Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.0 LAccepted-AOC 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | ₹48.0 L | L1 | Accepted-AOC AOC Issued |
| 2 | L2₹53.5 LRejected-Finance DHARSHA NEAR MATH P O GOVT OF INDIA PRESS COLONY DIST HOWRAH PIN 711 112 | HOWRAH | HOWRAH | WEST BENGAL | 711112 | ₹53.5 L | L2 | Rejected-Finance that the bid is not L1 |
| 3 | L3₹60.0 LRejected-Finance 2ND FLOOR KAMARHATI 1 GRAHAM ROAD KAMARHATI KAMARHATI KOLKATTA WEST BENGAL 700058 | 24 PARAGANAS NORTH | WEST BENGAL | 700058 | ₹60.0 L | L3 | Rejected-Finance that the bid is not L1 |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
17 Nov 2023, 1:00 pmClosed
EEI,KNHED, PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Electrical Installation and fire detection system restroration work after distressed structure repair by PWD civil at different building in RG Kar Medical College Hospital
2023_WBPWD_596695_1
WBPWD/EE/KNHED/NIQ-88/23-24
Open Tender
ELECTRICAL WORKS ORG
90 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.1 L
17 Feb 2026
30 Oct 2023
21 Nov 2023
3 Nov 2023
17 Nov 2023
3 Nov 2023
Amount
Supply of delivery 1.1KV XLPE Aluminium Armoured Cables of following size [Make- Gloster/Polycab/RR Kabel] 4 Core 70 Sqmm
4 Core 95 Sqmm
4 Core 240 Sqmm
4 Core 300 Sqmm
5 Core 400 Sqmm
Laying of Cables on surface Laying of cable above 3½ core 50 sqmm and upto 3½ core 90sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting[2d/F-1]
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [2e/F-1]
Laying of cable of 4 core 240 sqmm and on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [2e/F-1]
Laying of cable of 4 core 300 sqmm and on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [2e/F-1]
Laying of cable of 4 core 400 sqmm and on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [2e/F-1]
Laying of cables Under ground/Trench Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed[1(b)/F-2]
Laying of one No. cable of 300 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed[NS]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :[7(c)/F-4] For 4 core 70 sqmm
For 4 core 95 sqmm
For 4 core 240 sqmm
For 4 core 300 sqmm
For 4 core 400 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :8(b)/F-5 3½ core 70 sqmm cable
3½ core 95 sqmm cable
3½ core 240 sqmm cable
3½ core 300 sqmm cable
3½ core 400 sqmm cable
Supply and Fixing of MS ladder type cable tray made of Hot dip GI sheet of 2mm Thickness and 600mm wide
Supply and fixing MS angle support made of 75mm x 75mm x 8mm MS angle for support the cable vertically on wall ncluding welding, hole cutting, 4nos bullet fastener and painting with 2 coat RO primer and Black Japan paint.
Hiring charges for scafflding arrangement including dismantling at the end of work and carriage for installation of cable tray outside of building around 9 mtr height from ground and 40 mtr wide.
SITC of floor mounting cubicle type indoor compartmentalized 415 Volt. 50 Hz. dust & moisture proof L.T. distribution panel board fabricated from 3mm CRCA sheet. The panel should have adequate strength and space to accommodate the incoming & outgoing witches and bus bars with all inter connections in between the switches & bus bars with solid copper rod / flexible wire of suitable capacity. The panel should be provided with cable alley for facilitating connection of all the incoming & outgoing XLPE cables with termination arrangements by supply & fixing copper terminal bar / bolt of required sizes. The 2 nos.
G.I earth bus bar should run along the full length of the panel board. The incoming terminals of ACB & MCCB as well as out going terminals of MCCB should be provided with Extra copper bar of suitable capacity for smooth termination of double feeders. All incoming / outgoing ACB / MCCB / SFU units should have identification as directed by the E.I.C. The panel board should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing. The panel board should be manufactured by CPRI Approved manufacturer :
Incoming :- S/F of 415 Volts (Uimp=12KV peak),Icu @ 415V=Ics=Icw=100% and Icw for 1 sec=50KA,1250 Amp,4P Drawout type with Microprocessor Based LSIGN release having adjustable overload with time delay,adjustable short circuit with time delay,Instanteneous current,adjustable earth faultwith time delay,neutral protection( min 50%,100%),12KV Impulse withstand capacity,temperature rise p rotection,inbuilt metering arrangement of class 1. There must be at least 4 NO +4NC AUXILIARY CONTACT.The circuit breaker are to be complied IEC/EN60947-2. ACB but with castle locking arrangement, as bus coupler including electrical connection with both the bus-bars. (Make – L & T,/Siemens/ABB/Schneider)---2 nos Type Test Certificates for short circuit withstand of 50KA(1swc) along with 415V( Uimp=12kv-peak)Icu@415V=Ics=Icw=100% must be produced
Bus bar chamber :- do-do 2000 Amp capacity 4 bar electrolytic tinned copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification and segregated in two (2) equal length by keeping space for suitable accommodation of bus-coupler in the center of BBC.---1 set
Bus -Coupler S/F of 415 Volts (Uimp=12KV peak),Icu @ 415V=Ics=Icw=100% and Icw for 1 sec=50KA,1250 Amp,4P Drawout type with Microprocessor Based LSIGN release having adjustable overload with time delay,adjustable short circuit with time delay,Instanteneous current,adjustable earth faultwith time delay,neutral protection( min 50%,100%),12KV Impulse withstand capacity,temperature rise p rotection,inbuilt metering arrangement of class 1. There must be at least 4 NO +4NC AUXILIARY CONTACT.The circuit breaker are to be complied IEC/EN60947-2. ACB but with castle locking arrangement, as bus coupler including electrical connection with both the bus-bars. (Make – L & T,/Siemens/ABB/Schneider)---1 nos Type Test Certificates for short circuit withstand of 50KA(1swc) along with 415V( Uimp=12kv-peak)Icu@415V=Ics=Icw=100% must be produced
Out Going a) S/F of 415 Volts 800A Amp, TPN SFU with sheet steel enclosure with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating(Make -L&T / Schnider/ ABB/Siemens, ---1nos
a) S/F of 415 Volts 630A Amp, TPN SFU with sheet steel enclosure with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make -L&T / Schnider/ ABB/Siemens, ---10nos
a) S/F of 415 Volts 400A Amp, TPN SFU with sheet steel enclosure with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make -L&T / Schnider/ ABB/Siemens, ---14nos
a) S/F of 415 Volts 250A Amp, TPN SFU with sheet steel enclosure with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make -L&T / Schnider/ ABB/Siemens, ---2nos
Dismanteling of old cubical panel after temporary connection of existng sources, since these supply are very much essential for hospital patient care services.
Straight Through jointing of cable of different size by compound jointing kit including S& F ferrul, tapes and jointing materials (Brand aprroved by EIC) [10/F-6] 4 Core 70 Sqmm Cable
3 and 1/2 / 4 Core 95 Sqmm Cable
3 and 1/2 / 4 Core 240 Sqmm Cable
3 and 1/2 / 4 Core 300 Sqmm Cable
3 and 1/2 / 4 Core 400 Sqmm Cable
Refixing of the existing distribution wiring (PVC Rigid conduit of 20/25 mm size) with supplying PVC saddles screws etc.
Supply & Fixing 2 nos 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 200x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish i) Avg. run- 8 mtr.
ii) Avg. run- 10 mtr.
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make- Legrand/ABB/Cabtree) up to 160A [ D-11 /15] i) 8 way Enclosure
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection.(Make- Legrand/ABB/L & T )[D-8/ 10] A) 250A
Supplying and fixing 240/415 V TP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand/ABB/L & T) [D-6/7] A) 40A
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make- Legrand/ABB/L & T) [ D-10 /14 ] i) 4 way Enclosure (607715)
ii) 6 way Enclosure (607716)
Supplying and fixing 240/415 V FP MCB Isolator on din rail of existing DBs and necessary connection. (Make- Legrand/ABB/L & T) [D-5/ 6] i) 40 A
Supplying and fixing 240/415 V SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand/ABB/L & T) [D-6/ 7] i) 25A
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/Havells/Polycab/RR Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required [E-14/ 1(a)] 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-5/9] i) 2.5 sq mm
ii) 4 sq mm
iii) 6 sq mm
Supply & delivery of 4ft T8 22W single LED fitting complete with 1×18W LED tube on ceiling with ceiling plate down rod etc. as required. ( Philips- Cat No. TMC 501/ Crompton- LTT8-20 & IGP131LT8/ Wipro )
Supply & delivery of 4ft 22W twin LED fitting complete with 2×22W LED tube on ceiling with ceiling plate down rod etc. as required. ( ( Philips- Cat No. TMC 501/ Crompton- LTT8-20 & IGP132LT8/ Wipro )
S & D of ceiling fans (make - Crompton Greaves-High speed/Orient summer king/ Usha Striker) of following dimensions: 48''
Supply and delivery 1200mm length 6500K LED pc body master tube lifght with external heat sink. (Make-Philips / Crompton/ Wipro )
Supply and delivery 150 Watt LED street light with IP66 protection, CCT 5700K. (Make- Philips/ Crompton/ Wipro)
Supply and delivery 100 Watt LED flood light with IP66 protection, CCT 5700K. (Make- Philips/ Crompton/ Wipro)
(Rate should be quotated including all taxes and duties and GST)
ULTRA ELECTRICALS AND ELECTRONICS
CHAKRABORTY ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid