Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.8 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST AND REASONABLE | |
| 2 | L2₹16.4 L−₹73,078 (4.26%)Rejected-Finance | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹17.2 LSame as L1Rejected-Finance 301 TULSI TOWER KHADAKPADA KALYAN THANE MAHARASHTRA 421301 | THANE | MAHARASHTRA | 421301 | L3 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
16 Oct 2021, 6:00 pmClosed
CWE AF Banrauli
HQ CWE AF BAMRAULI ALLAHABAD-211012
SPECIAL REPAIR TO VCB AND RMU AT VARIOUS LOCATIONS AT AF STATION BAMRAULI.
2021_MES_473554_1
87161/C/E8
Open Tender
Civil Works - Others
Item Rate
182 days
Bamrauli
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) Bamrauli
₹42,000
Yes
26 Nov 2021
14 Sept 2021
25 Oct 2021
14 Sept 2021
16 Oct 2021
1 Oct 2021
Amount
Cable jointing kit for 11 KV (earthed) heat shrinkable, indoor (end) termination joint suitable for cross sectional area 185 Sqmm, 3 core aluminium conductor XLPE Cable including jointing material and accessories complete.
Dismantling of existing HT 4 pole structure 11 metre long with GOD, LA and all accessories ie. Cross arms, brackets, clamps, nut bolts, stay assembly, demolition of foundation of pole etc complete all as specified and directed by Engineer-in-Charge.
Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick directly burried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5metre below the ground level connected to GI strip 32x6 mm by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 40 mm bore medium grade for protection of earth strip, 20 mm bore medium grade for watering, PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, funnel with wire mesh, 50 mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8 mm MS bars at 150 mm centre to centre both ways, CI frame and charcoal dust and common salt, all as shown in electrical plate No. 3 of MES SSR part-I and making test point as specified including excavation & earth work in any type of soil and connecting the earthing to an earthing point/equipment as specified and directed & testing on completion. NOTES : (i) The concrete pit shall be made in PCC 1:3:6 type C-1, using 20mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order (iii) Items includes cost of 7.5 metre earth lead strip. Any variation in length shall be adjusted through deviation order. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides
Titco Electricals
Diamond Electric Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .