CWE Jaipur
HQ CWE Jaipur, Kalyan Marg, Jaipur
REPAIR/ MAINT OF HT 11 KV AND 33 KV NETWORK INCLUDING BREAKERS PANELS RMUS VCBS AND OTHERS ACCESSORIES AT ZONE-III AND BHANKORTA UNDER GE (S) JAIPUR
2022_MES_504309_1
CWE/JPR(S)/82126/E8
Open Tender
Miscellaneous Works
Item Rate
365 days
GE (S) Jaipur
Enlisted with MES in Class E and above and category b (iii) or b(ii)
7 documents required · 7 mandatory
₹500
Yes
GE (S) Jaipur
₹44,000
Yes
16 Mar 2022
28 Jan 2022
25 Feb 2022
28 Jan 2022
23 Feb 2022
11 Feb 2022
60 days
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in any type of soil complete all as specified and directed.
M&L for sand cushioning to PVC underground cable with tibba sand and punning to provide a required cover complete all as specified and directed. Note:- Punned thickness shall be considered for payment purpose
Supplying and laying factory made un-reinforced PCC precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in any type of soil complete all as specified and directed.
Removing of excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50metre above the starting point complete all as specified and directed
S&F in repair post insulator with GI post for holding fixed/moving contact assembly suitable for Air break gang operated switch 200 Amps, 11000 volts grade complete all as specified and directed
S&F in repairs lightening arrestor expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 11000 volts complete all as specified and directed
S&F in repairs lightening arrestor expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 33000 volts complete all as specified and directed
Supply, laying and commissioning in repair XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 volts grade IS-7098 marked, suitable for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing complete all as specified and directed of following cross sectional area :-
(a) 95 Sqmm, 3 core
(b) 120 Sqmm, 3 core
(c) 185 Sqmm, 3 core
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of following sizes :-
(a) 95 Sqmm x 3 core
(b) 120 to 185 Sqmm x 3 core
M&L for cable end termination, jointing kit, HT 33 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 33 KV grade for cable size 300 sqmm 3 core complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 33 KV grade, heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 33 KV grade for cable size 300 sqmm 3 core complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of following sizes:-
(a) 95 Sqmm X 3 core
(b) 120 to 185 Sqmm x 3 core
M&L for cable jointing kit, HT 11 KV grade, heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of following sizes:-
(a) 95 Sqmm X 3 core
(b) 120 to 185 Sqmm x 3 core
M&L for cable, jointing kit, HT 33 KV grade, heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 33 KV grade for cable size 300 sqmm 3 core complete all as specified and directed.
M&L for fault finding in U/G cable using fault locating machine on requirement for 33/11 KV HT cables of any type/size complete all as specified and directed.
Supply, installing, testing and commissioning of Air break, gang operated, triple pole switch 200 Amp rating complete with fuse carriers and HT fuse elements., outdoor, horizontal / vertical mounting type (ISI marked), mechanically operated, mounted on insulators and frame work with operating mechanism worked from ground level with locking arrangements including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections including taking down old UNSERVICEABLE items complete all as specified and directed
S&F in repair of metallic (brass/alloy steel) fixed contact set single pole including fixing screwed nuts and washers suitable for air break gang operated switch of cap 200/400 amp 3 pole 11000 volts grade complete all as specified and directed
S&F in repair of metallic (brass/ alloy steel) moving contact set single pole including screws, nuts and washers suitable for air break gang operated switch of capacity200/400 Amp 11000 volts including taking down complete all as specified and directed
S&F in repair of flexible copper strips including fixing screws, nuts and washers suitable for air break gang operated switch 200/400 amps 11000 volts for single phase complete all as specified and directed
M&L for shifting of trolley mounted transformer of any capacity any location within the station to location of defective transformer and connecting to HT cable 11000 volt in coming from existing source and LT outgoing cables complete all as specified and directed NOTE: T&P required for loading, unloading, shifting transporting the trolley mounted transformer back to E/M yard is deemed to be inclusive of the quoted rate.
M&L for Dehydration /filtration of transformer oil existing transformer installed at site with portable plant to improve the dielectric strength 60 KV including testing of dielectric strength after dehydration and filtration at site complete all as specified and directed. NOTE: Pre-heated oil shall be topped up as required at site before the process; oil will be measured and paid separately under respective item.
Supply & filling of transformer oil in transformer installed/ at site for toping up the level of oil having dielectric strength >65 KV during filling after initial filtration conforming to IS-335 complete all as specified and directed. NOTE: Transformer oil shall be supplied in sealed container and empty barrel of transformer oil will be deposited by contractor in E/M store yard.
M&L for disconnecting of defective transformer (indoor/outdoor type) 11KV/433 volts copper/ Aluminium wound from power mains and dismantling the same from 2/4 pole structure/ platform mounted and transporting the same to authorised workshop and opening the transformer cover, draining out of transformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts ie tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation on existing 2/4 pole structure/ platform with necessary fixing arrangement including connecting up electrically, commissioning and testing all as directed by Engineer-in-Charge and specified in particular specification of the following capacity :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
NOTE: U/S items required for replacement shall be measured and paid separately
Supply only following parts for indoor /outdoor transformer :-
(a) HT coil with insulation for Aluminium wound transformer of any capacity.
(b) LT coil with insulation for Aluminium wound transformer of any capacity.
(c)HT coil with insulation for copper wound transformer of any capacity.
(d)LT coil with insulation for copper wound transformer of any capacity.
Supply only HT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
Supply only LT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
S&F in replacement of breather assembly of transformer with silica gel complete with end fitting as directed by Engineer -in-Charge
M&L for painting of outer body of transformer of following capacity applying two coats of synthetic enamel paint of specified colour by spraying painting complete including preparation of old surfaces, removing, cleaning of oil, grease, dirt all as specified and directed of following capacity :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
supply and filling as in replacement of silica gel inside the breather assembly and fixing properly with transformer complete all as specified and directed
M&L scrapping/ removing old painted surfaces and preparation of surface of steel member on HT 2Pole structure including two coats of aluminium paint to steel structure over one coat of red oxide using brush/spray at site all as specified and directed
M&L for surface Dressing/Cleaning of various 11/33 KV sub-stations and fencing free from vegetation of any type once in months for entire contract period including trimming of tree branches, bushes, creepers etc. complete all as specified and directed. Note:- quoted rates per sqm shall be for cleaning of one year with frequency of 2 Months.
Supply and laying at 11 KV Switchyard/substation sand cushioning (river sand) which will be laid upto height of 30 cm including levelling. The sand should be supported by the bricks coloured in white respectively at the edge of the perimeter of switchyard/installation complete all as specified and directed
Supply and laying at 11 KV Switchyard/substation, stone aggregate of size 40-65 mm upto height of 40 cm over the sand cushioning (river sand) including levelling. The aggregate should be supported by the bricks coloured in white respectively at the edge of the perimeter of switchyard/installation complete all as specified and directed
Supply and laying at 33 KV Switchyard/substation sand cushioning (river sand) which will be laid upto height of 30 cm including levelling. The sand should be supported by the bricks coloured in white respectively at the edge of the perimeter of switchyard/installation complete all as specified and directed
Supply and laying at 33 KV Switchyard/substation, stone aggregate of size 50-80 mm upto height of 40 cm over sand cushioning (river sand) including levelling. The aggregate should be supported by the bricks coloured in white respectively at the edge of the perimeter of switchyard/installation complete all as specified and directed Note for item No. 34 to 36 :- It should be ensured that before laying stone aggregate and sand the grass or unwanted bushes shall be treated chemically to remove the unwanted vegetation and surface of the switchyard/installation should be made totally free from the existing unused aggregates without destroying the cable, earthpit etc at the installation.
S&F for HT/LT cables route indicator cast iron of suitable size along HT cable trench including painting and grouted in ground in PCC etc complete all as specified and directed.
M&L for calibration and setting of protection relay of any make or type fitted on 33 KV breakers, transformer Buchholz relay, WTI, OTT, PRV, control panel at MRS, 61 Cav, Ajaymeru station yard (details given below)and other locations as per IS and code of practice to insure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including synchronizing of the same with JVVNL/MRS setting to insure that fault shall not be travel to nearest source feeder including minor repair, replacement of wiring etc, if required complete all as specified and directed. (a) Incoming 33KV breaker :- 04 Nos (b) 33/11 KV, 5 MVA transformer relay control panel -04 Nos
M&L for calibration and setting of protection relays of any make or type fitted on 11 KV VCBs (details given below) as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including synchronizing of the same with MRS setting to ensure that fault shall not travel to nearest source feeder including minor repairs, replacement of wiring etc, if required complete all as specified and directed (a) outgoing/Incoming VCB 11 KV- 09 Nos(HQ SWC MRS)
NOTE FOR ITEM NO. 38 to 39 (i) The calibration and setting must be completed within 30 days from the date of commencement to avoid any major break down. (ii) The calibration and setting shall be carried out by only qualified and experienced engineer. (iii) The relay setting shall be carried out once in a three month as per load and site conditions to avoid and any fault travel to next adjacent source breaker and shall be monitored regularly. (iv) For payment purpose the payment for calibration & setting of relay twice in 06 months is considered as each job. The cost of monitoring is also included in the item rate. (v) Certificate of rep of authorised person should be submitted before calibration/setting the VCBs The record of calibration/setting of relays shall be submitted by the contractor
M&L for Disconnecting of HT supply from 11 KV VCB of capacity upto 1250 Amps-12 Nos. for overhauling of mechanism trolly and carry out repair works, servicing complete with decarburizing the contact points, cleaning with CRC solution etc testing after repair complete all as specified and directed. Make :- VCB AREVA/ALSTOM/CG Note:- (i) Parts replaced of VCB shall be measured and paid separately under respective items. (ii) Servicing shall be done in every month without any extra cost of Govt.
Disconnecting of HT supply from 33 KV VCB/SF6 CB - 4 Nos with panel capacity of 1250 Amp outdoor type for overhauling of mechanism and carry out repair works, servicing complete with decarburizing the contact points, cleaning with CRC solution etc testing after repair complete all as specified and directed Note:- (i) servicing will be done twice at the duration of 3 months and thiss will be considered as one job.
Replacement of following parts for Srl item Nos 40 & 41 shall be AREVA/CG/alstom:-
(a) Supply only Shunt Trip Coil, operating voltage 24 Volts DC suitable for 11 KV VCB/ SF6 gas breaker. Make :CG/Alstom/ABB/ Areva
(b) Supply only TNC switch suitable for 11 KV VCB Make- CG/Areva/Schneider/ABB
(c) Supply only digital type ammeter/volt meter for 11 KV VCB
(d) Supply & Fix HT fuse 30 to 200 amps capacity complete all as specified and directed
S&F of PT fuse 3.15 Amp suitable for 11 KV VCB complete all as specified and directed
S&F of anti-pumping relay 2NO+2NC, 24V DC, 6Amp complete all as specified and directed. Make Siemens/L&T/BCH
S&F of auxillary contactor for contact multiplication 7NO+7NC, 24V DC, 6 Amp complete all as specified and directed. Make Siemens/L&T/BCH
M&L in replacement of spring charge motor assembly with Gear Assembly operating voltage 220 V AC/ DC suitable for 11 KV VCB of Areva /CG complete all as specified and directed.
Supply and Fixing in replacement LED/Neon indicator Lamps with holder size 22.5mm of different colour (24 V/220 V, AC/DC) complete all as specified and directed.
M&L for rectification, detection of gas leakage & refilling of the same in compatible to the pressure marked by the OEM complete all as specified and directed
Supply & fixing HT Jumper in repair/replacement on existing OH circuit/two Pole/four Pole Structure etc including ACSR Conductor (Weasel) using PG clamp /lugs, fasteners etc complete all as specified and directed.
Laying/fixing only in repair and replacement of HT cable of size 95 to 185 Sqmm XLPE insulated armoured cables with stranded aluminium conductor, 1100 volts grade including connecting and testing laid in floors/ roads or on walls/poles complete all as specified and directed of following size of cable:- Note:- (i) Earth work, excavation shall be measured & paid separately under respective item of Schedule). (ii) Cables will be issued under Sch ‘B’ free for fixing only.
Supply only VCB interrupter for 11 KV VCBs or RMUs complete all as specified and directed
Supply only numerical relay having over current earth fault protection, three phase symmetrical fault etc. complete all as specified and directed Make:- CG Cat part CGI 14 N / or equivalent in Schneider,ABB
Supply and Fixing chain link fencing of size 100mm x 100mm, 4mm dia including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provision of binding wire and taking out old fencing all as directed and specified.
M&L for MS work such as angle iron fencing post struts and flat iron fillets etc of grade Fe-310-0, including drilling holes, punching, splitting ends to secure chain link fencing or fixing of barbed wire to posts including all necessary cutting, welding drilling, bolting or riveting etc and including bands strap support for chain link, steel screw as required, flat iron strip fixed to secure the fencing on posts complete and rolled mild steel Framed work as in Gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, Doors etc. to be prepared for hanging or sliding with & including either hooks & hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails & guides) & hanging; also fastening & fixing complete GDE Fe 410-0 or Fe 310-0 including taking down old fencing complete all as specified and directed
Schedule of Credit
SHREE BHAGWATI ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .