Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.7 CrAccepted-AOC | ₹1.7 Cr | L1 | Accepted-AOC LOWEST QUOTED HENCE ADMITTED |
| 2 | L2₹1.8 Cr+₹11.9 L (7.09%)Rejected-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹1.8 Cr+₹11.9 L (7.09%) | L2 | Rejected-AOC NOT LOWEST QUOTED HENCE NOT ADMITTED |
| 3 | L3₹1.9 Cr+₹19.3 L (11.5%)Rejected-AOC | ₹1.9 Cr+₹19.3 L (11.5%) | L3 | Rejected-AOC NOT LOWEST QUOTED HENCE NOT ADMITTED |
| 4 | L4₹2.4 Cr+₹67.2 L (40.0%)Rejected-AOC | ₹2.4 Cr+₹67.2 L (40.0%) | L4 | Rejected-AOC NOT LOWEST QUOTED HENCE NOT ADMITTED |
| 5 | Rejected-Technical NO 9 1ST FLOOR C J N HERITAGE PWD MAIN ROAD AKASH NAGAR B NARAYANAPURA DOORAVANI NAGAR BANGALORE 560016 | BANGALORE | BENGALURU URBAN | KARNATAKA | 560016 | - | - | Rejected-Technical Not Admitted as representation has been rejected by NHEA |
Tender Value
Refer Docs
EMD Value
₹2.8 L
Closing Date
14 Feb 2023, 6:00 pmClosed
COL MANOJ NEGI
CWE AF North Bangalore Bellary Road JC Nagar Post Bangalore 560006
PROVISION OF AIR CONDITIONER FOR VARIOUS LABS AT SDI AF UNDER GE (AF) MARATHAHALLI
2023_MES_575688_1
87507CWEAFNMAR
Open Tender
Civil Works
Item Rate
360 days
GE (AF) MARATHAHALLI
AS PER NIT
7 documents required · 7 mandatory
₹2,000
GE (AF) MARATHAHALLI
₹2.8 L
Yes
10 Apr 2023
18 Jan 2023
20 Feb 2023
19 Jan 2023
14 Feb 2023
27 Jan 2023
20 Jan 2023 - 25 Jan 2023
Amount
Dismantling wall and ceiling boards (fibre, pulp, insulation etc.) and boarding any thickness, including cover fillets and removal out side of MoD land/Air Force Unit area without paying any extra etc. complete all as specified and directed.
S&F false ceiling grid of size 600 x 600 mm system using hot dipped galvanized steel section with precoated capping, main tee of size 24x32 mm having 0.27mm thick at every 1200mm centre to centre, cross tee of size 24x27 mm having 0.25mm thick at 600mm centre to centre and wall angle of size 19x19 mm having 0.35 mm thick fixed to the periphery of the wall, and suspended at every 1200mm centre to centre in both directed using 2.00 mm thick GI wire and fixing 600 x 600 x 16 mm mineral fibre tegular edge ceiling tiles of RH90 complete all as specified and as directed.
M&L for Second class hard-wood in scantlings for timber framed and fixed Clean sawn etc complete
M&L for 2nd class hardwood Plain fillets of exc 13 & n.exc 25 sqcm in square, rectangular or triangular in section, clean sawn, secured with nails or brads. etc. complete
M & L for 12mm thick Prelaminated particle board, interior grade, prelaminated one side with decorative choice lamination & other side balancing white lamination, fixed with screws to timber frame work.
M&L for 2nd class hardwood wrought finished fillets of bullnosed, splayed, chamfered or rounded on one edge or faceclean sawn fillets. square, rectangular or triangular Exc 3 & n.exc 6 sq.cm in section, , secured with nails or brads.
Preparation of new surface of wood and wood based surface of wood filler stain or varnish including knotting and stopping and all preparation work required and applying two coats of Synthetic varnish over a coat of Filler coat thin varnish etc complete all as specified.
M & L for framed work such as grill, gratings, etc with ends of bars shoulderedand /or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work corn-conforming to Fe.290. Gde -E-165, complete all as specified and directed.
S&F rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment as in gusset plate conforming ot Fe- 410-W-(Gde-E-250) quality A etc complete.
Preparation of new surfaces of steel and iron surface of any description, not otherwise descriped over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide complete all as specified
Demolition of brickwork or stone/ boulder masonry, built in cement mortar , incl all quions, arches, pillars, etc, but excluding ashlar facings, dressed stonework and precast concrete articles, complete all as specified and directed.
Material and labour for Pre-cast cement concrete block masonry with solid blocks, exc. 10 cm in width Type C1 1:3:6 (20 mm graded aggregate ) and setting in mortar CM 1:6, complete.
Material and Labour for PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in coping, mud stops, benching, water tank platform etc.on roof, chajja weathering, slightly rounded or chamfered angles and throating etc. including necessary form work complete as directed.
Rendering 15mm thick in cement mortar 1:6 on other than fare face of brick work or concrete surfaces and finishing the surface even & smooth without using extra cement
Rendering 15mm thick in patches in cement mortar in 1:4 on fare face of brick work or concrete surfaces even and smoothe without using extra cement.
M&L for preparation of new surface/undecorated surfaces of walls and applying two coats of Oil bound distemper over a coat of priming on plastered and other surfaces with alkali resistant priming paint including one coat of Birla white putty etc. complete all as specified.
M&L for preparation of new surface/undecorated surfaces of walls and applying two coats of Cement Base Paint of approved tint over a coat of priming on plastered and other surfaces with alkali resistant priming paint complete all as specified
Supply install, testing, commissioning of air cooled packaged air conditioner, comprising of Hermetically sealed scroll compressors with microprocessor based control,suitable for operation refrigerants (R-410A) of nominal capacity,inverter condensing unit of capacity 11 TRX3 with all standard fittings/specification as per manufacture with all items and acessories measured as below, The Inverter condensing will be mounted on roof top with proper bedding as per manufacturers specfication to avoide vibration on roof with out damaging the roof & structure for EURO & HAWK LAB/MIG-29 LAB/SU-30 Small LAB all as specified & directed by Eng - in - Charge
Supply install, testing, commission of AHU kit with expansion valves, with all acessories measured as below for EURO & HAWK LAB (one), Mig-29 LAB (one), SU-30Small LAB Three No) all as specified & directed by Eng - in - Charge
Supply install, testing, commission floor mounted AHU unit with pre-filter (EU4-10 MICRON/fine filter EU7-3 Micron),mixing box, out door (thermobreak profile),Dx coil,row & deep 6/8 rows ,fan DIDW, 33 TR/21000 CFM/ESP-40MM for EURO & HAWK LAB , with all acessories measured as below,all as specified & directed by Eng - in - Charge
Supply install, testing, commission floor mounted AHU unit with pre-filter (EU4-10 MICRON/fine filter EU7-3 Micron),mixing box, out door (thermobreak profile),Dx coil,row & deep 6/8 rows ,fan DIDW, 33 TR/24000 CFM/ESP-40MM for MIG-29 LAB,with all acessories measured as below,all as specified & directed by Eng - in - Charge
Supply install, testing, commissionfloor mounted AHU unit with pre-filter (EU4-10 MICRON/fine filter EU7-3 Micron),mixing box, out door (thermobreak profile),Dx coil,row & deep 6/8 rows ,fan DIDW, 33 TR/20500 CFM/ESP-40MM for SU-30 Small LAB,with all acessories measured as below,all as specified & directed by Eng - in - Charge
Supply install, testing, commissioning of air cooled packaged air conditioner, comprising of Hermetically sealed scroll compressors with microprocessor based control ,suitable for operation refrigerants (R-410A) of nominal capacity,inverter condensing unit of capacity 11TRx3 &11TRX2 with all standard fittings/specification as per manufacture with all items and acessories measured as below, The Inverter condensing will be mounted on roof top with proper bedding as per manufacturers specfication to avoide vibration on roof with out damaging the roof & structure for SU- 30 BIG LAB all as specified & directed by Eng - in - Charge
Supply install, testing, commission of AHU kit with expansion valves, with all acessories measured as below SU-30 Big LAB,with all acessories measured as below,all as specified & directed by Eng - in - Charge all as specified & directed by Eng - in - Charge
Supply install, testing, commission floor mounted AHU unit with pre-filter (EU4-10 MICRON/fine filter EU7-3 Micron),mixing box, out door (thermobreak profile),Dx coil,row & deep 6/8 rows ,fan DIDW, 33 TR/22000 CFM/ESP-40MM ,with all acessories measured as below,all as specified & directed by Eng - in - Charge
Supply install, testing, commission, floor mounted AHU unit with pre-filter (EU4-10 MICRON/fine filter EU7-3 Micron),mixing box, out door (thermobreak profile),Dx coil,row & deep 6/8 rows ,fan DIDW, 22 TR/15000 CFM/ESP-40MM, with all acessories measured as below,all as specified & directed by Eng - in - Charge
Supply & installation, testing of Copper pipe 11/8" as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation, testing of Copper pipe 1/2" ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Communication copper cable of size 2Cx0.75 sqmm,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Communication copper cable of size 5Cx1.5sqmm,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Power copper cable 4Cx6 sqmm multi stranded,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Power cable 8SWGI,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Drain pipe CPVC 32 MM dia,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of ODU stand ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of refrigerant gas charge R410A,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Factory made 25 MM thick puf rectagluar duct with angle flanges,supports,joints,gaskets,bolts & nuts etc ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Mouth piece duct & exposed duct-20G ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Acoustic insulation10MM thickness-class 1 plain ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Thermal insulation -13 MM thickness-class 0 AI foil,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Jet Nozzle,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Supply/return grills ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Collar dampers ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Fire retardant flexiable canvas connection ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of MS duct supports,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Volume control damper,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Control panel without VFD ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Expansion valve ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply & installation of Fire damper with fusiable link ,as per standard ,specification air conditioning manufacturer,all as specified & directed by Eng - in - Charge
Supply and lay & testing XLPE cable insulated, armoured electric cable(heavy duty) with stranded alunimum conductor 1100 volts grade,cross -sectional area as following . (a) 120 Sqmm x 3.5 Core
(b) 70 sqmm X 3.5Core
(c ) 25 sqmm X 4Core
(d) 10 x 2 sq mm
(e) 10 x 4 sq mm
M & L excavation in trenches in hard/dense soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables/errection of pole etc complete all as specified and as directed.
M & L for returning, filling in trenches incl spreading leveling watering and well ramming in layers with excavated soil not exc 25 cm thick in each layer complete as specified and as directed
M & L for removing excavated material not exceeding 50 mtr and depositing where directed to a distance not exc 1.5mtr above the starting point complete all as specified and as directed.
M & L for sand cushioning in trenches for cable cushining with a layer of river sand under and above the cable complete all as specified and directed.
M & L sub clas 'B' burnt bricks for cable protection complete as specified as directed
M & L for GI tubing light grade 80mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 50mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for PCC 1:2:4 type B1 with 20mm graded stone aggregate in copping of poles/filling road cutting stays ,incl necessary form work all as specified and as directed
Design Fabricating supply and errecting connecting and testing totally enclosed LT cubicle panel board 3 Phase 4 wire system indoor double door front and back opening type, flat canopy ,separate compartment for each control gear,cable alley, Air vent on both side of panel as per stranded size, provision of knock out type plates for various sizes of cable up to 120 Sqmm 3.5 core in and out , incoming and out going feeders duly marked on revited plates etc complete IP-56, CPRI approved factory made fabricated out of 2 mm thick CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour,built in industrial type locking arrangement on front and back ,and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs ,Panel mounted on Angle iron frame of 50x50x6mm thick duly painted and embeded in PCC 1:3:6 45 CM below ground level and 15 Cm above ground level and consisting the folowing.
(a) High breaking capacity MCCB 350 A ,36KA 415 V 50HZ 50 KA, 4pole (incommer) (b) High breaking capacity MCCB 200 A 36 KA Amps 50HZ 415 V 50 KA, 3 pole,(out going) (c) High breaking capacity MCCB 100 A 16 KA Amps 50HZ 415 V 50 KA, 3 pole,3 Nos (out going) (d) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic,non combustible,track resistant high strength FRP insulators 600 Amps for phases and 300 amps for neural set of 4 for RYB &N -01 set (e) Multi Display meter (LED Display) to read KWH, Amps,Volts and frequency etc of each phase (3PH, 4W IPM 240 V (L-N) 5 A Class 1 FM) (f) Indicator LED Type for RYB set of 3 - 01 set
Design Fabricating supply and errecting connecting and testing totally enclosed LT cubicle panel board 3 Phase 4 wire system indoor double door front and back opening type, flat canopy ,separate compartment for each control gear,cable alley, Air vent on both side of panel as per stranded size control gear, cable alley, provision of knock out type plates for various sizes of cable up to 120 Sqmm 3.5 core in and out , incoming and out going feeders duly marked on revited plates etc complete IP-56 CPRI approved factory made fabricated out of 2 mm thick CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour,built in industrial type locking arrangement on front and back ,and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs ,Panel mounted on Angle iron frame of 50x50x6mm thick duly painted and embeded in PCC 1:3:6 45 CM below ground level and 15 Cm above ground level and consisting the folowing.
(a) High breaking capacity MCCB 350 A ,36KA 415 V 50HZ 50 KA, 4pole (incommer) (b) High breaking capacity MCCB 100 A 16 KA Amps 50HZ 415 V 50 KA, 3 pole,04 Nos(out going) (c) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic,non combustible,track resistant high strength FRP insulators 600 Amps for phases and 300 amps for neural set of 4 for RYB &N -01 set (e) Multi Display meter (LED Display) to read KWH, Amps,Volts and frequency etc of each phase (3PH, 4W IPM 240 V (L-N) 5 A Class 1 FM) (f) Indicator LED Type for RYB set of 3 - 01 set
Supply & fix sheet metal encousure for DBs when MCBs to be used triple pole and neutral 6 way double door 415V
Supply and fix isolator TP 415 Volts for feeder DBs 100A TP MCB
Supply and fix isolator TPN 415 for feeder DBs 40 A TPN MCB
Design Fabricating supply and errecting connecting and testing totally enclosed LT cubicle panel board 3 Phase 4 wire system indoor single door front opening type, flat canopy ,separate compartment for each control gear,cable alley,Air vent on both side of panel as per stranded size control gear, cable alley, provision of knock out type plates for various sizes of cable up to 95 Sqmm 3.5 core in and out , incoming and out going feeders duly marked on revited plates etc complete IP-56, CPRI approved factory made fabricated out of 2 mm thick CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour,built in industrial type locking arrangement on front and back ,and pre wired with PVC insulated multi stranded copper conductor for controls and monitors,/ PVC sleeved aluminium strip for connecting MCCBs ,Panel mounted on Angle iron frame of 40x40x6mm thick duly painted and embeded in PCC 1:3:6 45 CM below ground level and 15 Cm above ground level and consisting the folowing:- Make: L&T/ Legrand / Schneider
(a) High breaking capacity Main Incomming high breaking capacity MCCB 4 Pole 200A, 50HZ Rapturing 50KA (SU- 30 BIG) (b) C' curveTPN MCB 40to100 amps 6 Nos (c) Multi Display meter (LED Display) to read KWH, Amps,Volts and frequency etc of each phase (3PH, 4W IPM 240 V (L-N) 5 A Class 1 FM) (d) Indicator LED Type for RYB set of 3 - 01 set
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 10A 240 Volts.
M & L for earth continuity conductor or main earthing lead fixed to wall / on suitable insulators , on batten or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to pole on any other indicated situation of size 25x4 mm GI strip all as directed.
Material and labour for earthing including testing, commissioning complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth strip wire 25x4 mm dia by means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt I. The work is inclusive of necessary earth work and PCC chamber in type B1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre complete including taken out old earthing complete all as directed Note: (i) The earth resistance shall be below 1 ohms during testing. Note (For item No 01 to 70) :-The Tenderer should visit the site before quoting the tender, and the Lowest Tenderer shall submit the design details along with duct layout drawing and technical litereatures of all the equipments duly vetted by NIT/IIT/ Govt Engineering college before commencemenbt of work the same shall be approved by the accepting officer. The Contractor shall be responsible to arrange skilled technician and arrange site required materials to execute the work smoothly without damaging the govt accessories,(scafoldings as required ,Shifiting of materails to roof top with own arrangement,including closing of old existing supply/return grills as required at site, making surface in walls/roof good, if any unseen job while excuting the work all as specified and directed by Eng - In - Charge.
Shree Ayyappa Engineering
kb technologies
C R R CONSTRUCTIONS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .