Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹97,000
Closing Date
19 Apr 2025, 4:00 pmClosed
Executive Engineer Electric Division-II JPDCL
Executive Engineer Electric Division-II JPDCL
Creation of 400 KVA Distribution Substation along with HT Line on 9.0 Mtr. ST Poles with 70mm2 AB Cable for Providing dedicated Power Supply to Police Hospital Jammu within the jurisdiction of Electric Division-II Jammu on turnkey basis.
2025_PDD_274924_1
Enit No 09 of 2025 dated 26-03-2025
Open Tender
Electrical Works
Turn-key
60 days
ED-II JPDCL
As per Enit and SBD.
9 documents required · 9 mandatory
₹1,000
Executive Engineer ED-II JPDCL
₹97,000
28 Apr 2025
29 Mar 2025
21 Apr 2025
29 Mar 2025
19 Apr 2025
29 Mar 2025
Amount
Creation of 11/0.433kV, 400 KVA, 3-phase Distribution Substation
Supply, Installation & commissioning of 11/0.433 KV, 400 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) along with LV Cable Box having detachable Alumnium Gland plate including Transportation (As per Latest Amendment upto date )
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Pole mounted LT Distribution Box for 400 KVA DTR with 2 No. Triple Pole MCCB of 400 Amp with adjustable overload release of (80-100%) for incomer & & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Construction of Cement Platform 8'x8'x3' (3 feet above & 3 feet below ground level ) for 400 KVA SubStation along with the mesh fencing around the Periphery. (complete Job)
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete
Supply, Installation, Testing and Commissioning of 11 KV HT Line using 70mm² AB Cable on 9 Mtr ST Poles
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Erection, Testing & Commissioning of 70 mm² AB Cable ( HT) (3X70+1X95 mm2)
Supply, Erection, Testing & Commissioning of Suspension/Tension Clamp with eye hook
Supply, Erection, Testing & Commissioning of Heat Shrinkable Outdoor Cable Termination Kit
Supply, Erection, Testing & Commissioning of Straigh Through Cable Jointing Kit
Supply, Erection, Testing & Commissioning of Galvanized Nuts and Bolts.
Supply, Erection, Testing & Commissioning of Danger Plates
Supply, Erection, Testing & Commissioning of Anti-Climbing Device with Clamps
Supply, Erection, Testing & Commissioning of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Cement Bottoming 1:2:4 mix as per REC Standards .45 cum/pole
Supply, Erection, Testing & Commissioning of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
The Trikuta Engineer (BID ID -2355620)
M/S RATHER CONSTRUCTIONS AND TRADERS (BID ID -2359136)
SUMIT SHARMA (BID ID -2359161)
M/S PVM INFRA (BID ID -2359243)
M/S SHAH CONSTRUCTION (BID ID -2357758)
V K ELECTRICAL CONTRACTOR (BID ID -2357279)
M/S COMBINE GROUP OF ENGINEERS (BID ID -2358775)
Jatinder Singh (BID ID -2359253)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .