| Sl No | Description | Qty | Unit | PERFECT IMAGE SOLUTIONS L2 | Computer Gallery L1 | P R INFOSYS L3 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel (VDS / UL approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 5" alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. | ||||||
| 1.01 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software.. (Approval standards: VDS / UL ); ( Approved Make: Siemens / Edward / Honeywell). | 1 | Item | 2,50,000 ₹2,50,000 Lowest | 2,81,200 ₹2,81,200 | 3,61,000 ₹3,61,000 |
| 2.00 | Supply, Installation,Testing & Commisioning of Micropresssor controlled IP Addressable multisensor detector IP 54 ( VDS / UL approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. ( Approved Make: Siemens / Edward / Honeywell) | 126 | Nos | 2,800 ₹3,52,800 | 2,000 ₹2,52,000 Lowest | 2,340 ₹2,94,840 |
| 3.00 | Supply, Installation,Testing & Commisioning of IP Addressable Manual Call Point (VDS / UL approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. ( Approved Make: Siemens / Edward / Honeywell).. | 8 | Nos | 3,500 ₹28,000 Lowest | 3,500 ₹28,000 Lowest | 4,000 ₹32,000 |
| 4.00 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL approved) approved. ( Approved Make: Siemens / Edward / Honeywell). | 8 | Nos | 5,000 ₹40,000 Lowest | 5,000 ₹40,000 Lowest | 5,640 ₹45,120 |
| 5.00 | SITC of Power supply 23OV AC to 24V DC with all other accessories. (Make: Reputed) | 1 | No | 1,500 ₹1,500 | 200 ₹200 Lowest | 600 ₹600 |
| 6.00 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex / Gloster/Polycab/RR Cable) with 20 mm NB PVC rigid conduit pipe on the surface of the wall. (Make: Precisson/Polycab/AKG-Medium) | 3,390 | Mtrs | 110 ₹3,72,900 | 60 ₹2,03,400 Lowest | 110 ₹3,72,900 |
| 16.00TERMS & CONDITIONS | ||||||
| 17.00(i) Rate should be quoted inclusive of all applicable taxes and Duties etc including GST. (ii) The Agency must procure the materials for the Manufacturer / OEM or from their authorized sales channel, so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. iii) Documents that authenticate such procurement from the manufacturer /OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work / submission of bill. iv) If any refurbished material is supplied and installed, penal action will be taken as per existing rules. | ||||||
Tender Value
Refer Docs
EMD Value
₹16,100
Closing Date
19 Jun 2026, 2:00 pmClosed
EXECUTIVE ENGINEER PWD MALDA ELECTRICAL DIVISION
O/O THE EXECUTIVE ENGINEER PWD MALDA ELECTRICAL DIVISION Singatala Malda PIN 732101
Construction of 20 Bedded Matri Maa (Mini Mother and Child Hub) Building at Manikchak RH, Malda - SITC of Microprocessor based Addressable Fire Detection System
2026_WBPWD_5015138_1
WBPWD/EE/MED/e-NIQ-28/2026-27
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
Manikchak
Please refer Tender documents.
7 documents required · 7 mandatory
₹16,100
5 Aug 2026
8 Jun 2026
22 Jun 2026
8 Jun 2026
19 Jun 2026
12 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel (VDS / UL approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 5" alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. | |||||
| 1.01 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software.. (Approval standards: VDS / UL ); ( Approved Make: Siemens / Edward / Honeywell). | 1 | Item | 10 | ₹10 |
| 2 | Supply, Installation,Testing & Commisioning of Micropresssor controlled IP Addressable multisensor detector IP 54 ( VDS / UL approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. ( Approved Make: Siemens / Edward / Honeywell) | 126 | Nos | 10 | ₹1,260 |
| 3 | Supply, Installation,Testing & Commisioning of IP Addressable Manual Call Point (VDS / UL approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. ( Approved Make: Siemens / Edward / Honeywell).. | 8 | Nos | 10 | ₹80 |
| 4 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL approved) approved. ( Approved Make: Siemens / Edward / Honeywell). | 8 | Nos | 10 | ₹80 |
| 5 | SITC of Power supply 23OV AC to 24V DC with all other accessories. (Make: Reputed) | 1 | No | 10 | ₹10 |
| 6 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex / Gloster/Polycab/RR Cable) with 20 mm NB PVC rigid conduit pipe on the surface of the wall. (Make: Precisson/Polycab/AKG-Medium) | 3,390 | Mtrs | 10 | ₹33,900 |
| 16TERMS & CONDITIONS | |||||
| 17(i) Rate should be quoted inclusive of all applicable taxes and Duties etc including GST. (ii) The Agency must procure the materials for the Manufacturer / OEM or from their authorized sales channel, so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. iii) Documents that authenticate such procurement from the manufacturer /OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work / submission of bill. iv) If any refurbished material is supplied and installed, penal action will be taken as per existing rules. | |||||
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
Tendernotice_2.pdf
PDF • 0.43 MB
Tendernotice_3.pdf
PDF • 2.93 MB
BOQ_5083742.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .