Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical WARD 17 JAIN TEMPLE ROAD JAIN TEMPLE ROAD DIMAPUR NAGALAND 797112 | DIMAPUR | NAGALAND | 797112 | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical OLD DAILY MARKET DIMAPUR 797 112 NAGALAND | PEREN | NAGALAND | 797112 | Admitted-Fee/PreQual/Technical |
Tender Value
₹16 L
EMD Value
₹32,000
Closing Date
11 Jun 2026, 6:00 pmClosed
COL AMIT CHAUBEY
HQ 137 Wks Engr PIN 914137 c/o 99 APO
REPLACEMENT OF DG SET60 KVA DG SET WITH AMF PANEL AGAINST BER DG SET OF SAME CAPACITY AT MRS AT CHAKABAMA MIL STN
2026_MES_764388_1
8891/II/E8
Open Tender
Civil Works
Item Rate
180 days
Zakhama
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
AGE (I) Zakhama
₹32,000
6 Jun 2026
9 May 2026
18 Jun 2026
9 May 2026
11 Jun 2026
23 May 2026
Engine Specifications : Engine Rating- 60KVA B.H.P.- 72 Stroke- 4, No. of Cylinders -4 RPM- 1500 Cyl. Configuration- Inline, Direction of Rotation- Clockwise viewed from flywheel end Method of aspiration Turbocharged Inter cooled Method of cooling- Coolant cooled. Type of Governor- Electronic Starting system- 12V Electric Start Battery-12 Volt Overload capacity 10% for 1hr. for every 12hrs.running Duty Continuous Safety control: Low lube oil pressure, High coolant temp., Over speed Applicable Standards ISO 3046,BS 5514 Fuel tank capacity-140 Ltrs Bore/stroke-104x113 Dispalcement-3.84Ltr Lube oil changed Period 750 hours or 12 months. Exhaust after treatment system- DOC +SCR Applicable Standard - BS 5514/ ISO 8528 Generator Controller-GC1206 Lube oil grade/ Specification - SAE 10W 30 CK4/Gulf Leypower XLE
ALTERNATOR Specifications : Rating : 60KVA KW : 48KW Type : Brushless Excitation : Self excited, self regulated (AVR) Enclosure : SPDP Enclosure protection : IP-23 Rated Voltage : 415V No. of Phases : 3 Frequency : 50Hz Power Factor : 0.8 (lag) Rated current : 83.4Amps Class of Insulation : H Voltage Regulation : ±1% Overload capacity : 10% for 1hr. for every 12hrs. running. Applicable standards : IS 4722/BS 5000
ACCESSORIES:- The following accessories will be supplied alongwith the DG set:- (i) Suitable capacity fuel tank for running continuously 8 hrs. The fuel tank will be mounted inside the conopy with connections. (ii) Anti vibration mounting pad (mounted inside the conopy). (iii) Residential silencer (fitted on top of conopy) (iv) Exide 12 volt battery with lead (v) First filled of lube oil & coolant. MICROPROCESSOR BASED AMF CONTROL PANEL The AMF Control panel shall be made of 16SWG CRCA Sheet, indoor type, dust and vermin proof, Pre-Treated and Powder coated, suitable for 415 V, 3Phase, 50Hz system to be fitted inside Acoustic Enclosure.Panel shall consist of the following Equipment‟s:- (i) Microprocessor based AMF Controller with display features for Engine & Alternator parameters. (ii) Current Transformers of suitable ratio. (iii) MCB/HRC Fuse for Control protection. (iv) Cluster Type Indicating Lamps for DG ON/Load ON/Mains ON. (v) MCCB of Suitable Rating -1 Set with 2 Sets of Power Contactor – For Mains & DG Incomer. (vi) FRLS Type Copper Flexible cable for Switchgear Interconnections. (vii) Suitably rated Auxiliary Contactors/Relays. (viii) Earth Studs. (ix) Battery Charger (x) Electronic Voltage Regulator(EVR)
ACOUSTIC ENCLOSURE Acoustic enclosure shall be made of specially procured CRCA Sheet and structural sheet metal Base frame and comply with CPCB-IV+ norms with following features : (i) The most compact, six sided close, modular construction and detachable. (ii) Meet CPCB-IV+ / MOEF norms. (iii) Sound level < 75 dBA at one meter distance. (iv) Easy accessibility around the DG Set, which ensures optimum serviceability. (v) Special power coated enclosure, weather proof, corrosion resistant, environment friendly. (vi) Specially designed lifting hooks. (vii) Use of high quality hardware ensures longer life of enclosure. (viii) Provision for emergency stop facility. (ix) Fuel tank is specially designed and mounted inside of the enclosure as a integral part of Acoustic enclosure. Note : Apart from above cost of the following provisions shall deemed to be included in unit quoted rate:- (i) Dismantling of Old BER DG Sets alongwith its connected cables and the same shall be deposited to MES store for further disposal. (ii) Necessary civil work for foundation as per manufacturer instructions. (iii) Anything technically required for installation of DG set, if missing above, is incl in the quoted rate.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised iron strip of 32 x 6mm size by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion complete all as specified and as directed. Note: (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 50 Sqmm 3.5 core laid in trenches or fixed to wall / pole / ceiling as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc including taking down of existing unserviceable cable complete all as specified and as directed.
stage.html
html • 0.02 MB
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
BOQ_856150.xls
BOQ • 0.24 MB
8891tenderdocpdc.pdf
Tender Documents • 1.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .