Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
19 Jun 2026, 6:00 pm
GE Central Bangalore
GE (CENTRAL) BANGALORE AGRAM POST BANGALORE KARNATAKA-560007
REPAIR MAINT OF INTERNAL WIRING SUB MAIN MCCBS LIGHT FITTINGS WITH OTHER INTERNAL WIRING AT OFFR ORS MD ACCN AT 70 MAJ NGV 100 MAP AND 598 OR MD ACCN WITH OTHER AREA UNDER GE (CENTRAL) BANGALORE
2026_MES_768592_1
8648E
Open Tender
Electrical and Maintenance Works
270 days
ASC CENTRE AND COLLEGE BANGALORE
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE CENTRAL BANGALORE
₹60,000
Yes
29 May 2026
29 May 2026
22 Jun 2026
29 May 2026
19 Jun 2026
13 Jun 2026
1 Jun 2026 - 12 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down copper/ aluminium point wiring(light, fan, socket or power) complete, including fittings and fixtures such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions seperately) and making good distrubed surfaces of wall, floors, etc complete all as specified and directed. | 955 | Point | - | - |
| 2 | M&L for Point wiring for One light point controlled by one 5 Amps switch one way with PVC insulated and unsheathed FRLS cable single core multistranded copper conductor 1.5 sqmm size, 1100 volts grade cable conforming to IS-694 1990 drawn in and including PVC rigid non metalic conduit concealed conforming to IS-9537 with all accessories including fabricated MS terminal boxes fixed flush with wall surface with 3mm thick laminated sheet top cover fixed with brass screw for mounting switches, sockets, regulator etc including 1.5 sqmm single core PVC insulated and unsheathed copper conductor earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed.
Note:Location of light points, socket points and light fittings may be decided by Engr-in-charge as per site/user requirment. | 200 | Point | - | - |
| 3 | All as per item No 2 above but for One fan point controlled by one 5 Amps switch one way complete all as specified and directed. | 40 | Point | - | - |
| 4 | All as per item No 2 above but for One bell point controlled by one switch complete all as specified and directed. | 30 | Point | - | - |
| 5 | All as per item No 2 above but for One light point controlled by one 5 Amps switch two way complete all as specified and directed. | 20 | Point | - | - |
| 6 | All as per item No 2 above but for One 3 pin socket point 5 Amp on independent board complete all as specified and directed. | 60 | Point | - | - |
| 7 | All as per item No 2 above but for One 3 pin socket point 5 Amp on same board with other switches complete all as specified and directed. | 30 | Point | - | - |
| 8 | All as per item No. 2 above but with 2.5 sqmm ( Nominal area ) cable with 2.5 Sqmm size copper earth continuity conductor for 3 pin 15 A socket outlet on independent board complete all as specified and directed. | 50 | Point | - | - |
| 9 | All as per item No. 2 above but with 4 sqmm ( Nominal area ) cable with 4 Sqmm size copper earth continuity conductor for 3 pin 15 A socket outlet on independent board complete all as specified and directed. | 50 | Point | - | - |
| 10 | M&L for Point Wiring for One light point controlled by one 5 Amps switch one way with 1.5 Sqmm (Nominal Area) PVC insulated unsheathed 1100 Volts Grade Stranded Copper Conductor Cable (Red Colour Cable for Phase and Black Colour Cable for Neutral), laid in and including PVC Casing and Capping with Accessories (size of Casing and Capping as required at Site) including 1.50 Sqmm PVC ins-ulated Stranded Copper Conductor Cable (Green Colour) as Earth Continuity Conductor and connected to Common Earth Dolly or as directed and MS terminal box with 3mm thick masonite laminated sheet top cover fixed on Wall complete all as specified and as directed
Note:Location of light points, socket points and light fittings may be decided by Engr-in-charge as per site/user requirment. | 260 | Point | - | - |