EXECUTIVE ENGINEER (SDW)-II
S.T.P. OKHLA MATHURA ROAD NEW DELHI-110025
Retrofitting of 10 MGD centrifugal pump Beacon Weir make of set No. 05 at EPH Okhla.
2022_DJB_217642_1
Press NIT No-19 EE (SDW) II/ (21-22)
Open Tender
Electrical Works
Works
183 days
S.T.P. OKHLA MATHURA ROAD NEW DELHI-110025
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
A/c.50448339804
₹55,800
19 Mar 2022
26 Feb 2022
11 Mar 2022
26 Feb 2022
11 Mar 2022
26 Feb 2022
By carrying out following works including all the required works, materials, arrangements tools & tackles workmanship, safety arrangements & equipments as per NHRC guidelines etc. and as per site requirement, remodeling all the damages up to standard if occurred any complete in all respect satisfactorily. Retrofitting of 10 MGD centrifugal pump Beacon weir make of set No. 05 at EPH Okhla by carrying out following works. Supply of 10 MGD Centrifugal Pump Discharge Capacity minimum 527 Litre/S 50 m head, RPM minimum 980, Shaft Sealing- Gland Packed, Heavy duty, Casing- CI IS 210 Gr FG 260, PN 16 Rating, Cathodic electro-deposition coating (CED) coated PUMP, Casing Wear Ring- SS ASTM A 276, Impeller SS ASTM A 351, Shaft- SS ASTM A276, Shaft Sleeve- SS ASTM A276 (Unit will comprise of Pump + Coupling+ Coupling Guard) min. Efficiency = >74% Note- Pump will be connected to 500 HP/350 KW existing motor and used for heavy duty pumping of effluent water. Make- LUBI/ M&P/ Kirloskar/ KBL/ Jyoti/ KSB/ Andritz
Dismantling the pump after complete closing of suction & delivery valves, decoupling from motor end, cutting of all rusted studs & nut bolts with gas cutter as required and taking out the pump up to floor level
Isolating the suction & delivery system by fixing dead flange on pump casing
Modification/strengthening of existing base frame as per site requirement i/c Civil work.
Installation of the 10 MGD centrifugal pump at site after removing the dead flange from suction & delivery pipe line, fixing the coupling tightening the complete body of pump and making alignment with motor.
Safety arrangement air face mask, Hand gloves, helmet, gum boots, protective bodysuits, safety belts, first aid box, caution tape, etc arranged by the firm at site of work for safe working at Site
Testing and commissioning of the pump on full load and No load as per satisfaction of engineer In-charge.
Sarvottam Sales and Services
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .