Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹98,000
Closing Date
24 May 2024, 11:00 amClosed
Superintending Engineer
office of the S.E., EUDC-II, Sec-18, Noida.
Replacment of Damged VCB and Substation Protection Work in Greator Noida
2024_PVVNL_922310_2
Replacment of Damged VCB and Substation Protection Work in Greator Noida
Open Tender
Electrical Works
Item Rate
60 days
office of the S.E., EUDC-II, Sec-18, Noida.
Attached in DOC
2 documents required · 2 mandatory
₹3,540
S.E. EUDC-II, Noida.
₹98,000
1 Jun 2024
19 Apr 2024
24 May 2024
19 Apr 2024
24 May 2024
19 Apr 2024
Amount
Supply and Fixing of Tail less Fuse unit for medium power transformerunder EDD-GR. NOIDA leLr lkexzh o dk;Z dk;Znk;h laLFkk }kjk lEikfnr djk;k tkuk gS iw.kZ VuZdh ijA
Double Circuit Tailess Unit : Providing and Installation of LT Protection Unit/Tailless Units for Double Circuit Containing06+06+ Nos. incoming + outgoing studs of 500Amp./650 volts, made out of copper and Rod made of brass along with 1 Neutral made of Brass & 03 + 03 back entry made of Brass & having 07+07 LT Porcelain insulator fixed in holding clamps made of MS Strip. Both Tailess Unit should be connected with only from copper Bus Bar of size 50x6mm and 16to 18 inches long.
Providing & Fixing of Frame made of angle of size 50x5mm with the help of nut& bolt off size.
Providing & Fixing of Copper Fuse Strip.
Providing & Fixing of Copper Bus Bar.
Providing & Fixing of Alu. Crimping Lugs 630sqmm.
Connecting of LT XLPE Cable (lead) 1x630sqmm/connecting lead into Tailless unit.
Grouting of Frame in Plinth
33@11 dsoh fo|qr midsUnz eaMh';ke uxj ds vUrxZr {kfrxzLr 11 dsoh oh0lh0ch0 ls Mcy iksy ds vUrxZr 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 11 to 14
11KV 3x300sqmm XLPE Cable
11KV O/D Termination Kit 3x300sqmm XLPE cable.
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Laying and commissiong of 11KV 3x300sqmm XLPE Cable Double Ckt. after digging trench of dia 220 mm in two parallel bores for Double Curcuit by manual method at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level for laying cable and refilling of trench including connections at both ends after providing and crimping of lugs of proper size for completion of work and Providing & Laying of Ist Class Bricks, along the length on both side of 11KV XLPE Cable in Cable Trench (minium 18No. Bricks/Mtr per Cable) and Stone Slab of size 450x600x50mm on top of the each Cable, Providing 150 thickness mm River sand for cushion beneath and 150mm above the cable and Back filling of excavated earth in the cable trench upto the ground level and ramming properly.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable Indoor jointing kits suitable for 3x300sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. after digging trench of dia 220 mm in two parallel bores for Double Curcuit by manual method at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level for laying cable and refilling of trench including connections at both ends after providing and crimping of lugs of proper size for completion of work and Providing & Laying of Ist Class Bricks, along the length on both side of 11KV XLPE Cable in Cable Trench (minium 18No. Bricks/Mtr per Cable) and Stone Slab of size 450x600x50mm on top of the each Cable, Providing 150 thickness mm River sand for cushion beneath and 150mm above the cable and Back filling of excavated earth in the cable trench upto the ground level and ramming properly.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable Indoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Replacement of 200 Nos. PCC Poles against Damaged and Old & Jarjar Poles under EDD-Gr. Noida.
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 22 to 27
11KV Pin Insulator with Pin
11KV X-Arm
PCC Pole 8.5mtr Long
11KV Disc Insulator with Fitting
ACSR Weasel conductor
ACSR Rabbit conductor
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST/PCC 11Mtr Long and PCC 8.5 Mtr Long Pole.
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) 11M Long ST/PCC Pole and 8.5 Mtr Long PCC Pole
Fixing of X-Arm as per requirement.
Fixing of Pin Insulator with pin as per requirement.
Fixing of Disc Insulator with fitting as per requirement.
Laying, Sagging and Re-Sagging of 11KV 3 Phase ACSR Weasel conductor with fixing of all accessories with complete work in all respect.
Laying, Sagging and Re-Sagging of 11KV 3 Phase ACSR Rabbit conductor with fixing of all accessories with complete work in all respect.
Providing and Fixing of Clamp with Nut & Boltsfor X-Arm as per site requirement.
Removal and Dismentalling of old and Damaged PCC Poles and Conductor from the Site and its safe carriage to any store centre of PVVNL Discom including loading and unloading both ends.
Replacement of 50 Nos. PCC Poles 11MTR against Damaged and Old & Jarjar Poles under EDD-Gr. Noida.
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 40 to 45
11KV Pin Insulator with Pin
11KV X-Arm
PCC Pole 11mtr Long
11KV Disc Insulator with Fitting
ACSR Weasel conductor
ACSR Rabbit conductor
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST/PCC 11Mtr Long and PCC 8.5 Mtr Long Pole.
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) 11M Long ST/PCC Pole and 8.5 Mtr Long PCC Pole
Fixing of X-Arm as per requirement.
Fixing of Pin Insulator with pin as per requirement.
Fixing of Disc Insulator with fitting as per requirement.
Laying, Sagging and Re-Sagging of 11KV 3 Phase ACSR Weasel conductor with fixing of all accessories with complete work in all respect.
Laying, Sagging and Re-Sagging of 11KV 3 Phase ACSR Rabbit conductor with fixing of all accessories with complete work in all respect.
Providing and Fixing of Clamp with Nut & Boltsfor X-Arm as per site requirement.
Removal and Dismentalling of old and Damaged ST Poles and Conductor from the Site and its safe carriage to any store centre of PVVNL Discom including loading and unloading both ends.
33@11 dsoh fo|qr midsUnz bVSgjk ls fuxr 11 dsoh iks"kd ua0 06 ij ,d ewfrZ xksy pDdj ij 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 58 to 59
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
Laying of HDPE Pipe by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
33@11 dsoh fo|qr midsUnz nudksj ls fuxr 11 dsoh [ksjyh Hkko iks"kd ij [ksjyh Hkko vUMj ikl ij 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 69 to 70
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
Laying of HDPE Pipe by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
33@11 dsoh fo|qr midsUnz nudksj ls fuxr 11 dsoh fetkZiqj iks"kd ij oh0lh0ch0 ls Moy isky rd 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 80 to 81
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. after digging trench of dia 220 mm in two parallel bores for Double Curcuit by manual method at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level for laying cable and refilling of trench including connections at both ends after providing and crimping of lugs of proper size for completion of work and Providing & Laying of Ist Class Bricks, along the length on both side of 11KV XLPE Cable in Cable Trench (minium 18No. Bricks/Mtr per Cable) and Stone Slab of size 450x600x50mm on top of the each Cable, Providing 150 thickness mm River sand for cushion beneath and 150mm above the cable and Back filling of excavated earth in the cable trench upto the ground level and ramming properly.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable Indoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
33@11 dsoh fo|qr midsUnz nudksj ls fuxr 11 dsoh [ksjyh Hkko iks"kd ij oh0lh0ch0 ls Moy isky rd 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 87 to 88
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. after digging trench of dia 220 mm in two parallel bores for Double Curcuit by manual method at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level for laying cable and refilling of trench including connections at both ends after providing and crimping of lugs of proper size for completion of work and Providing & Laying of Ist Class Bricks, along the length on both side of 11KV XLPE Cable in Cable Trench (minium 18No. Bricks/Mtr per Cable) and Stone Slab of size 450x600x50mm on top of the each Cable, Providing 150 thickness mm River sand for cushion beneath and 150mm above the cable and Back filling of excavated earth in the cable trench upto the ground level and ramming properly.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable Indoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
33@11 dsoh fo|qr midsUnz bVSgjk ls fuxr 11 dsoh iks"kd ua0 01 ij ,d iVokjh xksy pDdj ij 11 dsoh Mcy dsfcy Myokus dk dk;Z
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 94 to 95
11KV 3x185sqmm XLPE Cable
11KV O/D Termination Kit 3x185sqmm XLPE cable.
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
Laying of HDPE Pipe by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement.
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
fo|qr forj.k mi[k.M nudkSj ds vUrxZr ,p0oh0Mh0,l0 flLVe ds vUrxZr 11 dsoh ykBzu ij vksiu dMsDVj ds LFkku fo|qr nq?kZVuk jksdus ds n`f"Vxr 11 dsoh ¼1X35 PVC Cable sq mm½ flaxy dksj dsfcy djus dk dk;Z
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Supply of 11KV HT Single Core Cable 1x35sqmm(GTP Approved)
Laying and Fixing of 11KV HT Single Core Cable 1x35sqmm as per site requirement.
Providing of 11KV HT O/D Termination Kit 1x35sqmm
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 1x35sqmm Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Supply of 11 KV Best Quality HT Tape.
Fixing of above HT Tape as per site requirement.
Removal and Dismentaling of existing old and Damaged conductor with safe carriage of its from work site to any store of Discom PVVNL including loading and unloading both ends.
fo|qr forj.k [k.M xzsVj uks,Mk ds vUrxZr 100 ux 100 dsoh, forj.k ifjroZdks ij dh 200 ,Eih;j dh ,e0lh0lh0ch0 yxkus dk dk;ZA
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Providing and Fixing of 200Amp. 50KA 4 Pole MCCB with syntax Distribution Box make ABB, L&T, C&S, Syntax, HPL, Havells etc.
Providing and Fixing of 50sqmm Single Core PVC Insulator Copper Cable as per site requirement.
Providing and Fixing of 50sqmm copper Lug as per site requirement.
{kfrxzLr ohlhch cnyus ls lEcfU/kr dk;ZA 33@11 dsoh fo|qr midsUnz lsDVj&17 ,] ux 10 ux ohlhch cnyus dk dk;Z ,oa 33@11 dsoh fo|qr midsUnz bVSgjk] nudkSj] jcqiqjk] lykjiqj ,oa lsDVj&17 , ij 33 dsoh dh 6 ux ohlhch cnyus dk dk;ZA
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 119 to 122
11KV VCB I/C 600/300/5Amp.
11KV VCB O/G 400/200/5Amp.
33KV VCB WITH SINGLE T/F PANEL AND CT 200/100/1A
33KV VCB WITH DOUBLE T/F PANEL AND CT 200/100/A
Supply and Errection of the ABOVE Following material AND SUPPLY & ERRECTION OF THE FOLLOWING MATERIAL for completing the work as per RESPO.
Installation and commissioning of 11KV VCB I/C with complete connections and work in all respect.
Installation and commissioning of 11KV VCB O/G with complete connections and work in all respect.
Installation and commissioning of 33KV VCB WITH SINGLE AND DOUBLE T/F PANEL AND CT 200/100/1A with complete connections and work in all respect.
Plinth, Foundation and Earthing of all above 11KV and 33KV VCB with complete work in all respect.
Removal and Dismenatling of Old and Damaged 13 Nos. 11KV and 33KV VCB from site and its safe carriage from Store to any Store Centre of PVVNL Discom including loading and unloading both ends.
Shiv Electricals
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .