Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAccepted-AOC 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | ₹19.0 L Quoted ₹21.3 L | L1 | Accepted-AOC ACCEPTED BEING LOWEST BIDDER |
| 2 | L2₹26.1 LRejected-Finance GAT NO 454 1 TAPKIR NAGAR TAPKIR NAGAR NASHIK ROAD MOSHI PUNE MAHARASHTRA 412105 UDYAM MH 26 0082541 | PUNE | MAHARASHTRA | 412105 | ₹26.1 L | L2 | Rejected-Finance REJECTED BEING NOT LOWEST BIDDER |
| 3 | L3₹26.8 LRejected-Finance | ₹26.8 L | L3 | Rejected-Finance REJECTED BEING NOT LOWEST BIDDER |
| 4 | L4₹29.9 LRejected-Finance S NO 259 LOHOGAON ROAD KALWAD PUNE 411032 | PUNE | MAHARASHTRA | 411032 | ₹29.9 L | L4 | Rejected-Finance REJECTED BEING NOT LOWEST BIDDER |
| 5 | L5₹35.5 LRejected-Finance | ₹35.5 L | L5 | Rejected-Finance REJECTED BEING NOT LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Star Electrical L5 | PURVA ELECTRICALS AND ENGINEERS L3 | Rama Electricals L4 | Adinath Technical Services L1 | ONKAR ELECTRIC AND GENERAL STORE L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00Disconnecting and dismantling the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350 MVA, 630/800 Amps from location and repair /overhauling servicing and carrying out with the following activities as mentioned below complete all as specified and directed by Engineer-in-Charge. (i) Inspecting / overhauling servicing of manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw, motor cut -off limit switch, butter fly switch assembly and apply multi grease lubricant to function smoothly. (ii) Inspecting / overhauling of tripping assembly, earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system. (iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces. (iv) Assembling all items/components parts to the respective postion & testing the breaker with High Voltage(DC) and meggering before and after high voltage test complete. (v) Cleaning all busbar by rubbing and by CRC liquid cleaner. (vi) Spraying two coat of anti track paint on CTs. (vi) Applying insulating boots for busbar and cables. (vii) Supply and fixing all missing nut bolts for panels. (viii) Replacement all rusted nut bolts. | ||||||||
| 1.01 | Make-CROMPTON 800 Amps | 5 | Each Job | 3,000 ₹15,000 | 3,500 ₹17,500 | 2,500 ₹12,500 | 3,500 ₹17,500 | 2,700 ₹13,500 |
| 1.02 | Make-Areva 800 Amps (VCB Trolly Mounted) | 6 | Each Job | 3,000 ₹18,000 | 3,500 ₹21,000 | 2,500 ₹15,000 | 3,500 ₹21,000 | 3,000 ₹18,000 |
| 1.03 | Make-ABB 630 Amps | 4 | Each Job | 3,000 ₹12,000 | 3,500 ₹14,000 | 2,500 ₹10,000 | 3,500 ₹14,000 | 3,100 ₹12,400 |
| 2.00M&L for Testing /Overhauling primary injection and secondary injection of over current earth fault relays/ numerical relays /release on each multiple setting readjustment by artificial load by artificial load through CT's as per CTR and checking performance of CT's, Ammeter, Selector Switch, Tripping control wiring and tripping of mechanism of Circuit Breaker and complete all as specified and directed including testing on completion. Note :- (i) Including fixing of spare parts to function Circuit breaker smoothly and rate to be included. (ii) Spare parts will be measured and paid separatly. | ||||||||
| 2.01 | Make-CROMPTON 800 Amps | 5 | Each Job | 2,600 ₹13,000 | 3,200 ₹16,000 | 2,500 ₹12,500 | 2,500 ₹12,500 | 3,000 ₹15,000 |
| 2.02 | Make-Areva 800 Amps | 6 | Each Job | 2,600 ₹15,600 | 2,600 ₹15,600 | 2,500 ₹15,000 | 2,500 ₹15,000 | 3,100 ₹18,600 |
| 2.03 | Make-ABB 630 Amps | 4 | Each Job | 2,600 ₹10,400 | 3,150 ₹12,600 | 2,500 ₹10,000 | 2,500 ₹10,000 | 3,200 ₹12,800 |
| 3.00Note for Item No 1 & 2 : (i) Spares required will be measured and paid seperately under relavant items in the schedule as supply only. (ii) Labour Charge deemed to be included in quotated rate. | ||||||||
| 4.00Supply only the following spare for Crompton make of 800 Amps VCB:- | ||||||||
Updated dates
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
25 Nov 2025, 6:00 pmClosed
CWE Khadki Pune
Headquarters CWE Khadki, Military Engineer Services, Range Hills Road, Khadki, Pune-411003
REPAIR AND MAINTENANCE OF 11 KV HT DISTRIBUTION NETWORK OF MH AREA INCLUDING MAINTENANCE AND SERVICING OF HT BREAKERS TRANSFORMERS VCB RMUS AND APFC PANELS AND ITS CONNECTED WORKS AT MH KHADKI UNDER GE MH AND RH KHADKI
2025_MES_737196_1
CWE/KKE/TOKEN-59 OF 2025-26
Open Tender
Electrical and Maintenance Works
180 days
CWE Khadki Pune
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE MH AND RH KHADKI
₹60,000
Yes
26 Mar 2026
28 Oct 2025
27 Nov 2025
28 Oct 2025
25 Nov 2025
11 Nov 2025
28 Oct 2025 - 4 Nov 2025
Amount
Disconnecting and dismantling the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350 MVA, 630/800 Amps from location and repair /overhauling servicing and carrying out with the following activities as mentioned below complete all as specified and directed by Engineer-in-Charge. (i) Inspecting / overhauling servicing of manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw, motor cut -off limit switch, butter fly switch assembly and apply multi grease lubricant to function smoothly. (ii) Inspecting / overhauling of tripping assembly, earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system. (iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces. (iv) Assembling all items/components parts to the respective postion & testing the breaker with High Voltage(DC) and meggering before and after high voltage test complete. (v) Cleaning all busbar by rubbing and by CRC liquid cleaner. (vi) Spraying two coat of anti track paint on CTs. (vi) Applying insulating boots for busbar and cables. (vii) Supply and fixing all missing nut bolts for panels. (viii) Replacement all rusted nut bolts.
Make-CROMPTON 800 Amps
Make-Areva 800 Amps (VCB Trolly Mounted)
Make-ABB 630 Amps
Make-CROMPTON 800 Amps
Make-Areva 800 Amps
Make-ABB 630 Amps
Note for Item No 1 & 2 : (i) Spares required will be measured and paid seperately under relavant items in the schedule as supply only. (ii) Labour Charge deemed to be included in quotated rate.
Supply only the following spare for Crompton make of 800 Amps VCB:-
Master trip relay VAJH13
Trip supervision Realay VAX31
Hooter 110 VAC
Digital Ammeter square type of size 96 mm X 96 mm
Digital Voltmeter square type of size 96 mm X 96 mm
Hooter 230 VAC
Local / Remote switch
TNC switch
TTB test terminal Block
Load Manager
AC/DC Fail unit
8 Window Announciater as per existing size
Aux Relay VAA 33 of suitable size
CG Make VCB Trip Coil of 240 Volt
CG Make VCB Closed Coil of 240 Volt
Spring Charging motor of 240 Volt
Rack-in-rack-out half gear
Rack-in-rack-out handle
CG Make VCB Aux Switch
11 KV CG Make 800 Amp Vaccume bottle
CG Make VCB spring charging handle
Manual Push to trip switch
CG Make VCB finger contact
CG Make VCB poll housing
CG Make VCB Vacuum Interrupter
CT of required size
PT of required size
CG make 11 KV 3.15 Amps PT fuse
Spring charging mechanisum
Supply only the following spare for AREVA make of 800 Amps VCB of 11 KV :-
11 kv Areva make HWX 230 Volt Spring Charging motor
Tripping coil 30 VAC
Closing coil 30 VDC
Finger contact of 400 Amps
Pole housing
A/B key lock as per exisitng
Aux switch as per exisitng
Vaccum bottle of 11 KV
TNC Switch
LR switch
6 window annuanciator
Master trip relay VAJH13
Load manager
O/C + E/F Relay as per exisiting Model No and Make
110 VAC power pack
VAA 33 Aux Relay
CT of required size
PT of required size
Ammetor Digital
Voltmeter Digital
Spring charging mechanism
Spring Charging handle
Rack-in-Rack-out handle
Supply only the following spare for ABB make of 630 Amps RMU + VCB:-
Multi function meter
Digital Voltmeter
RMU ABB safe plus operating handle
ABB Make 11 KV 3.15 Amps PT fuse
ABB Make RMU Tripping Coil
ABB Make RMU Closing coil
Spring Charging motor
O/C + E/F Relay micron P 111
ABB RMU protection relay
CT of required size
PT of required size
S& F 11 KV, SF 6, RMU Panel SF 6 Gas filling up to the indication mark complete all as specified and as directed
M&L for Servicing/Repairing of Transformer by disconnecting of LT and HT side cable carefully from Transformer and draining out transformer oil, dismantling transformer top cover and dismantling of 4 Nos LT bushing and 3 Nos of HT bushing including necessary tools and plant for removal of sediments, carbon deposits at bottom of transformer tank, on core, on winding, etc. cleaning with new transformer oil including cleaning of oil tank and attending leakage problem with oil seal and all gaskets and re-assembling complete all as specified and directed. (Note : New Transformer oil and spare parts will be measured and paid separatley under the relavant items of schedule as supply only excluding oil seal)
Transformer 11 KV/433V of capacity 100 KVA to 400 KVA
Transformer 11 KV/433V of capacity 500 KVA to 1000 KVA
M&L for on line Centrifuging (filteration) of transformer oil including checking initial and after filteration dielectric strength of oil for transformers installed at various locations in MH area under AGE E/M(West) with suitable machine having filteration, heating and pumping facility to improve the dielectric strength/insulation value of oil all as specified and directed by Engr - in- Charge. Note:- (i) Dielectric strength of oil after filteration/dehydration shall not be less than 60 KV. (ii) Oil for toping up shall be measured and paid for separately as supply only. (iii) The contractor will take shut down orders in writing before commencement of the work from Engr - in - Charge. (iv) The contractor shall ensure no wastage of transformer oil. (v) The contractor solely responsible for any damage to the transformer during filtration operations. He is responsible for making good any damage to the transfomer at his own cost without any extra cost to the department. (vi) The contractor shall ensure that the conservator tanks are full to its level before starting the dehydration. (vii) The di-electric strength of oil shall be tested before & after filtration. Test results shall be submitted to Engr-in-Charge.
Supply and filling of transformer oil, di electric strength not less than 60 KV, confirming to IS 335/1983 complete for the transformers installed at variuos locations Military Hospital and Range Hills area all as specified and directed.
Supply the material in repair or replacement of taking out core assembly of defective winding materials from HV side of the transformer and replacement with super enameled electrolytic insulated copper wire of suitable gauge to withstand the high voltage including replacement of new cork sheet, neoprene gasket etc and reinstalling the core assembly after re- winding all as specified and directed.
Supply the material in repair or replacement of taking out core assembly of defective winding materials from LV side of the transformer and replacement with super enameled electrolytic insulated copper wire of suitable gauge to withstand the high voltage including replacement of new cork sheet, neoprene gasket etc and reinstalling the core assembly after re- winding all as specified and directed.
Supply the material in repair or replacement of HT metal parts brass or copper & HT bushing Voltage Grading 11 KV suitable for indoor/outdoor type transformer of capacity 100 KVA to 1000 KVA as required at site all as specified and directed.
Supply the material in repair or replacement of LT metal parts (Brass / Copper) & LT bushing grading 50 volts suitable for out door of capacity as required at site all directed for the following capacity of transformer
100 KVA to 400 KVA
500 KVA to 1000 KVA
Supply only Breather / Silica gel
Supply only Oil temperature indicator as per existing size and capacity
Supply only Winding temperature indicator as per existing size and capacity
Supply only 4" Dia thermometer
Supply only Labour for Cleaning, checking and rewiring of the marshalling box
Supply only Oil level glass indicator
Supply only LED indication lamp of any colour 19 /22 mm dia
Supply, laying & testing XLPE insulated screened PVC bedded Aluminium HT Cables, Stranded Compacted Circular Aluminium Conductor, Screen with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up, Inner sheath of PVC, Galvanised Steel round Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 and laid in trenches / passing through pipe all as specified and directed of following sizes.
95 Sq mm 3 Core 11000 Volts
185 Sq mm 3 Core 11000 Volts
240 sq mm 3 Core 11000 Volts
Supply only Cable jointing kit for below mentioned voltage (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes
95 Sq mm to 185 Sq mm 11000 Volts
240 sq mm to 300 sq mm 11000 Volts
Supply only Cable jointing kit for below mentioned voltage (Earthed) grade cable for outdoor termination heat shrink type End joint complete with Jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes
95 Sq mm to 185 Sq mm 11000 Volts
240 sq mm to 300 sq mm 11000 Volts
Supply only Cable jointing kit for below mentioned voltage (Earthed) grade cable for indoor termination heat shrink type End joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes
95 Sq mm to 185 Sq mm 11000 Volts
240 sq mm to 300 sq mm 11000 Volts
Supply only Cable jointing kit for below mentioned voltage (Earthed) grade cable for Boot Joint termination heat shrink type End joint for RMU complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes
95 Sq mm to 185 Sq mm 11000 Volts
S&F in repairs air break gang operated HT 11 KV volt grade out door type, triple pole of capacity 200 Amps rating mounted on polymer based 9 insulator and fitted on steel frame horizotally mechanically operated mechanisum from ground level consisting of operating rod of 25 mm bore heavy grade GI pipe of suitable length worked from ground level and with locking arrangement including pad locks with key flat iron clamp 50 mm X 6 mm including taking down old unserviceable Gange operated switch as specified and directed. Make: Pactil/ Atlas /Jaipuria Brothers / MEC Trivandrum) Note : The quotated rate shall be included necessary cable removal and cable termination charges to new Gang Operated switch (if any)
Supplying, installing, fixing, connecting and testing of polymer based Drop-out fuse set (set of 3 nos), mounted on insulators with steel frame 200 Amps capacity, siutable for 11 KV, HT system, out door type, including Expulsion fuse carriers and fuse element Upto 20 Amp, including taking down old unserviceable one complete all as specified and directed..
M&L for Lightning arrester high tension expulsion type complete with all fittings transmission class, discharge capacity 30 Kilo amps suitable for 11000 Volts supply including taking down old lightning arresters all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying of cables, fixing on pole etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified as per below soil.
Soft / Loose soil
Hard / dense soil
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in soft/loose soil all as specified & directed
Removing excavated meterial to a distance n.exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified & directed by Engineer-in-Charge
M&L for riddled earth cushioning to under ground cable in trenches / existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable all as specified and directed by Engr in charge. Note : For the purpose of payment only punned thickness will be measured.
M&L for protection with PCC cable cover class HV, type-III, flat size 450x180x40 mm factory casted ISI marked all as specified and directed.
M&L for Cement concrete in foundations, filling and mass concrete of PCC 1:2:4 type B2 (using 40 mm graded crushed stone aggregate) all as specified and directed
Supplying and laying synthetic Rubber insulated blue colour mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m
S&F in repair / maintenance Space Heater for Panel HT Panel /Electronic Instruments Panel Space Heater 80 to 120 watt capacity, rust resistance and shock proof along with necessary connection all as specified and directed. Make : Airflex, Warmex, as per sample
M&L Painting of Two /four pole stracture complete by two coats of aluminium paint all as specified and directed.
Supply & spreading stone aggregates of size 40 mm in complete area of outdoor substation & 4 pole structure area all as specified and directed.
Supply only Male contact/ Moving contact blade for 11/22 KV all as specified and directed.
Supply only Female contact/ Fix contact Jaw for 11/22 KV all as specified and directed.
Supply Only Tinned Copper flexible jumper 200 A, 11/22 KV all as specified and directed.
Supply only MS jumper carrier for 11/22 KV all as specified and directed.
Supply only Back connector plate for 11/22 KV all as specified and directed.
M&L for shifting of transformer of any capacity from one area to another area within a distance of 3 km approx and placing in its position and making all connections including removing and depositing the old transformer to store yard carefully and properly testing and commissioning transformer all as specified and directed.
S&F in repair Power pack 30 V suitable for HT VCB of capacity 630A/800A,11KV, 3 ph,50 Hz Panel, all as specified and directed. Make-CROMPTON/ AREVA
M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small inequalities (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 meters away complete for the various sub station all as specified and directed.
ONKAR ELECTRIC AND GENERAL STORE (BID ID -3477419)
PURVA ELECTRICALS AND ENGINEERS (BID ID -3477188)
Rama Electricals (BID ID -3477338)
Star Electrical (BID ID -3477049)
Bidder Name
Star Electrical
Rama Electricals
PURVA ELECTRICALS AND ENGINEERS
Adinath Technical Services
ONKAR ELECTRIC AND GENERAL STORE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
TenderT59.pdf
Tender Documents • 0.91 MB
BOQ_825424.xls
BOQ • 3.53 MB
Download all tender documents and submit your bid