GE 866 EWS CARNICOBAR
GE 866 EWS CARNICOBAR PIN-913866 C/O 99APO
REPAIR/MAINTENANCE OF LT PANEL BOARD, FEEDER PILLAR BOX AND ALLIED WORKS AT AF STATION CARNICOBAR
2026_MES_763452_3
8816/E8
Open Tender
Civil Works
365 days
GE 866 EWS CARNICOBAR AIR FORCE STATION
As per tender documents
9 documents required · 9 mandatory
₹500
GE 866 EWS
₹88,000
Yes
8 Jul 2026
8 Jul 2026
29 Jul 2026
8 Jul 2026
22 Jul 2026
15 Jul 2026
8 Jul 2026 - 11 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking out old unserviceable panel board from existing position and making good of disturbed portion of floor and wall including disconnecting all cables and joints complete all as specified and as directed. | 3 | EACH JOB | - | - |
| 2 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 1.3 x 1.1x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :- | 1 | EACH JOB | - | - |
| 2.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 400 Amps,36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 2.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 250 Amps, 36 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(ii) MCCB 3 Phase, 04 Pole 100 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(iii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(iv) MCB C Type 32 Amps SPN - 02 Nos | - | - | - | - |
| 3 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 1.3 x 1.1x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :- | 1 | EACH JOB | - | - |
| 3.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 350 Amps,36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 3.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 100 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(ii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 04 Nos
(iii) MCCB 3 Phase, 04 Pole 40 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 06 Nos | - | - | - | - |
| 4 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 1.3 x 1.1x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :- | 1 | EACH JOB | - | - |
| 4.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 400 Amps,36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 4.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 100 Amps, 36 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 05 Nos
(ii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 04 Nos
(iii) MCCB 3 Phase, 04 Pole 40 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.12 MB
8816Tender.pdf
Tender Documents • 1.08 MB
BOQ_870472.xls
BOQ • 0.26 MB
8816changecategorycorrigendum3.pdf
PDF • 0.19 MB
Download all tender documents and submit your bid