Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.9 CrAccepted-AOC | ₹2.9 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹3.3 Cr+₹43.5 L (15.3%)Rejected-Finance MIA GARAGE BUILDING 1ST FLOOR HILLCART ROAD DIST SILIGURI PIN 734401 | SILIGURI | SILIGURI | WEST BENGAL | 734401 | ₹3.3 Cr+₹43.5 L (15.3%) | L2 | Rejected-Finance Quoted Higher Rate |
| 3 | L3₹3.3 Cr+₹45.0 L (15.8%)Rejected-Finance | ₹3.3 Cr+₹45.0 L (15.8%) | L3 | Rejected-Finance Quoted Higher Rate |
| 4 | L4₹3.4 Cr+₹57.7 L (20.2%)Rejected-Finance 00 BALITIKURI BALITIKURI NASKARPARA HOWRAH WEST BENGAL 711113 | HOWRAH | WEST BENGAL | 711113 | ₹3.4 Cr+₹57.7 L (20.2%) | L4 | Rejected-Finance Quoted Higher Rate |
Tender Value
₹2.6 Cr
EMD Value
₹5.3 L
Closing Date
9 Aug 2024, 1:00 pmClosed
SE,KHEC,PWD
Kolkata Health Electrical Circle, P.W.Dte KIT Annex Building, 5th Floor KOLKATA
Proposed (G plus 9) storied Private Cabin Building within the premises of IPGMER- SSKM Hospital, Kolkata - Electrical Installation Works and Other Utility Services - External EI work.
2024_WBPWD_713184_1
WBPWD/SEKHEC/KSHED/eNIT8/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
Kolkata
Please refer Tender documents.
8 documents required · 8 mandatory
₹5.3 L
Office of the SE,KHEC,PWD
27 Dec 2024
13 Jul 2024
12 Aug 2024
13 Jul 2024
9 Aug 2024
25 Jul 2024
22 Jul 2024
Amount
SUB-HEAD I : SITC OF LT PANEL
MAIN LT PANEL: SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 1600A 4P ACB - 2 Nos & Buscoupler 1600A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 2500A 4 Bars- 2 Set, O/G : 1250 A 4P ACB - 2 nos, 1000A 4P ACB - 3 nos, 200A 4P MCCB --- 2 nos. & 125A 4P MCCB - 5 nos.]
CHILLER PANEL: SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 1000A 4P ACB - 2 Nos & Buscoupler 1000A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 1600A 4 Bars- 2 Set, O/G : 400 A 4P MCCB - 4 nos, 160A 4P MCCB - 1 no, 100A 4P MCCB --- 14 nos.]
BUILDING DG PANEL: SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 1000A 4P ACB - 2 Nos & Buscoupler 1000A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 1600A 4 Bars- 2 Set, O/G : 200 A 4P MCCB - 2 nos, 125A 4P MCCB - 14 nos & 100A 4P MCCB --- 2 nos.]
UPS PANEL: (FOR PARALLEL OPERATION OF 2 X 60 KVA 3 PHASE IN & 3 PHASE OUT UPS FOR CABIN) SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [ (Main I/C 200A 4P MCCB - 1 No.), (UPS I/C 160A 4PMCCB ----- 2 Nos.), (UPS O/G 125A 4P MCCB ---- 2 Nos. & B/C 200A 4P MCCB ----- 1 No. with Mechanical & Electrical Interlock), (BBC 320A 4 Bars ----- 2 Set), ( O/G : 100A 4P MCCB --- 3 Nos.) ]
UPS PANEL : ( FOR PARALLEL OPERATION OF 2 X 20 KVA 3PHAHE IN & 1 PHASE OUT UPS FOR OT & RECOVERY) SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [ (Main I/C 125A 4P MCCB - 1 No.), (UPS I/C 100A 4PMCCB ----- 2 Nos.), (UPS O/G 125A DP MCCB ---- 2 Nos., (BBC 200A 4 Bars ----- 2 Sets ) & (125A C/O Switch for outgoing to UPS VTPN)
PANEL FOR WATER PUMP: SITC of floor cum wall mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section) [I/C 160A MCCB - 1 No., BBC 250A 4 Bars ----- 1 Set, O/G : 125A MCCB --- 4 Nos. & Star-Delta Starter - 4 Nos]
SUB HEAD II - LT CABLING FROM SUBSTATION TO BUILDINGS & PANEL TO PANEL CONNECTION
Supplying of following size PVC insulated and PVC sheathed / XLPE Aluminium armoured power cable of 1.1 KV grade of following size. (Make:- Gloster/Polycab/Havells/RR Kabel)
4 Core 300 Sq. mm
4 Core 240 Sq. mm
4 Core 95 Sq. mm
4 Core 70 Sq. mm
4 Core 50 Sq. mm
4 Core 35 Sq. mm
4 Core 25 Sq. mm
Laying of following cables through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand
5x4 Core 300 Sq. mm
Laying of 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable ( Armoured ) of following size on existing cable tray as to GS.
5x4 Core 300 Sq. mm
4 nos 4 Core 240 mm²
3 nos 4 Core 240 mm²
1 nos 4 Core 95 mm²
1 nos 4 Core 70 Sq. mm
1 nos 4 Core 50 Sq. mm
3 no 4 Core 35 Sq. mm
3 no 4 Core 25 Sq. mm
Laying of 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable ( Armoured ) with 2 Nos 8 SWG G.I wire on wall with S/F MS shaddle incl. making connections as per direction of EIC.of following size as to GS.
1 nos 4 Core 95 mm²
1 nos 4 Core 70 Sq. mm
1 nos 4 Core 70 Sq. mm
1 no 4 Core 25 Sq. mm
Supplying and making end termination with Brass compression gland and Finishing the end of conductor by crimping method by aluminium lugs for the following sizes of PVC insulated and PVC sheathed aluminium conductor cable of 1.1 KV Grade as required.
4 Core 300 Sq. mm
4 Core 240 Sq. mm
4 Core 95 Sq. mm
4 Core 70 Sq. mm
4 Core 50 Sq. Mm
4 Core 35 Sq. Mm
4 Core 25 Sq. mm
Straight through Jointing of cable of different size by compound jointing kit including S&F ferrul, tapes and jointing materials (Brand approved by EIC)
4 / 3.5 core 300 sqmm cable
4 core 240 sqmm cable
Supply & Installation of Electro Zinc Galvanised Hot Dip Galvanised (105 / 400 mm outdoor type) Wiremesh cable Tray in accordance with standard BSEN 12329-2000 with all mounting accessories. Fire test certification should be published in accordance with the E30/E90 standard. Electrical continuity across a coupling should be demonstrated by means of a published test method and result. [MAKE: LEGRAND CABLOFIL /OBO]
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.
300x50x1.25 mm (18SWG) with 25x25x6mm angle iron support.
400x50x1.25 mm (18SWG) with 35x35x6mm angle iron support.
600x50x1.25 mm (18SWG) with 50x50x6mm angle iron support.
S& laying 250 mm (10") NB (ISI Heavy) HDPE pipe for Cable protection with necy. fittings & jointing materials as required.
S& laying 150 mm (6") NB (ISI Heavy) HDPE pipe for Cable protection with necy. fittings & jointing materials as required.(Make:- Dalda/Dolly/AKG/Bardia/Narayani)
SUB HEAD III - EARTHING
Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F heavy type heat shrinkable PVC sleeve protection for entire GI strip to an average depth of 3.65 Mts. (For Main panel - 2 Sets, Chiller Panel - 2 Sets, Bldg. DG Panel - 2 Sets, Building Equipment -- 2 Sets, Lift Machine room - 2 Sets and Special Earting for Medical Instruments - 2 Sets. )
S&F 50 mm x 6 mm galvanized (Hot Dip) steel strip (beyond 4 Mts. For each earthing & equipment connection) incl. S & F heavy type heat shrinkable PVC sleeve protection for entire GI strip
Insulating the 50 x 6 mm M.S. flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar).
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe.
Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor withh GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI inged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode ( For UPS )
Supply & Laying of 6 SWG single strand bare-copper-conductor (Solid copper wire) with PVC insulation by heat shink as per direction of EIC.
Supplying & fixing 19mm dia medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required as per direction of EIC.
SUB HEAD - IV - SAFETY EQUIPMENT
Supply and fixing safety instruction chart in word duly framed with 5mm thick glass as required (approx. Front area 1.20 sqmt.)
Danger board of Medium Voltage - size 200mm x 150mm
Providing First Aid Box as approved by St. John Ambulance Brigade / Indian Red Cross conforming to IS 13115-1991.
Supply and fixing shock treatment chart duly mounted on a wooden frame with 5mm thick glass as reqd. (approximate front area 1.20 sq.metre).
Providing of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 6KV dielectric strength as per IS 15652-2006.
SUB-HEAD V : COMPOUND LIGHT
Supply & Erection of swagged type 9 Mtrs long ST pole (410 SP-30) with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 300 mm and 300 mm above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly. (Make:- Bajaj, Philips, Valmont, CG, Transrail,Bansal,Utkarsh)
Extra on items 1 above, for providing CC (6:3:1) base block (around the pole) dimension 0.60x0.60x0.76 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) suitable for alkathene/ polythene pipe entry as directed for street light wiring, incl. S & F 25cmx25cmx10cm GI Loop box, 16SWG & incl. drilled hole in pole (For 9 mtrs Long Pole).
Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint upto 9 Mtrs long pole.
(i) One coat of red lead/Zinc chromate priming
(ii) 1st coat of synthetic enamel paint over the primer
(iii) 2nd coat of synthetic enamel paint over the 1st coat
S & F 1.5 M long detachable type arm bracket with sleeve, made by 50 mm & 100mm dia Class 'C' MS pipe with bolts & nuts, through bolts with nuts, CI pole Cap etc to be fixed on top of ST pole incl. painting of 2nd coat of aluminium paint with ready mixed paint over one coat of red lead primer of approved brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint. as required as per direction of EIC.
(i) Single Arm Bracket
(ii) Double Arm Bracket
(iii) Three Arm Bracket
S & F 50 mm dia 1.5 Mtrs long "L" shape'' GI pipe single arm bracket to be fixed on wall by GI clamp with fasner, nuts & bolts, washer etc as required as per direction of E.I.C.
Supply & Laying 3 Core 10 mm² XLPE Ar./ Al. Cable incl mending dameges to original finish aas to G.S. as follows:- as per direction of EIC.(Make:- Gloster/Polycab/Havells/RR Kabel)
(i) In U.G. trench
(ii) On wall by MS saddle
(iii) In existing cable trench/Tray
S&F compression type gland & Finishing the end with dowells solderless socket by crimping method for 3 Core 10 sqmm XLPE Ar./Al. cable as per GS.
S/Drawing 1.1kV Gr. 3 core 2.5 sq. mm. stranded FRLS PVC unurmared Cu cable through pole and Arm bracket from loop Box to fittings for necessary connection. [Make:- Finolex/RR Kabel/Polycab/Havells]
S/Drawing 1.1kV Gr. 3 core 1.5 sq. mm. stranded FRLS PVC unurmared Cu cable through pole and Arm bracket from loop Box to fittings for necessary connection. [Make:- Finolex/RR Kabel/Polycab/Havells]
Finishing the end of 3 core 1.5/2.5 Sq mm copper wire end / PVC cable/Al. with dowells solderless socket by crimping method as pre GS.
Supply & drawing of 40 mm. dia. GI (ISI-M) pipe for cable protection with all fittings etc in UG trench as per GS.
Supply & fixing of pressure die cast aluminium housing of minimum175 watt LED Street light fittings including IP 66 protection with CCT( 5700-6500) & minimum Luminious effiency ≥ 110 Lumen/Watt suitable for mounting on 50 mm dia (OD) Arm bracket and making necessary connection. (Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified ).
Supply & fixing of pressure die cast aluminium housing of minimum130 watt LED Street light fittings including IP 66 protection with CCT( 5700-6500) & minimum Luminious effiency ≥ 110 Lumen/Watt suitable for mounting on 50 mm dia (OD) Arm bracket and making necessary connection. (Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified ).
Supply & fixing of pressure die cast aluminium housing of minimum 45 watt LED Street light fittings including IP 66 protection with CCT( 5700-6500) & minimum Luminious effiency ≥ 110 Lumen/Watt suitable for mounting on 50 mm dia (OD) Arm bracket and making necessary connection..(Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified ).
Supply & fixing of pressure die cast aluminium housing of minimum 100 watt LED flood light including IP 66 protection with CCT( 3000-4000) & minimum Luminious effiency ≥ 110 Lumen/Watt to be fixed on wall / pole and making necessary connection. (Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified ).
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
S/F 16 SWG 250 x 200 x 100 mm stainless steel loop box with 4 nos connector fixed on porcelain chair, recessed in wall with hinged top cover, rubber gasket, mechanical locking arrangement incl. S/F 1 no. 240V 6A MCB C-curve with earthing attachment complete. (Make : Sintex/Hensel)
Supplying & fixing 415V 63A 4 bars (Size of Al. bar 4 x 20 x5 mm) sheet metal (16 SWG), Busbar chamber of size 500 x 500 x 150 mm fixed on angle iron frame on wall, incl. earthing attachment and painting as required as to GS.
S & F 415V 63A Timer controller for out side light or compound light in SS double door 4-way TPNDB enclosure (Make:- Legrand/Simens/ABB) with S&F following electrical accessories & front door locking arrangement with all connection incl. earthing attachment on wall as per direction of EIC :-
i) 63A TPNMCB (Legrand/Simens/ABB) --- 1 No
ii) 24 Hr programmable Digital/Analog Timer (Legrand/ABB) ---- 1 No
iii) 4 pole power contactor (Legrand/Simens/ABB) with 1 NO +1 NC additional contact block ---- 1 set
iv) 20A Auto-Off-Bipass SPDT toggle switch Approved/reputed make) ---- 1 No.
v) Two nos. indicating lamp for on/off. (Approved/reputed make)
vi) Two nos. On & Off push bottom switch.(Approved/reputed make)
SUB-HEAD VI : LED GLOW SIGN BOARD
Supply & fixing of angle iron frame fabricated from 40mm x 40mm x 5 mm thick hollow rectangular bar with sufficient cross and radial support including MS angle iron frame (by 40 mm x 40 mm x 5 mm ) for holding the sign board and support from wall by 50 mm x 50 mmx 6 mm MS angle of 6 fts apart with necessary hooks. Back side shall be covered by S&F of 22 SWG GI sheet. The above structure should be painted with synthetic enamel paint over one coat of primer. The above sign board to be fixed on wall or Parapet as per direction of EIC. [32 ft (L) x 4 ft (W) x 4" (D) -- 2 Set ]
Supply & Installation of 3 mm thick polyvenile coated Aluminium Composite Panel board ( Aludecor / Alstone / Pratap Bond) of blue colour as the base for fixing raised letter duly fixed on the MS structure as per direction of EIC. The riser structre should be covered with ACP sheet incl. side portion on the board. [32 ft (L) x 4 ft (W) x 4" (D) -- 2 Set ]
Supply & fixing of Superior Quality acrylic dimensinal letters inscripted in English front side of the letter to be made 3mm thick Imported (White-0.40) uv stabilised excellent to self display. Make - Acast, Mitsubishi / Astari / UB. All letter will be 3D and to be fixed by special type of solution and RTV sililicon filler for leakprofees and maintaing suitable space with Male & Female attachments for each letter and necessary interconnections as per direction of the EIC.
(i) Letter size : 1.5 fts for "PRIVATE CABIN BUILDING" ----- 20 Nos. X 2 Sets
(ii) Letter size : 1.3 fts for "IPGME&R-SSKM HOSPITAL" -------20 Nos. X 2 Sets
(iii) Letter size : 2 fts for "PRIVATE CABIN BUILDING" for vertical glowsign to be fixed on wall or glass including fixing materials and interconnection by sutable copper cable through PVC pipe with wall matching colour as per direction of EIC-------20 Nos. X 1 Set.
S&F of imported 12 V DC IP-65 LED modules having three LED in a single base module and the LEDs will emit mild attractive white colour light and the two runs of LED for each letter base area and shall be properly fixed including necessary interconnections. Specification of the LEDs is given as below : a) LED-white, Samsung/cree/osram b) Type-Straight, 3 Nos. Led per module c) Life – 50,000 Hrs. burning hours. d) Visibility – 100 mtrs at least, for normal eye e) Power consumption – 1.5 watt per module with IP65
S&F of imported heavy duty Input – 230V AC, output 12V DC., IP65,300W or above SMPS power supply (Make-Aries/Union/e-power) with properly rated isolation transformer in suitable enclosure (Make Sintex/Hager) to be fixed with the signage frame for driving total LED system of the signage in a distributed manner for uniform load sharing in view of long run continuous use including necessary interconnections..
M.S. works in brackets made from flats, angles, tees etc. to sizes specialy bent, twisted, forged; making holes drilled and fitted to rafter of trusses with necessary bolts, nuts, washer or screws etc. (length of straight not less than 230 mm) for extra support of Glow Sign by 50mmx50mmx5mm and the above supports should be painted with synthetic enamel paint over one coat of primer as per directiuon of EIC.
Scaffolding arrangement for working at 40 ft. height on entrance of the building by bamboo, ropes and wooden planks etc. and shifting of scaffolding materials after completion of work. [ For Horizontal Glow Sign ]
Scaffolding arrangement for working at 47 Mtrs. height on entrance of the building by bamboo, ropes and wooden planks etc. and shifting of scaffolding materials after completion of work. [ For Vertical Glow Sign ]
Transportation cost for taken away the glow sign board from Co’s workshop site to work site including loading, un-loading.
SUB-HEAD VII : SUPPLY & INSTALLATION OF GYSER
S&F 240V. 25 Lts capacity vertical type Water-Heater (Gyser) with hot & cold copper pipe line as required & thermostate, temperature setting regulator etc including fixing by suitable GI fasner , GI Bolt & Nuts as direction of EIC ( For VVIP cabin & Doctors rooms) (Make:-Havells Adonia Spin 25-Litre Vertical Storage Water Heater (Geyser) White Blue 5 Star/ Jaquar ELENA 25 Litres Vertical Storage Water Heater White).
S&F 240V. 15 Lts capacity vertical type Water-Heater (Gyser) with hot & cold copper pipe line as required & thermostate, temperature setting regulator etc including fixing by suitable GI fasner , GI Bolt & Nuts as direction of EIC ( For VIP cabin & Nurses Room) (Make:-Havells Adonia Spin 15-Litre Vertical Storage Water Heater (Geyser) White Blue 5 Star/ Jaquar ELENA 15 Litres Vertical Storage Water Heater White).
SUB-HEAD VIII : SITC OF NURSE CALLING SYSTEM
SITC of 43" (108 cm.) Full HD LED TV for display having in-built WLAN and minimum 2 x HDMI, 2 x USB Port including Full Function Remote, Power Cord, Wall mounting Kit,LAN modem etc incl all accessories.(AS per direction of EIC)(Make-Samsung, Model UA43T5450AKXXL/ Sony, Model KD43X74K)
SITC of 32" (80 cm.) Full HD LED TV for display having in-built WLAN and minimum 2 x HDMI, 2 x USB Port including Full Function Remote, Power Cord, Wall mounting Kit,LAN modem etc incl all accessories.(AS per direction of EIC)(Make-Samsung, Model LS32CM501EWXXL/ Sony, Model KD32W820K)
SITC of Wireless Nurse Station Display Driver Converter Of Sigals - From NCS Server To LED TV Main Display,LAN modem ,Bugger indicator etc incl all accessories.(AS per direction of EIC) (Make-Webtronics/Webtron)
SITC of Wireless Addressable Nurse Calling Modular & Decorative Patient Switch , LAN modem etc incl all accessories. (AS per direction of EIC). (Make-Webtronics/Webtron)
SITC of Wireless Addressable Nurse Calling Patient Cabin Indicator Supports Calling By Patient. LAN modem etc incl all accessories. (AS per direction of EIC) (Make-Webtronics/Webtron)
SITC of Wireless Addressable Bathroom Calling point by pull cord calling by Patient incl all accessories. (AS per direction of EIC) (Make-Webtronics/Webtron)
SITC of Wireless Addressable Nurse Calling System Central Proggrameable Server Performs for Call & Reporting Management,with Central Memory Unit Of W/L NCS minimum 128GB storage and upto 256GB expandable. LAN modem etc incl all accessories.(AS per direction of EIC) (Make-Webtronics/Webtron)
SITC of Router with dual band & frequency range of 2.5 to 5 GHz with 750 MBPS WiFi speed including inbuild or separate LAN jointer for isolation of fauly router including necessary connecter (RJ45) to be fixed on wall/ceiling including all accessories.(AS per direction of EIC) (Make- TP-Link, Model : AC750).
S&I of 230V AC / 12 V DC , 20 Amps SMPS including suitable enclosue with suficient vetilation to be fixed on wall as per direction of EIC. (Make- Schneider / Siemens).
S&Laying of 1.1 KV Gr. 2 core 1.5 Sqmm, FRLSH unarmoured copper cable (Make- Finolex/RR Kabel/Polycab/Havells ).through prelaid 19/20mm dia PVC rigid conduit pipe (Pricision -M) as per direction of EIC.
Supply & Laying of Solid Cable Cat 6, 4 pair, UTP must have Fire retardant PVC Compound (FRPVC) Flame Rating material, All cables meet and exceed Category 6/Class E requirements in ANSI/TIA-568-C.2, and ISO/IEC 11801. Must be RoHS Compliant as per Technical specification. (For Panel to Panel Network) (Make : Cosmcope/ Finolex / MOLEX ).
Supplying and fixing PVC Rigid Conduit 'FR' [Make : Precision/AKG/ATUL/VIP/Universal/BEC/Polypack] on wall, ceiling with saddles and other accessories as required and mending good damages to building works.
Testing,Commissioning & Proggramming of above addressable Nurse Calling system by Company commissioning Engineer. Whole Nurse Calling System are minimum 2years warranty after complication.
SUB-HEAD IX : MISCLLENEOUS WORKS
Making masonary cable trench after cutting all sorts of soil. The inside mearsurment of trench 900 mm clear width x 900 mm clear depth by providing 250 mm thick brick work with 1st class brick cement mortorr (1:4) on both sides and bottom of the trench consisting with 100 mm thick cement concrete (1:3:6) with stone chips over a layer of jhama brick flat soling 15mm thick (1:4) cement plaster to inside wall & 3mm thick neat cement finish.
Making & placing split type RCC slab cover of size 1400 mm x 400 mm x 150 mm thick each in 150 mm x 80 mm x 80 mm x 6 mm thick fabricated MS channel frame with inside welded reinforcement steel rods (12mm & 10mm dia) and the slabs to be placed over masonary cable trench properly recessed on both side walls and the cover slabs shall be capable of bearing minimum 200 Metric Ton load.
Core cutting of 125mm thick RCC slab by suitable core cutting machine for passing necessary vertical run of Electrical Bus duct/ cables/ cable tray/ protection pipes/ earthing strip etc including mending good the damages as per direction of the EIC.
Cutting floor/ brick wall by suitable tools for passing electrical cables/ cable tray/ protection pipes/ earthing strip etc including mending the damages as per direction of the EIC.
Supply, fabrication and placing/fixing MS checkered plate made of 6mm thick incl 30mm x 30mm x 6mm MS angle iron structure welded by fixing for insert plates at 4 sides in cable trench top with 2 nos 3/8" TMT handle rod incl gas cutting, grinding & drilling with one coat of red laid primer and one coats of synthetic enamel paint as per direction of EIC.
S&F of MS Channel of following sizes with nut, bolt, washer etc to provide overhead supporting arrangement above different LT panels, cable support at HV side of transformer incl painting as to GS for following :
150mmX 75mm X 10mm
100mmX50mmX8mm
75mmX40mmX6mm
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/ perspex cover and making necessary connections as required
S & Drawing following sizes PVC insulated FRLS Cu.wire (Make - Finolex/Havells/RR Kabel/Polycab) in 20 mm dia PVC rigid conduit pipe on wall complete with all accessories incl. making connections as to G.S. :-
2 x 2.5 sq.mm.+ 1 x 1.5 sq.mm. (for Power Plug, Sw-soc boards).
Finishing the end of following sizes copper wire end with dowells solderless socket by crimping method as per GS as follows:-
2 x 2.5 & 1 x 1.5 mm² copper wire
Supply & Fixing 230 V., 18" (450mm) 4 (four) Blades Industrial type Air-Circulator Pedestal Fan complete with all accessories such as Regulator, Cord and 15 Amp. 3-pin Top (Make - E.P.C. Electrical Pvt. Ltd., Heavy Duty)
Supply & Fixing 230 V., 18" (450mm) 4 (four) Blades Industrial type Bracket Fan complete with all accessories to be grouted on wall inclu. Making necesy. Connection as per direction of the EIC (Make - E.P.C. Electrical Pvt. Ltd., Heavy Duty)
S & F 240 V A.C. Exhaust Fan (EPC Electrical Pvt. Ltd. - Heavy Duty) incl. Cutting hole on wall with Nuts, Bolts, washers etc. on wall and mending good the damages to original finish as per direction of the EIC for following sizes:-
375 mm (15") sweep 1420 RPM
S&F of "L" shape Cowl made of G.I sheet of size 300x300mm having length 600mm with 4 nos 20x3mm MS flat support and S&F of wire mess at the ends of the said cowl with nuts, bolts etc as reqd. for following sizes exhaust fans:-
375 mm (15") sweep
S&F of sequential timer comprising with 1 no single pole power contractor (Make:- ABB/Legrand) & 1 no digital time switch (Make:ABB/Legrand) in SS enclosure incl. internal wiring by suitable copper wire to be fixed on wall as per direction of EIC. (For Toilet Exhaust Fan).
S & F 250V 25A Twin Timer controller in SS suitable enclosure including locking arrangement with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 2x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :- (Make:-ABB/Schneider/Legrand). as per direction of EIC. (For Exhaust Fan, Air-Circulator Bracket Fan of AC Plant room , Panel room and ventilation of Toilet exhaust Fan).
i) 25A DPMCB --- 1 No
ii) 24 Hr programmable Digital Timer (Make: ABB/Legrand) ---- 1 No
iii) 3 pole power contractor with 1 NO +1 NC additional contact block ---- 1 set (Make: ABB/Legrand) ---- 2 Nos
iv) 2 Moduler AC motor stater ---- 1 No.
v) 3 Module plate with cover -- 1 No
vi) 20A Auto-Off-Bipass SPDT toggle switch ---- 1 No.
vii) 10A SPST Moduler type switch - 1 No.
viii) LED Indication lamp (Approved/reputed make) - 2 Nos
ix) Outgoing connector (Approved/reputed make) - 2 Nos
S&F 415V Fully Automatic Star-Delta /DOL stater of different rating incl necessary connection to be fixed on angle iron frame incl painting on wall as per direction of EIC as follows:-
For Chilled Water Primary Pump & Cooling Tower (Make:- ABB/Legrand/Siemens, Relay Range 14 - 23A)
For Chilled Water Secondary Pump & Condencer Water Pump (Make:- ABB/Legrand/Siemens, Relay Range 30 - 50A)
For Makeup water Pump & Water Treatment Plant (Make:- ABB/Legrand/Siemens, Relay Range 9 - 15A)
Supply & fixing of 6W LED mirror light (3-in-1 Color Chnaging Black Rose Gold Finish LED Mirror) to be fixed wall on T.W board or PVC board including ncessary connection by suitable copper wire through PVC tube of wall matching colour as per direction of EIC (Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified).
Supply & delivery of recessed mounted 36W LED fittings with CCT (as per actual requirement as directed by EIC) & minimum Luminious effiency ≥ 120 Lumen/Watt to be fixed on wall / pole and making necessary connection. (Make: Philips/Lighting Technology/Wipro/Jaquar (Model as specified).
SUB-HEAD X : DRAWING & DOCUMENTATION
Preparation of planned & as-built G.A. drawings and Single Line Diagrams (SLD) of the proposed Electrical power distribution system of Private Cabin Building and Sub-station mentioning the cable sizes at different levels and the drawings to be made in as built GA Drawing in both Hard Copy & soft copy form (latest Autocad version in CD). Hard copy of size 1.5mt X 3mt in flex covered with transparent Acrylic sheet & sides are bind with stainless steel frame as per direction of the EIC.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished or defective or duplicate material is supplied and installed during execution of work or found any stage of running work necessary penal action will be taken as per existing rules.
a. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
b. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
c. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
M/S. N.C. HORE
THE INDIAN OVERSEAS TRADING COMPANY
CHAKRABORTY ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .