Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.3 L+₹94,535 (5.15%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹20.5 L+₹2.1 L (11.6%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
10 Mar 2020, 3:00 pmClosed
Lt Col PK Morolia
GE (AFA) Hyderabad, Pin- 500043
REPAIRS RENEWAL OF INTERNAL ELECTRIFICATION TO MD ACCN FOR DOMESTIC AREA AT AFA HYDERABAD
2020_MES_321435_1
8956/02/E8
Open Tender
Civil Works
Item Rate
330 days
GE (AFA) Hyderabad
As per Tender Documents
5 documents required · 5 mandatory
₹500
Yes
GE (AFA) Hyderabad
₹50,000
Yes
24 Oct 2020
4 Feb 2020
11 Mar 2020
4 Feb 2020
10 Mar 2020
18 Feb 2020
4 Feb 2020 - 7 Feb 2020
Amount
Taking down carefully unserviceable point wiring of light points, fan, socket out let ceiling rose etc on teak wood battens / PVC pipes / casing & caping including removing the materials from site and making good the disturbed portion of walls / floors ceiling etc including painting/colour washing/distempering complete all as per existing specification of the surroundings complete all as specified and as directed.
M&L for cutting chases, pinning in. making good to facings on brick wall / stone, concrete block where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10 cm girth including painting/colour washing/distempering complete all as per existing specification of the surroundings complete all as specified and as directed.
M & L for Point wiring with 1.5 Sq mm multistranded copper conductor wire with unsheathed, FRLS grade PVC insulated, single core with earth continuity conductor of 1.5 sqmm FRLS grade PVC insulated multistranded copper conductor and including rigid PVC conduit of suitable size but not less than 20mm dia. and all accessories fixed to the surface of the roof/ walls or in chases etc. including terminal boxes made out of MS sheet of thickness should be not lessthan 1.2mm thick for fixing of switches, fan regulators socket outlet etc along-with 3mm thick top laminated bakelite sheet for housing switches, etc complete all as specified and as directed for the following :-
(a) One light point controlled by one switch
(b) One light point controlled by two nos 2 way switches
(c) One ceiling / Exhaust fan point controlled by one switch
(d) One three pin socket 5 Amps independent
(e) One Bell point controlled by one bell switch
(f) One three pin socket 5 Amps plug point on same board
(g) One 3 pin 5amps socket outlet independent but below the switch board of light points in the same vertical plane.
M & L for Point wiring with 1.5 Sqmm multistranded copper conductor wire with unsheathed, FRLS grade PVC insulated, single core with earth continuity conductor of 1.5 sqmm FRLS grade PVC insulated multistranded copper conductor and including rigid PVC casing & capping of suitable size and all accessories fixed to the surface of the roof/ walls or in chases etc. including PVC terminal boxes for fixing of switches, fan regulators socket outlet etc. complete all as specified and as directed for the following :-
(a) One light point controlled by one switch
(b) One light point controlled by two Nos, 2 way switches
(c) One ceiling / Exhaust fan point controlled by one switch
(d) One three pin socket 5 Amps plug point independent
(e) One Bell point controlled by one way bell switch
(f) One three pin socket 5 Amps plug point on same board
(g) One 3 pin 5amps socket outlet independent but below the switch board of light points in the same vertical plane.
All as per Ser item No 3 above but with 2.5 sq mm multistranded copper wire with 2.5 Sq mm multistranded copper wire as earth continuity conductor in and including PVC conduit (not less than 20 mm) complete all as specified and as directed for 15 Amps socket.
All as per Ser item No 4 above but with 2.5 sqmm copper cable in the PVC casing & capping complete all as specified and as directed for 15 Amps socket.
All as per Ser item No 3 above but with 1.5 sqmm copper cable in the existing Concealed/surface conduit complete all as specified and as directed for one light point controlled by one switch.
All as per Ser item No 4 above but with 2.5 sq mm copper cable in the existing Concealed/surface casing / caping complete all as specified and as directed for one light point controlled by one switch
S&F ceiling rose, three terminal, PVC/polycarbonate, insulated body, ISI marked complete all as specified and as directed.
S&F Switch Piano type polycorbonate white 1 way, 6A, 240Volts complete all as specified and as directed.
S&F Bell Switch flush type polycorbonate white 6A 240Volts complete all as specified and as directed.
S&F Socket outlet polycorbonate white 6A - 2/3 pin complete all as specified and as directed.
S&F Switch socket combination polycorbonate white 2 in 1, 3 pin, 5 flush type universal complete all as specified and as directed.
S&F Switch socket combination polycorbonate white 2 in 1, 3 pin, 5 and 15 Amp flush type universal complete all as specified and as directed.
S&F Switch 15 Amp flush type universal complete all as specified and as directed.
S&F Socket out let polycorbonate white 2 in 1, 3 pin, 15 Amp flush type universal complete all as specified and as directed.
S&F Bell Multi Music type / Ding Dong AC 230 V complete all as specified and as directed.
S&F stepped type polycorbonate white electronic fan regulator flush type complete all as specified and as directed.
S&F polycarbonate white angle holder/batten holder insulated complete all as specified and as directed.
S&F PVC Gang Box suitable for 5Amps Switch Socket Combination complete all as specified and as directed.
S&F in repair of PVC Gang Box suitable for 15Amps Switch Socket Combination complete all as specified and as directed.
S & F modular switch 6 Amp one way 230 V AC complete all as specified and as directed.
S & F modular switch 16 Amp one way 230 V AC complete all as specified and as directed.
S & F modular switch 6 Amp bell push, 230 V AC complete all as specified and as directed.
S & F modular socket outlet 6Amp intel multi socket for all pins 230 Volts AC supply complete all as specified and as directed.
S & F modular socket outlet 16 Amp and 6 / 16 Amp heavy duty 230 Volts AC supply complete all as specified and as directed.
S & F modular step type fan regulator heavy duty 230 Volts AC supply complete all as specified and as directed.
S& F in repairs 1x10W LED Tube light fitting having housing with high pressure die cast alluminium, poly carbonate front diffuser cover including LED driver, Lamp and all accessories internally pre-wired, connecting up with three core twisted flexible copper conductor cable with cross sectional area 1.0 Sq mm i complete all as specified and as directed. Make : Havells Cat No-ENDURALINEARNEOBS10WLED830SPCWH, PhillipsCatNo-BN021CLED10S65000PSUGRS1, Crompton Cat No-LCTL-9-CDL,Bajaj Cat No-BCLSB 10 NW
S&F in repairs surface mounting / wall mounted LED tube light fitting 1x20 Watt (Lumen output not less than 1980 lumen) high efficiency, anti glare, maintenance free operation including LED driver, Tube 20W/18W and mounting arrangements, all accessories internally pre-wired, connecting up with three core twisted flexible copper conductor cable white colour with suitable size complete all as specified and as directed. Make : Havells Cat No-ENDURALINEARNEOBS20WLED830SPCWH, Phillips Cat No-BN021CLED20SPSUCWGRS2,Crompton Cat No-LCTL-18-CDL,Wipro Cat No-LM34-251 XXX 57TLGI
S&F in repairs LED lamp 15 Watts suitable for pintype / thread type holder complete all as specified and as directed.
S&F in repairs LED lamp up to 9Watts suitable for pintype / thread type holder complete all as specified and as directed.
S&F in repairs LED driver suitable to existing LED light fittings of capacity up to 9W, 230Volts, 50 Hz supply, complete all as specified and as directed.
S&F tube rod 28 watt for replacement of unserviceable rod from existing 28 watts FTL fitting complete all as specified and as directed
S&F in repairs LED street light luminaries 20-25 W including suitable inbuilt driver and complete accessories with MS housing finished & having clear acrylic cover, and provision of 1.20 mtr bracket made with light grade GI pipe of 25 mm dia for fixing on walls with MS flat (25mm X 3mm) clamps and anchor fastner complete all as specified and as directed. Make: Crompton Cat No-LSTS-25 CDL, Havells Cat No-ENDURAPEARLSL25WLED757 SASYTOPC, Bajaj cat No-BRLEP25W LED WH
S&F in repairs flush / surafce type light fittings of size 600x600mm suitable for 36W LED complete with inbuilt driver surface mounted slim box type luminaries with CRCA housing white powder coated finish suitable to operate with 230 V AC, complete with all accessories internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with cross sectional area 1.0 Sq mm complete all as specified and as directed. Make : Havells cat No-ENDURA SLIMPROPLUS2X2PLR28/36W LED 857MOD, Crompton Cat No- LCTRS 36 CDL
S&F in repairs flush / surface type light fittings square / round as per site requirement suitable for 18W LED complete with inbuilt driver surface mounted slim box type luminaries with CRCA housing white powder coated and finish suitable to operate with 230 V AC complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed. . Make :Lucker Cat No-LNPSRS18, Crompton cat No-LCTLSN 18 CDL
S&F laminated hylum sheet 3 mm thick with suitable chromium plated machine screws with cup washers for fixing switches/ sockets etc including cutting for accommodating the switches / sockets and removing the damaged switch plates by carefully removing the switches /wiring/ sockets for refixing and re connecting the removed wires testing the circuits complete all as specified and as directed.
M&L for Sub Main wiring with four runs of 10 sq mm 1100 V grade (nominal area) single core FRLS grade PVC insulated unsheathed wire with multi-stranded copper conductor, drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with two runs of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.
(iv) Six runs of cable and one run of PVC conduit / casing caping will be measured as one unit length..
M&L for Sub Main wiring with four runs of 6 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable size with all necessary fittings, surface in walls/roof/floor duly earthed with two runs of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Six runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
M&L for Sub Main wiring with two runs of 6 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable sizewith all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
M&L for Sub Main wiring with two runs of 6 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through existing conduit with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
M&L for Sub Main wiring with two runs of 4 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable sizewith all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
M&L for Sub Main wiring with two runs of 2.5 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through and including medium grade, rigid non-metallic PVC conduit / casing & caping (as per site requirement) of suitable sizewith all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note:-(i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
M&L for Sub Main wiring with two runs of 2.5 sq mm 1100 V grade (nominal area) single core PVC insulated unsheathed cable multi-stranded copper conductor drawn through existing conduit with all necessary fittings, surface in walls/roof/floor duly earthed with one run of single core cable of same size but green in colour as continuous earthing wire and connecting to common earth dolly complete and after taking out the existing sub-main wiring etc. complete all as specified and as directed.
Note :- (i) Necessary PVC dummy plates & rigid PVC junction boxes for maint./inspection purpose as required on site/directed by Engr-in-charge shall deemed to be included in the quoted rate.
(ii) Same size wire shall be used for phase, neutral & earth conductor
(iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue only for phase, black for neutral and green for earth leads.
(iv) Three runs of cable and one run of PVC conduit / casing caping will be measured as one unit length.
Taking out old unserviceable distribution board of any type and S&F MCB DB SPN 4 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the existing wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F MCB DB SPN 8 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the existing wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F MCB DB SPN 12 way with copper bus bar & neutral link double door type to be fixed in the wall including connections and making good the disturbed surface of wall to perfectly match with the existing wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F MCB DB double door 4 way triple pole vertical type 415 volts 50 Hz AC supply suitable for 4 pole MCCB incomer, fixed to the existing wall (concealed/surface) after removing the existing un serviceable MCB DB and reconnecting the electrical connections and making good the disturbed surface of wall to perfectly match with the existing wall complete all as specified and as directed.
Taking out old unserviceable distribution board of any type and S&F MCB DB,,double door 8 way triple pole vertical type 415 volts 50 Hz AC supply suitable for 4 pole MCCB incomer, fixed to the existing wall (concealed/surface) after removing the existing un serviceable MCB DB and reconnecting the electrical connections and making good the disturbed surface of wall to perfectly match with the existing wall complete all as specified and as directed. Note : MCCB will be measured and paid separately under relavant items.
Taking out old unserviceable MCCB of any type and S&F MCCB 4 pole 63 Amps, 16KA breaking capacity, 415Volts 3-phase supply complete all as specified and as directed.
Taking out old unserviceable MCCB of any type and S&F MCCB 4 pole 100 Amps, 16KA breaking capacity, 415Volts 3-phase supply complete all as specified and as directed.
Taking out old unserviceable MCB any type and S&F MCB SPN 6 to 32A, 10KA rupturing capacity complete all as specified and as directed.
Taking out old unserviceable MCB any type and S&F Fix MCB SP 6 to 32 A 10 KA rupturing capacity complete all as specified and as directed.
Taking out old unserviceable MCB and S&F single pole and neutral enclosure with a two pin and earth plug and socket complete with one number single pole MCB 20 Amps , 240 Volts complete all as specified and as directed.
Dismantling & Taking down single phase energy meter of any capacity / make from the existing position and supply and fixing single phase tamper proof KWH meter with LCD display and optical port with accuracy class-1%, base mounting type of capacity 10-60 Amps complete all as specified and as directed Make : L&T (Cat No. WM101BC 7DDH) or euivalent to in Secure / HPL
Dismantling & Taking down three phase, prewired, counter type energy meter of any capacity / make from the existing position and supply and fixing three phase, prewired, counter type tamper proof KWH meter with optical port with accuracy class-1%, base mounting type of capacity 10-40Amps complete all as specified and as directed Make : L&T (Cat No. WM301BC 6D2O) or euivalent to in Secure / HPL
S&F in repairs LED Tube light rods 18/20 Watt, 4 ft long, fixed on existing patty as in replacement of old unserviceable tube light rods complete all as specified & directed.
S & F in repairs LED retrofit lamp 9 watt B-22 holder base with polycarbonate body and aluminium heat sink complete all as specified and as directed.
S & F in repairs LED retrofit lamp 7 watt B-22 holder base with polycarbonate body and aluminium heat sink complete all as specified and as directed
Supply and fix in replacement of Decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit CFL 20 W spiral / 10 W LED bulb with B22 base complete all as specified and as directed
S&F in replacement of Ceiling fan capacitor AC 230 volts, 2.5/3.15 MFD complete all as specified directed.
OM SAI POWER SYSTEMS
EXELLENT POWER CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .