Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.9 CrAdmitted-Finance | ₹5.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹6.2 Cr+₹27.5 L (4.63%)Admitted-Finance | ₹6.2 Cr+₹27.5 L (4.63%) | L2 | Admitted-Finance |
| 3 | L3₹7.2 Cr+₹1.3 Cr (21.2%)Admitted-Finance | ₹7.2 Cr+₹1.3 Cr (21.2%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical 9TH FLOOR 920 WAVE SILVER TOWER SECTOR 18 NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | - | - | Rejected-Technical Disqualified as per DTCN |
| 5 | Rejected-Technical | - | - | Rejected-Technical Disqualified as per DTCN |
| Sl No | Description | Qty | Unit | EVAC ENGINEERING PROJECTS PVT. LTD. L3 | M/s Krishna Refrigeration L2 | UNIQUE ENGINEERS PVT LTD L1 |
|---|---|---|---|---|---|---|
| 1.00SUB HEAD 'I' - MACHINERY | ||||||
| 2.00Supplying, Installing, testing & commissioning of AHRI certified Twin Screw water chilling machine with VFD each having 250TR (756000 K.Cal. / hr.) actual capacity at chilled water inlet/ outlet temperature of 12 deg.C /6.5 deg.C with chilled water circulation rate of 600 USGPM (nominal) and condenser water inlet/ outlet temperature of 32.2 °C / 36.4 °C with circulation rate of 1000 USGPM (nominal) suitable for stepless continuous capacity control from 100% to 25% and operation on refregerant R-134a for screw type machine each comprising of the following complete as per specifications and as reqd.(Note1:The chilling unit shall have COP of 5.8 and IPLV not less than 7.5 at AHRI condition.Note2:The IKW/Tr at actual operating condition shall not exceed 0.68KW/Tr,Note :3 In case of multi compressor configuration the capacity of all compressor shall be same: Note 4: The chilling machine shall carry a warranty of 3 years)(Make: Trane/ Carrier/ York) | ||||||
| 3.00Twin screw type helical rotary compressor semi-hermatic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications. | ||||||
| 4.001 No.- Suitable capacity squirrel cage induction motor with class B / H (As per manufacturers standards) insulation suitable for operation on 415±10% volts, 3-phase, 50Hz A.C. supply. | ||||||
| 5.00Variable Frequency Drive (with necessary logic controller for speed variation) for the motor with CTs, over load/ under voltage protection, protection against phase reversal, single phase preventors, timer control & trip circuit complete as required. (The VFD shall beunit mount | ||||||
| 6.001 Set- Microprocessor based BMS compatible control panel with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc. | ||||||
| 7.00Necessary drive arrangement | ||||||
| 8.001 No.- ASME stamped matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes. Fouling factor 0.001 (FPS Unit). Pressure drop in condenser shall not exceed 20 ft of Wg. | ||||||
| 9.001 No.- ASME stamped matching shell and tube DX / flooded type chiller for screw type units of MS shell and copper tubes. Fouling factor 0.0005 (FPS Unit). The pressureop in chiller shall not exceed 20 ft of Wg. | ||||||
| 10.001 Lot- Refrigerant piping fittings, valves and accessories to inter connect compressor, condenser, chiller and expansion valve, sensing element for HP/LP/ Anti freez etc complete as required. | ||||||
Tender Value
₹6.7 Cr
Closing Date
21 Dec 2021, 5:00 pmClosed
CGM PC
IDCO Tower Janpath Bhubaneswar
SITC of 3x250 TR HVAC system including operation and Maintenance during Guarantee or Warranty period at Office cum Commercial Complex Badmal Jharsuguda
2021_IDCO_72711_1
PC/EST/E-41/2021-22
National Competitive Bid
Electrical Works
Item Rate
90 days
Badmal Jharsuguda
Please refer Tender Document
3 documents required · 3 mandatory
₹11,800
Exempted
Chamber of CGM PC
30 Apr 2022
17 Nov 2021
22 Dec 2021
17 Nov 2021
21 Dec 2021
7 Dec 2021
17 Nov 2021 - 22 Nov 2021
24 Nov 2021
Amount
SUB HEAD 'I' - MACHINERY
Supplying, Installing, testing & commissioning of AHRI certified Twin Screw water chilling machine with VFD each having 250TR (756000 K.Cal. / hr.) actual capacity at chilled water inlet/ outlet temperature of 12 deg.C /6.5 deg.C with chilled water circulation rate of 600 USGPM (nominal) and condenser water inlet/ outlet temperature of 32.2 °C / 36.4 °C with circulation rate of 1000 USGPM (nominal) suitable for stepless continuous capacity control from 100% to 25% and operation on refregerant R-134a for screw type machine each comprising of the following complete as per specifications and as reqd.(Note1:The chilling unit shall have COP of 5.8 and IPLV not less than 7.5 at AHRI condition.Note2:The IKW/Tr at actual operating condition shall not exceed 0.68KW/Tr,Note :3 In case of multi compressor configuration the capacity of all compressor shall be same: Note 4: The chilling machine shall carry a warranty of 3 years)(Make: Trane/ Carrier/ York)
Twin screw type helical rotary compressor semi-hermatic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications.
1 No.- Suitable capacity squirrel cage induction motor with class B / H (As per manufacturers standards) insulation suitable for operation on 415±10% volts, 3-phase, 50Hz A.C. supply.
Variable Frequency Drive (with necessary logic controller for speed variation) for the motor with CTs, over load/ under voltage protection, protection against phase reversal, single phase preventors, timer control & trip circuit complete as required. (The VFD shall beunit mount
1 Set- Microprocessor based BMS compatible control panel with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc.
Necessary drive arrangement
1 No.- ASME stamped matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes. Fouling factor 0.001 (FPS Unit). Pressure drop in condenser shall not exceed 20 ft of Wg.
1 No.- ASME stamped matching shell and tube DX / flooded type chiller for screw type units of MS shell and copper tubes. Fouling factor 0.0005 (FPS Unit). The pressureop in chiller shall not exceed 20 ft of Wg.
1 Lot- Refrigerant piping fittings, valves and accessories to inter connect compressor, condenser, chiller and expansion valve, sensing element for HP/LP/ Anti freez etc complete as required.
Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc.
Lot- Water flow switches at inlet and outlet of condenser & chiller, water drain & air purge valves wherever required.
Lot- Suction line and chiller insulation with minimum 19mm thick polvinyl / nitrile rubber insulation finished with 0.63mm thick G.S.S. cladding complete as required.
Lot- Frame work (including victaulic couplings at the inlet & outlet of cooler & condenser; & painting of all components) for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads/ springs.
Lot- Initial / first charge of refrigerant gas & compressor oil
Refrigerant piping shall be factory assembled as per the specifications.
Additional Safety Devices shall include Internal Thermostat for Compressor Motor, Fusible Plug, Discharge Gas Thermostat, Operation Hour-Meter etc.
Lot - RCC/ Cement concrete foundation
Make:Carrier/ Traine / York
Condenser Water Pump
Supply, erection, testing and commissioning of End suction type Horizontal Condenser water pump set capable of delivering 1000 USGPM of water against 30 mtrs head each comprising of the following and complete as per specifications and as required.(Note: In case the reuired flow rate is higher than 1000USGPM the pump shall match the same) as required. (Make Pump: Grundfoss/ Xylime/ Armstrong/Wilo, Make Motor: Grundfoss/ ABB/ Siemens/ Crompton)
1 No. - End Suction type centrifugal pump with bronze impeller
1No.- Suitable HP, TEFC squirrel cage induction motor of efficiency class IE3, 1450 RPM, operating on 415±10%volts, 3phase, 50HZ A.C supply
Lot- Base frame with Antivibration pads, Coupling and Coupling guard
All the pumps mentioned above shall be complete with mechanical seals, rubber flexible connections with M.S. flanges etc. and drain connections.
Lot - RCC/ Cement concrete foundation
Chilled Water Pumps with VFD
Supply, erection, testing and commissioning of End suction type Horizontal Chilled water pump set capable of delivering 600 USGPM of water against 24 mtrs head each comprising of the following and complete as per specifications and as required.(Note:In case the reuired flow rate is higher than 600USGPM the pump shall match the same) as required. (Make Pump: Grundfoss/ Xylime/ Armstrong/Wilo, Make Motor: Grundfoss/ ABB/ Siemens/ Crompton)
1 No. - End Suction type centrifugal pump with bronze impeller
1No.- Suitable HP, TEFC squirrel cage induction motor of efficiency class IE3, 1450 RPM, operating on 415±10%volts, 3phase, 50HZ A.C supply
1 No- Suitable capacity VFD with sensors (VFD to be installed near the pump or in the panel as per standard design)
Lot- Expanded polystrene (TF/FR Quality) insulation of not less than 50mm thick duly cladded between aluminium sheets of 0.5mm thickness and properly clamped to pump in two semicircular sections as per specifications.
Lot- Base frame with Antivibration pads, Coupling and Coupling guard
All the pumps mentioned above shall be complete with mechanical seals, rubber flexible connections with M.S. flanges etc. and drain connections.
Lot - RCC/ Cement concrete foundation
Supplying, installing, testing and commissioning of Induced draft FRP cooling tower of 300TR (900000 K.Cal /hr.) heat rejection capacity with eliminators complete with water basin either fitted with spray nozzles or having self rotating sprinklers, statically and dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with TEFC induction motor with efficiency class IE3, suction screen make up quick fill arrangement, overflow and drain connections with necessary valves and suitable aluminum inspection ladder, access arrangement for cooling tower interior, anti vibration mountings etc. complete as per specification and as reqd.
Entering water temperature :36.4°C, Leaving water temperature : 32.2°C. Designed wet bulb temperature 85 Deg F flow rate 1000 USGPM,Wet bulb approch-5 deg F
Type of fan : Aerodynamic Propeller .Type of motor : Weather proof, Less than 600 RPM with Single Fan or Less than 1000 RPM with Twin Fan Cooling tower
Lot- RCC / Cement concrete foundation alongwith frame for installation of cooling tower
Double Skinned Floor mounted Horizontal Type Air Handling Units
Supply, installation,testing & commissioning of factory fabricated Double Skinned Chilled Water AHU (horizontal floor mounted) fabricated out of 25 mm thick panels consisting of pre plasticized GI casing of thickness 0.8mm outside layer & 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.5 mm), 6 row deep cooling coil, blower motor TEFC type of efficiency class IE3 suitable for operation on 415volts±10%,50Hz±5% AC supply, efficiency class IE3, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 18G sheet with PUF insulation, 150 mm dial type pressure guage (2 nos), industrial type thermometer (2 nos), auto purge valve whereever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities.(Make:Zeco/ Edgtech/ VTS/ Voltas/ Waves Aircon)
6000 cfm, 50 mm static pressure.(GF 2 nos)
4000 cfm, 50 mm static pressure.(2nos each for FF,2nd Floor)
Double Skinned Ceiling Suspended Air Handling Units
Supply, installation,testing & commissioning of factory fabricated Double Skinned Chilled Water Ceiling suspended AHU fabricated out of 25 mm thick panels consisting of pre plasticized GI casing of thickness 0.6mm outside layer & 0.6 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with plug fans suitable for operation on 415 Volt 3 phase supply with electric motor of efficiency class IE3 suitable for static pressure as mentioned below, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.41 mm), 4 row deep cooling coil, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 18G sheet with PUF insulation auto purge valve whereever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities.The AHU shall be complete with starter wired remote ON/OFF operation and temperature control
2500 cfm, 30 mm static pressure.
3000 cfm, 30 mm static pressure.
4000 cfm, 30 mm static pressure.
Double skinned Ceiling Suspended FCU
Supply, installation,testing & commissioning of factory fabricated Double Skinned Chilled Water Ceiling suspended FCU fabricated out of 40 mm thick panels consisting of pre plasticized GI casing of thickness 0.6mm outside layer & 0.6 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower fans suitable for operation on 230 Volt 1 phase supply with three speed electric motor of efficiency class IE2/IE3 suitable for static pressure as mentioned below,wired remote for ON/OFF,speed control and temprature control with thermostat minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.41 mm), 3 row deep cooling coil, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 18G sheet with PUF insulation auto purge valve whereever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities..(Make:Zeco/ Edgtech/ VTS/ Voltas/ Waves Aircon)
1600 cfm with 12 mm static pressure
2000 cfm with 12 mm static pressure
Providing, Installation, Testing and Commissioning of floor/ ceiling mounted HRU having efficiency of 75% and above with energy recovery wheel, suction and discharge DIDW forward curved centrifugal blowers with suitable motor for fans of efficiency class IE3, leak proof casing as per specification including starters for heat recovery wheel and blowers along with relays, prefilter, fine filter etc as required.(The manufacturer of Heat Recovery Wheel & Heat Recovery Unit should be same.)(Make:DRI/ Greenheck)
1800 cfm supply & 1650 cfm exhaust(2nos each for FF & 2NDF)
2800 cfm supply & 2650 cfm exhaust(For GF)
Supplying, installation, testing and commissioning of following direct driven Tube axial type fan and casing suitable for smoke exhaust application & suitable for operation at 300 Deg C for 2 hours Class H rating. Motor shall be suitable for 415 Volt 50 c/s, 3 ph AC supply and of efficiency class IE2.The fan shall be equipped with mounting bracket & outlet cone required at discharge. (Make:Kruger/ Alstom/ Systemair)
12000 cfm, 15 mm Spwg (Basement)
Supplying, installation, testing and commissioning axial flow fan of following capacity complete with totally enclosed fan cooled 3 Phase IE2 motor, multi sheaved pulley on motor and fan shaft and vibration isolator. The fan shall be of low noise level and low RPM (less than 1000 RPM) and shall be equipped with bracket and inlet & outlet cone. (Make:Kruger/ Alstom/ Systemair)
10000 CFM, 12mm Spwg for liftwell pressurisation.
20000 CFM, 12mm Spwg for liftwell pressurisation.
SUB HEAD 'II' - PLUMBING
Chilled Water Piping (Nitrile Rubber Insulation, Inside the Building)
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water plumbing inside the building ( with necessary clamps, vibration isolators and fittings fittings like elbows, tees, reducers, bends, MS flanges but excluding valves, strainers, guages etc) duly insulated with following thickness cross linked close cell performed section of polyethylene insulation applied by adhesive to standard specificationand finally applying 0.63mm Aluminium sheet cladding complete with type3, grade I roofing felt strip (as per IS: 1322 as amended upto date) at the joints etc. as per specifications and repairing of damage to the building as required complete in all respect. ( The piping shall include drain valve, purge valve, socket thermowell as required) Note : The pipes of size 150 mm and below shall be MS 'C' Class as per IS 1239. Pipe sizes above 150 mm shall be welded black steel pipe heavy class as per IS 3589,from minimum 6.35 mm thick MS sheet for pipes upto 350 mm dia and from 7mm thick MS sheet for pipes od 400 mm dia and above.
25 mm dia (32 mm thick insulation)
32 mm dia (32 mm thick insulation)
50 mm dia (32 mm thick insulation)
65 mm dia (32 mm thick insulation)
80 mm dia (32 mm thick insulation)
150 mm dia (32 mm thick insulation)
250 mm dia (32 mm thick insulation)
Valves & Strainer In Chilled Water Line
Supplying, fixing, testing and commissioning in position of following valves, strainers, guages in the chilled water plumbing confirming to minimum PN16 pressure rating, duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
Supply, installation, testing and commissioning of Ball/Butterfly valves complete with companion flanges, nuts, bolts, gaskets etc. as specified and position confirming to standard specification
Note: size from and above 200 mm dia will be gear operated
25 mm dia(Butterfly valve)
32 mm dia(Butterfly valve)
40 mm dia (Butterfly valve)
50 mm dia (Butterfly valve)
65 mm dia (Butterfly valve)
150 mm dia (Butterfly valve)
Supply, installation, testing and commissioning of Balancing valves complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position conforming to standard specification.
150 mm dia
Supply, installation, testing and commissioning of Dual plate type check valves (NRV) complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position conforming to standard specification.
150 mm dia
Supply,installation,testing and commissining of MS fabricated "Y" type strainers with removable type bronze screen with 3mm perforation & permanent magent etc.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.
32 mm dia
40 mm dia
50 mm dia
65 mm dia
150 mm dia
Supply, installation, testing & commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50mm valves and 7 Bar for 65mm & above. Valves should have pressure rating of 25 Bar minimum.
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
Motorised valve
Supply, installation, testing and commissioning of Motorised butterfly valves with Actuator including provision for mannual operation duly insytalled complete with companion flanges, nuts, bolts, gaskets etc. as specified and position confirming to standard specification
150 mm dia
Expansion Tank
Supply, Installation ,Testing and commissioning of pressurised water expansion tank of 1000 lt capacity in chilled water circuits along with necessary accessries such as pumps (1 working + 1 standby), strarter panel, 2 nos pressure switches, air separator of suitable size in order to keep chilled water system under pressure and to prevent entrapment of air in the system. The tank shall be pre-charged steel rxpansion tank with replaceable heavy duty butyl rubber bladder, system/ drain/ charge connection with valves, with all accessories and safety fixtures required for proper functioning of the complete hydronic system as required.
Condensate Drain Piping
Supplying, fixing, testing and commissioning of G.I. 'B' Class medium water pipes for Condensate Drain of following size along with necessary clamps, fittings such as bends, tees etc. adequately supported duly insulated as per specifications and as required. (for AHU & FCU drain)
25 mm dia
32 mm dia
50 mm dia
Ball valve for drain connection 32 mm
Ball valve for drain connection 25 mm
Condenser Water Piping
Supplying,laying/ fixing, testing and commissioning of Condenser water pipes M.S 'Heavy' Class ERW conforming to IS:1239 / 3589 complete of following sizes and materials along with necessary clamps, vibration-isolators, and fittings such as bends, tees etc but excluding strainer and guages etc adequately supported on rigid supports etc as per specification and as required.
80 mm dia
200 mm dia
400 mm dia
Valves & Strainer In Condenser Water Line
Supplying, fixing, testing and commissioning in position of following valves, strainers, guages in the Condenser water plumbing confirming to PN16 pressure rating as the connected piping and adequately supported as per specifications.
Supply, installation, testing and commissioning of Butterfly valves complete with companion flanges, nuts, bolts, gaskets etc. as specified and position confirming to standard specification
Note: size from and above 200 mm dia will be gear operated
80 mm dia
200 mm dia
Supply, installation, testing and commissioning of Balancing valves in position conforming to standard specification.
200 mm dia
Supply, installation, testing and commissioning of Dual plate type check valves (NRV) in position conforming to standard specification.
200 mm dia
Supply, installation, testing & commissioning of Strainer of the following sizes conforming to standard specification.
200 mm dia Y strainer
400 mm dia pot strainer
Motorised valve
Supply, installation, testing and commissioning of Motorised butterfly valves with Actuator including provision for mannual operation complete with companion flanges, nuts, bolts, gaskets etc. as specified and position confirming to standard specification
200 mm dia
Supply, installation, testing and commissioning of mercury filled 'V' form thermometer with copper well of approved make conforming to technical specifications.
Supply, installation, testing and commissioning of common pressure guage with appropriate range with both side cock valve of approved make of dia 100 mm conforming to techinical specifications.
Sub Head 'III' - Ducting & Grills
Rectangular GI Ducting (Factory Fabricated)
Supply, installation, balancing and commissioning of factory fabricated G.S.S. (Class VIII 120 GSM) rectangular ducting complete with neoprene rubber gaskets, elbow, splitter dampers, vanes, hangers, supports etc as per approved drawings and specifications of following sheet thickness complete as required.
Rectangular GI Ducting (Site Fabricated)
Supply, installation, balancing and commissioning of site fabricated G.S.S. (Class VIII 120 GSM) rectangular ducting complete with neoprene rubber gaskets, elbow, splitter dampers, vanes, hangers, supports etc as per approved drawings and specifications of following sheet thickness complete as required.
Acoustic Lining of Duct
Supply & fixing of Acoustic lining of supply air duct and plenum with 25mm thick resin bonded glass wool having density 32 Kg/CuM, with 25 mmX 25 mm GI section of 1.25 mm thick, at 600 mm center to center covered reinforced plastic Tissue paper & 0.5 mm thick perforated Aluminium sheet (30% perforation) fixed to inside surface of the ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc as required & as per specifications. and as per approved shop drawings.
Duct Insulation
Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (class O) insulation on existing duct after applying two coats of cold setting adhesive (CPRX compoun) . The joint shall be sealed with 50 mm wide 3 mm thick self adhesive nitrile rubber tape insulation complete as per specification and as required.
Fire Dampers
Supplying, installation, testing & commissioning of fire dampers in supply air duct/ main branch/ return air duct as and where required of required size i/c control wiring as per specification as required.
Spring return type so as to close the damper in the event of power failure and open the same in case of power being restored. (To be used in conjunction with damper actuator) and also close in case of fire signal as required and as per specification.
Fusible link type as per UL- 555 (to be installed in return air path) of required size with fusible link. The damper shall have limit switch to switch off the AHU when damper shuts off.
Damper Actuator
Supply, installation, testing and commissioning of Motorised Spring Return Actuator for devices upto 0.8 sq. metre with control panel ,temperature sensor .The price shall include control cabling including necessary step down transformers etc. as may be required .(Make of fire sensor & controller :Belimo)
Supplying, installation, testing & commissioning of Powder coated extruded Aluminium grills and diffusers as required
Diffuser with VCD with anti smudge ring and removable core
Diffuser with anti smudge ring and removable core
Grill including linear grill with volume control damper
Grill including linear grill
Supplying & fixing extruded aluminium fresh air intake louvers with bird screen, pre filter and VCD as required.
Insulation
Supplying & fixing of thermal insulation on exposed roof (underdeck) with 13 mm thick cross linked closed cell polyethylene FR-XPE insulation, tape & adhesive (pidilite SR- 998) as required.
Sub Head 'IV' - Electric Works
Electrical Control Panel in AC plant
For 3 x 250 TR Rotary Screw Water Chilling M/C (2W + 1S ), 3 Nos Cond Water Pump, 3 Nos CHW Pump, 3 Nos cooling tower
Supplying, installing testing and commissioning of MV Panel Board suitable for Bus Trunking Termination from Top/ cable termination as the case may be for 3 phases, 415 V, 50 HZ with 1000 Amp Aluminium busbar, fabricated from minimum 2mm thick CRCA sheet powder coated through seven tank process facility for prickling and degreasing, powder coat painting, complete with following mountings, inter connections etc.as required.
Note: All MCCB shall have Ics = 100% Icu
Incomer : 1 Nos (Normal Supply).
1000 Amp ACB (MDO Type) 415 V ACB TP + NL 50 KA incoming manual drawout type microprocessor based electronic trip adjustable protection relays complete with O/L, S/C and E/F protection, shunt trip relay .
1 No.Ammeter with ASS and CTs of rating 1000/5A.
1 No.Voltmeter with VSS.
Digital multifunction meter suitable for displaying and recording voltage, current, pf, KW, KVAr, KWhr etc and compatible for communication with BMS,
3 Nos.phase indicating lamps, 2 Nos ON/OFF indicating lamps.
1 No.Trip push button
1 Set Castel Key Interlock
Incomer : 1 Nos (DG Supply).
800 Amp ACB (MDO Type) 415 V ACB TP + NL 50 KA incoming manual drawout type microprocessor based electronic trip adjustable protection relays complete with O/L, S/C and E/F protection, shunt trip relay .
1 No.Ammeter with ASS and CTs of rating 800/5A.
1 No.Voltmeter with VSS.
Digital multifunction meter suitable for displaying and recording voltage, current, pf, KW, KVAr, KWhr etc and compatible for communication with BMS,
3 Nos.phase indicating lamps, 2 Nos ON/OFF indicating lamps.
1 No.Trip push button
1 Set Castel Key Interlock
Outgoing
3 Nos.630 Amps. 415 V 35 KA TP+NL MCCB outgoing for 250 TR chillers,,ON/OFF indication,3 nos CTs with Multi function meter
3 Nos. 100 Amps. MCCB TP+NL 35 KA with Star delta starter ON/OFF push button,On/OFF/TRIP indication,loacl/remote S/S,3 nos CTs,Multi function meter
3 Nos. 100 Amps. MCCB TP+NL 35 KA with VFD starter(rate of VFD and logic controller considered along with the rate of chilled water pump) ON/OFF push button,On/OFF/TRIP indication,loacl/remote S/S,3 nos CTs,Multi function meter
3 Nos 63 Amp MCCB TP+NL 35 KA with star delta starter with ON/OFF push button,ON/OFF/TRIP indication,Local/Remote S/S, 3 nos CTs,Multi function meter for cooling tower motor.
1 Nos. 200 Amps. MCCB TP+NL 35 KA (for spare).
1 Nos. 63 Amps. MCCB TP+NL 35 KA (for spare).
Cooling tower isolator panel (To be installed in terrace)
Supplying installation, testing and commissioning of outdoor type isolator panel with 6 nos 63 Amp SDF Unit with solid copper link , bottom entry gland plate for isolation of cooling tower motors during maintenance as required.
AHU with HRU Panel
Supply, installation, testing and commissioning of Cubicle type wall/ floor mounted front operated panel board made of 2mm thick CRCA sheet duly treated in 7 tank process and powder coat painting with 200 Amp TPN Copper busbar suitable for operation on 415 Volt, 3 ph, 50 c/s supply conforming to the specifications. (Each starter shall be provided with necessary contactors, O/L relay, single phase preventor, ON/OFF push button & indication, necessary auxilliary contacts for remote operation and indication)
Incomer - 1 No 40 Amp TPN MCCB, 10 KA with phase indicating lamp and instrument fuse.
Outgoing
1 No 40 Amp TPN MCB with DOL starter for AHU , ON/OFF push button and indicating lamps,Local/Remote S/S.
1 Nos- 25 Amp MCB with DOL starter for Auto/Manual & Local/Remote S/S
2 No 10 Amp DP MCB
Note : The rate should include cost of control cabling in the AHU room on existing ladder type tray.The panel shall be provided with necessry relays to accepr fire signal and should be BMS compatible.
Basement Ventilation
Supply, installation, testing and commissioning of Cubicle type wall/ floor mounted front operated panel board made of 2mm thick CRCA sheet duly treated in 7 tank process and powder coat painting with 200 Amp TPN Copper busbar suitable for operation on 415 Volt, 3 ph, 50 c/s supply conforming to the specifications. (Each starter shall be provided with necessary contactors, O/L relay, single phase preventor, ON/OFF push button & indication, auto necessary auxilliary contacts for remote operation and indication)
Incomer : 1 Nos.
100 Amp MCCB TP + NL 35 KA adjustable protection release
1 No.Ammeter with ASS and CTs of rating 100/5A.
1 No.Voltmeter with VSS rating.
3 Nos.phase indicating lamps
Outgoing
Note: The panel shall be designed for automatic operation of all the fans in fire conditions.potential free contact shall be provided through relay module conected to the fire alarm system
Pressurisation Fan Panel (Located at Lift machine room)
Supply, installation, testing and commissioning of Cubicle type wall/ floor mounted front operated panel board made of 2mm thick CRCA sheet duly treated in 7 tank process and powder coat painting with 200 Amp TPN Copper busbar suitable for operation on 415 Volt, 3 ph, 50 c/s supply conforming to the specifications. (Each starter shall be provided with necessary contactors, O/L relay, single phase preventor, ON/OFF push button & indication, auto necessary auxilliary contacts for remote operation and indication)
Incomer : 1 Nos.
100 Amp MCCB TP + NL 35 KA adjustable protection release
1 No.Ammeter with ASS and CTs of rating 100/5A.
1 No.Voltmeter with VSS rating.
3 Nos.phase indicating lamps
Outgoing
Note: The panel shall be designed for automatic operation of all the fans in fire conditions.potential free contact shall be provided through relay module conected to the fire alarm system
Cable tray
Supplying instalaltion hot dip galvanized ladder type cable tray of following size including installation along wall/ suspended from ceiling with brackets/ threaded suspenders including bends etc as required.
150 mm (W) X 50 mm (H) with 1.6 mm thick sheet
300 mm (W) X 50 mm (H) with 1.6 mm thick sheet
450 mm (W) X 50 mm (H) with 2 mm thick sheet
Cable
Supply of 1.1 KV grade Aluminium XLPE power cable of following size suitable for 415 Volt, 3Ph, 50 c/s supply.
3.5C X 240 sqmm
3C X 25 sqmm
3C X 16 Sqmm
Supplying installation testing and commissionning 1.5 sqmm 4 core copper armoured FRLS PVC sheathed cable
Supplying installation testing and commissionning 6 sqmm 3 core copper armoured FRLS PVC sheathed cable
Supplying installation testing and commissionning 16 sqmm 3 core copper armoured FRLS PVC sheathed cable
Cable laying
Laying of cable of cable of various size on ladder type cable tray including providing cable ties or laying through existing pipe as required.
upto 35 sqmm
Above 185 sqmm and upto 400 sqmm
TERMINATION OF CABLES :-
Supply & Making end Termination with brass compression gland and aluminium lugs for PVC insulated and PVC sheathed cable of 1.1 kv grade (without cost of Cable)
3.5C X 240 sqmm
3C X 25 sqmm
3C X 16 Sqmm
Supply & Making end Termination with brass compression gland and Copper lugs for PVC insulated and PVC sheathed cable of 1.1 kv grade (without cost of Cable)
3C X 6 sqmm
3C X 16 sqmm
Sub Head - "V" - Operation and Maintenance During Guarantee/ Warranty Period
Operation & maintenance (routine & preventive) of the high side & low side of the air-conditioning plant comprising of all the machinary, equipments installed in the AC Plant room including cooling towers in one shift during the defect liability period of one year as required as per maintenance schedule. (The rate shall be quoted on per month basis for 12 hrs ).
GST Applicable Extra
M/s Krishna Refrigeration
EVAC ENGINEERING PROJECTS PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
BOQ_374000.xls
BOQ • 0.39 MB
Bid.HVAC.doc.pdf
Tender Documents • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .