LT 3 Phase 4 Wire Electronic Tri vector Meter (b) Standard: IS 13779:1999 / CBIP 88 (c) Accuracy: Class 0.5 (d) Voltage and Current rating:- (i) Reference Voltage - 3x240 V (ii) Basic Current (Ib) - 5 A (iii) Maximum continuous current (Imax) - 10 A (e) Rated Frequency (variation) - 50Hz (±5%) (f) Power consumption:- (i) Voltage circuit: Less than 1.5 W and 10 VA per Phase at reference voltage, reference temperature and reference frequency (ii) Current circuit: Less than 1 VA per phase at basic current, reference frequency and reference temperature (g) Display type: 8 digit 7 segment backlit LCD display, not less than10 mm character height (h) Display in the event of Power Failure: Internal battery back-up for LCD display (j)Communication port: (i) Galvanically isolated Optical Communication port for data transfer through either CMRI or remote device or both is provided (ii) RS 485 for DLMS protocol (iii) Energy recording - Unidirectional
Supply only in replacement of 11 KV electrical Rubber insulating seamless hand gloves complete all as directed.
S&F and installation battery 12 volts,100 AH, dry type in replacement of old unserviceable battery in battery charger with suitable size of new copper battery terminal and lugs and initialy charging, commissioning and testing complete.
Supplying & fixing of LED street light Fitting 60 watt LED, IP-66 protection, single peice pressure die cast aluminium housing high grade powder coated finish with heat resistant toughned clear glass cover for lamp and control gear compartment with high voltage surge protection device up to 4.5 KV, prewired conductor to fitting with 3 core 1.5 sqmm pvc insulated cable along with GI pipe bracket & MS clamps etc complete all as specifiedand directed.
S&F in replacement of UNSV /Burnt MCCBs of capacity 630 Amps, FP, 50 KA, 415 Volts 50 Hz, AC, with microprocessor release fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable MCCB from panels etc complete all as specified and directed.
All as per sel item No 17 here in before but rating of MCCB 400 Amp, 35 KA .
All as per sel item No 17 here in before but rating of MCCB 250 Amp, 35 KA .
S&F in replacement of UNSV /Burnt MCCBs of capacity 630 Amps, FP, 50 KA, 415 Volts 50 Hz, AC, with thermal and magnetic release fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable MCCB from panels etc complete all as specified and directed.
All as per sel item No 18, here in before but rating of MCCB 320 Amp, FP, 36 KA.
All as per sel item No 18, here in before but rating of MCCB 250 Amp,FP, 36 KA.
All as per sel item No 18,here in before but rating of MCCB 200 Amp,FP, 25 KA.
All as per sel item No 18, here in before but rating of MCCB 160 Amp,FP, 25 KA.
All as per sel item No 18, here in before but rating of MCCB 100 Amp,FP, 25 KA.
All as per sel item No 18, here in before but rating of MCCB 63 Amp,FP, 16 KA.
S&F in replacement of UNSV /Burnt MCCBs of capacity 630 Amps, TP, 50 KA, 415 Volts 50 Hz, AC, with thermal and magnetic release fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable MCCB from panels etc complete all as specified and directed.
Allas per sel item No 19 ,here in before but rating of MCCB 400 Amp, 36 KA
Allas per sel item No 19 ,here in before but rating of MCCB 200 Amp, 25KA
All as per sel item No 19 here in before , but capacity MCCB 125 Amp, 25 KA
All as per sel item No 19 here in before but capacity MCCB 63 Amp, 16 KA
Supply, installing, testing and commissioning in replacement of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 500 Amps aluminium bus bar and with 250 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level.
Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized iron strip 32X6 mm by means of electric arc welding of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40mm bore GI pipe light grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply and fixing in replacement of galvanised iron strip 32 X 6 mm for additional earthing lead beyond 7.5 meter.
S&F in renewal on load change over switch open execution of capacity 630 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable changeover from panels etc complete all as specified and directed.
S&F on load change over switch open execution of capacity 400Amps , 4 pole , 415 volt , 50 Hz mounted on wall with fastner and suitable size of nut and bolts after taking down old existing un serviceable changeover from panel etc complete all as specified and directed.
Supply and fixing in replacement of indicator lamp for RYB phases complete all as specified and directed.
M&L for re-painting of LT Panels/feeder pillars of approx size 2 to 5 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of feeder pillar numbers in appropriate size of letters as directed.
M&L for re-painting of LT Panels/feeder pillars of approx size 5 to 10 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of feeder pillar numbers in appropriate size of letters as directed.
Supplying and fixing of Mild steel sliding door bolts 200 mm long ,plate type, stove enamelled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate.
S&F in replacement ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type , front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection
Material and labour in replacement Retro Reflective installation sign boards of size 12 feet x 4 feet fabricated out of 16 gauge MS sheet frame duly welded/riveted with MS square pipe of size 25mm x25mm at height 9.00 meter above ground level on stainless steel heavy duty pipe of size 80mm bore embaded 75 CM in PCC 1:2:4 type B 1 block of size 45cmx45cmx75cm including necessary excavation and earth work .The steel portion of the board shall be painted in stove enameled paint and the front & back of the frame shall be overall sheathed with blue colour base painter adhesive tape. The wiriting matter will be in English language on both sides with reflective adhesive painter tapes as directed by Engineer -in-charge.
Supplying and fixing in replacement LED flood light fitting of following size complete all as specified and directed by Engr-in-charge :-
Supply and fixing in renewal of 3 pole power contactor ML-6 mounted on any type/description LT panel/feeder pillar/wall after taking down old existing un serviceable contactor etc complete all as specified and directed.
Supply and fixing in renewal of 3 pole power contactor MNX-110 mounted on any type/description LT panel/feeder pillar/wall after taking down old existing un serviceable contactor complete all as specified and directed.
Supply and fixing in renewal of Analog Time switch, 240 Volt AC , 50 Hz , mounted on any type/description LT panel/feeder pillar/wall after taking down old existing un serviceable time switch complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel/feeder pilar for 25 sqmm cable to 70 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel/feeder pilar for 95 sqmm cable to 120 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel for 150 sqmm cable to 300 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of Halogen light fittings including fitting of capacity 1000 Watt complete all as specified and directed.
Supply and fixing in replacement of Halogen lamp 1000 Watt for existing Halogen light fittings complete all as specified and directed.
Material and labour in replacement of Voltmeter 0-500 V digital type as per existing size complete all as per specified and directed.
Material and labour in replacement of Ammeter 0-400 Amp digital type per existing size complete all as per specified and directed
M & L for cutting and removing grass, vegetation bushes etc from surrounding of installation/LT Panel/LT ACB panel and removing all rubbish to a distance not exceeding 50 m as directed.
Supply installation & commissioning in replacement of 24V/40A Float Cum Boost Battery Charger unit including battery bank comprising 02 Nos of 12 Volts-100 AH sealed maintenance free battery. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion . During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DC digital ammeter , DC digital voltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness , louvers for ventilation , gland plate will be provided for cable entry from bottom . The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:-
(a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1 (c) On load input power factor - > 0.8 (d) On load unit watt efficiencies-> 80% (e) No load losses of complete charge-< 10% (f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell . (j) Float charging -2.15 V/Cell (k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode. (l) Reverse polarity -No damage will caused . A visual indication for reverse polarity will appear with an audio alarm. (m) Short circuit-MCB protecton provided.
Supply and fixing in replacement LT current transformer having ratio 400/5 Amp , 15 VA, Class 0.5. Complete all as specified and directed by Engr-in-Charge
All as per Srl item No.45 herein before but CT ratio 250/5 Amp
All as per Srl item No.45 herein before but CT ratio 200/5 Amp
Material and labour disconnecting faulty /burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work , suitable size of thimble LT tap , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 25 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch complete all as directed.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
MV Engineers And Contractors
Ridhi engineers and builders
M/s JAIMAA ASSOCIATES
Vijay Electricals
DS CONSTRUCTION
mayur enterprises
Bee Kay Engineers & Contractors
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .