Loading…
Loading…
Tender Value
₹7.9 Cr
EMD Value
₹15.8 L
Closing Date
21 Sept 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
90 days
Expenditure
Capital (Works)
Above/Below/Par
ADEE G GRC
14 conditions · 2 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less ; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Form-11, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i) Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii) Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii) One similar work costing not less than the amount equal to 60% of advertised value of the tender. Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Defination of Similar Work :- Supply, installation, testing and commissioning of HT panels/LT panels, cable laying, wiring/rewiring of any building/office in Central Government or State Government or Public Sector Undertakings (also called Public Sector Enterprise).
11 conditions · 5 needing a document upload
Bidder should submit copy of GST registration certificate along with the bid. GST will levied as per instruction circulated by GOI from time to time and bidder should comply with the same.
Tenderers are required to upload their Permanent Account Number (PAN)card.
Tenderer has to submit mandatory declaration for Retired Railway employee as per Proforma/form attached in compliance to Clause 16 of IR GCC along with the tender.
Tender shall carefully go through clause 14 of GCC 2022 part I and submit the requisite document such as Power of Attorney, Board Resolution, Partnership deed etc. as applicable. The tender to be participated & signed by such persons as may be legally competent to sign them on behalf of the firm, company, association, trust or society, as the case may be.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Bidder is to submit Bid Security as per clause 5 of GCC 2022 part I along with the offers.
The security deposit shall be as per the clause 16.1 of GCC 2022 part II.
Performance Guarantee shall be as per clause 16.4 of GCC 2022 Part II.
Tender is governed by the conditioned mentioned in the NIT, General Condition of Contract 2022 with latest amendments, special conditions attached with the NIT and conditions mentioned in the other attached documents with the NIT. The order of precedence is given in the GCC 2022
Electrical work for provision of concealed wiring with accessories at different administrative buildings and Central Hospital to implement fire safety recommendation and augmentation of power supply arrangement at sub station no 6 and 8 GRC S.E Railway.
ADEE-G-Concealed-26-04-R4~SER
ADEE-G-Concealed-26-04-R4
Open
Works - General
12 Months
Unknown (Unspecified Location)
₹0
₹15.8 L
26 Aug 2026
26 Aug 2026
7 Sept 2026
379 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 7,88,70,336.24 | ||
| — | 1.00 | — | — | ||
| Installation, testing and commissioning of outdoor plinth mounted Transformer, 1000 KVA, 6.6-6kV/415V complete as per IS:1180 (Level 2)/Latest. The scope of work also covers construction of plinth by excavation of soil, preparation of foundation with concrete structure and plastering as per site condition and as advised by Rly. The plinth shall be 0.6-1.2 m height from the ground level. Width and length of the plinth shall be sufficient enough for a person to stand along the transformer for maintenance work. The plinth shall be made up of concrete having grade M 15 or higher. PVC pipe of sufficient dia to be inserted in the plinth for ease of cable entry as per site requirement. Concreate flooring (thickness 8cm minimum) to be developed at surrounding area of plinth with minimum M 15 Grade material. The foundation should be strong enough to carry the heavy load of transformer and it should be efficiently designed to prevent accumulation of water below the platform. Danger board of 60x60 cm of Stainless steel to be provided. The transformer will be supplied by the railway. All the cost of loading, unloading and transportation of transformer from railway store to installation site (at GRC colony both north and south), termination of cable using nut bolts, Bi metallic strips (if required), HT & LT termination kit if required has to be borne by the firm. For testing commissioning the requisite data shall be collected by both firm and railway for EIG approval. | — | — | — | 58,410 | |
| — | 9.00 | — | — | ||
| Supply Of HT panel consisting of 12KV, 25KA,800Amps Indoor type VCB-01nos 12KV, 25KA, with all other accessories (with power pack up, battery and charger) complete set. Including Ammeter, voltmeter, led indicator, Energy meter,CT ,PT, Protective relay e.t.c with suitable metalic enclosure and complete wiring to complete the job with 1000Amp capacity Cu. Busbar and with interlocking facilities) as per specification no SER/ELEC/GS/ DESCRIPTION / VCB/Indoor/1/2023,Rev.'0' Dec. 2023. . VCB confirms to IS 13118 (1991), IS:IEC-62271-100 / IEC62271-1 & latest, Cu Bus bar conforms to IS:613/latest & 2826/latest. Dressing of wire inside the panel for protection circuit shall be done as per code of IS 732. Before fabrication firm has to submit the requisite drawing of HT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 36,07,741.44 | |
| — | 9.00 | — | — | ||
| Installation and commissioning of HT panel consisting of 12KV, 25KA,800Amps Indoor type VCB-01nos 12KV, 25KA, with all other accessories (with power pack up, battery and charger) complete set (as mentioned at item no 2). The cost also includes for making cable ducting and RCC slab to cover the cable trenching as per site requirement. This work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & outgoing cables with necessary termination with cable glands and terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire inside the panel for protection circuit shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 1,80,380.7 | |
| — | 15.00 | — | — | ||
| Supply of HT Heat shrinkable type End Termination Outdoor type as per specification IS-13573:2011 or latest suitable for 3 x 120-185 Sq mm XLPE cable 11KV grade. | — | — | — | 55,117.8 | |
| — | 15.00 | — | — | ||
| Fixing and Commissioning of HT Heat shrinkable type End Termination (as specified at item no 4) Outdoor type as per specification IS-13573:2011 or latest suitable for 3 x 120-185 Sq mm XLPE cable 11KV . | — | — | — | 3,380.7 | |
| — | 2.00 | — | — | ||
| Supply, of LT Panel Outdoor type (IP-65) consisting with 4-pole Draw-out type ACB 1600 A, 50KA, Microprocessor Based , MDO type - 02 Nos as incomer, ACB 1600 A, 50KA, Microprocessor Based , Draw-out type - 01 Nos as bus coupler with , 4-pole 800A 50kA MCCB 02 nos & 4-pole 400A 50 kA MCCB -06nos as outgoing with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side and protective circuit & Sheet steel enclosure , appropriate spreader link for MCCB and mechanical/electrical interlocking for ACB with necessary item for seal the cable entry and outgoing point. ACB Conforms to IS/IEC 60947-2 & IEC 60947-2 and MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest, for HRC fuse as per IS: 13703-2-1 (1993) and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 30,50,318.88 | |
| — | 2.00 | — | — | ||
| Fixing and commissioning of LT Panel Outdoor type (IP-65) (as specified at item no 06). The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 1,52,515 | |
| — | 3.00 | — | — | ||
| Supply of LT panel Outdoor type (IP-65) , made of CRCA Sheet Steel, powder coated complete with TPN copper busbar with earth terminal, neutral link consisting of Incoming : 1x400A,50kA FP, MCCB, Outgoing: 10x 63A 15kA MCB (FP) (B curve) with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side for protective circuit, appropriate spreader link for MCCB.MCCB and MCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 2,72,158.74 | |
| — | 3.00 | — | — | ||
| Installation and commissioning of LT panel Outdoor type (IP-65) (as specified at item no 08). The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labors required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732 .The earthing connection work shall follow the code of practice as per IS 3043 (1987) | — | — | — | 13,607.76 | |
| — | 7.00 | — | — | ||
| Supply of LT panel Outdoor type (IP-65), made of CRCA Sheet Steel, powder coated complete with TPN copper busbar with earth terminal, neutral link consisting of Incoming : 2x400A,50kA FP MCCB, Bus cuppler - 1x400A,50kA FP MCCB, Outgoing: 16 x 125A,36kA, FP, MCCB with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side for protective circuit, appropriate spreader link for MCCB .MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 33,28,077.9 | |
| — | 7.00 | — | — | ||
| Installation and commissioning of LT panel Outdoor type (IP-65) (as specified at item no 10) . The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labors required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 1,66,397.7 | |
| — | 140.00 | — | — | ||
| Supply installation including suspension, testing and commissioning of 1600A capacity sandwich bus trunking with aluminum bus bars having minimum current density of 130A per sq cm at nominal current rating in 1.6mm thick GI enclosure, IP 55 protection in convenient section for use on 3 phase [3 phase + 100% Neutral + 100% isolated Earth+ Integral Ground Earth], 415V, 50 Hz AC supply including jointing of section, flexible joints, expansion joints, bends , suspenders, angle iron bracket, Stainless steel Fastners, connecting to earthing etc. as required to complete the work in all respect. | — | — | — | 43,19,154 | |
| — | 10.00 | — | — | ||
| Supply ,installation, testing and commissioning of 400A, Isc =50KA for 1 sec, capacity plug in/ tap off box on the existing bus trunking/rising mains for use on 3 phase [3 phase + 100% Neutral + 100% isolated Earth+ Integral Ground Earth], 415V, 50 Hz, AC supply made with 1.6 mm thick sheet steel enclosure (IP 55), duly powder coated with provision of MCCB (but without MCCB) complete as required. | — | — | — | 1,75,395.2 | |
| — | 2.00 | — | — | ||
| Supply ,installation, testing and commissioning of 1250A, Isc =50KA for 1 sec, capacity end Feed unit on the existing bus trunking/rising mains for use on 3 phase [3 phase + 100% Neutral + 100% isolated Earth+ Integral Ground Earth] 415V, 50 Hz, AC supply made with 1.6 mm thick sheet steel enclosure (IP 54), duly powder coated with provision of 1250 A ACB 50KA, Microprocessor Based , MDO type (including supply and installation) complete as required. LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 7,50,003.28 | |
| — | 50.00 | — | — | ||
| Supply of maintenance free Earthing system (Pipe in pipe technology) complete with GI steel earth pipe, back field compound as per RDSO specification no RDSO/PE/SPEC/PS/0109(Rev 0-2008 Amendment1 or latest). | — | — | — | 4,90,762 | |
| — | 50.00 | — | — | ||
| Fixing and commissioning of maintenance free Earthing system (Pipe in pipe technology) as mentioned at item no 15.Erection of Maintenance free earthing shall be done by excavation of pit either manual or by machine in any kind of soil, pit making and making of sump box with back fill compound of adequate quantity etc. and construction of RCC Cover for sump box of minimum dimension of 1.5ftx1.5ftx1.5 ft. Cost also includes connection of earth wires/strips between earth pole and main switch/DB/Street light pole/LT /HT panels etc. as per site supervisor's instruction. Cost also includes earth clamp and testing of earth resistance jointly with Railway representative. The earth value shall be printed on the earth sump box. The work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 1,72,339 | |
| — | 1000.00 | — | — | ||
| Supply of 50mmx10mm GI Flat bar strip for proper connection of earthing. | — | — | — | 3,59,900 | |
| — | 1000.00 | — | — | ||
| Laying of 50 mmx10mm GI Flat bar , clamped to brick wall, cable tray, etc., as required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welded | — | — | — | 35,400 | |
| — | 400.00 | — | — | ||
| Supply of 50mmx06mm Cu Flat strip for proper connection of earthing. | — | — | — | 8,49,600 | |
| — | 400.00 | — | — | ||
| Laying of 50 mmx06mm Cu Flat bar , clamped to brick wall, cable tray, etc., as required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding | — | — | — | 42,480 | |
| — | 1000.00 | — | — | ||
| Supply of 25mmx06 mm GI Flat bar strip for proper connection of earthing. | — | — | — | 1,47,500 | |
| — | 1000.00 | — | — | ||
| Laying of 25 mm x06 mm GI Flat bar clamped to brick wall, cable tray, etc., as required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding | — | — | — | 35,400 | |
| — | 1000.00 | — | — | ||
| Supply of 40mmx06 mm GI Flat bar strip for proper connection of earthing. | — | — | — | 1,88,800 | |
| — | 1000.00 | — | — | ||
| Laying of 40mmx06 mm GI Flat bar strip , clamped to brick wall, cable tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding | — | — | — | 47,200 | |
| — | 1000.00 | — | — | ||
| Supply of 6 sq. mm, Single Core, Multistrand (84/0.3mm), Copper Conductor (flexible), Unsheathed, , Flame Retardant Low Smoke and Halogen(FR-LSH), PVC insulated of 1100V grade, Type C PVC Compound as per IS 5831, Conforming to IS :694 - 2010 (Reaffirmed 2020) with all amendments, ISI marked. | — | — | — | 1,18,000 | |
| — | 1000.00 | — | — | ||
| Laying of 6 sq.mm multi strand FRLS insulated copper wire mentioned at item no 25 , clamped to brick wall, cable tray etc., as required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using termination socket and connector. | — | — | — | 9,440 | |
| — | 500.00 | — | — | ||
| Laying of 10 sq.mm Cable (supplied by Railway) , clamped to brick wall, tray etc., as required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using termination socket and connector. | — | — | — | 5,900 | |
| — | 500.00 | — | — | ||
| Laying of 16 sq.mm Cable (supplied by Railway) ,clamped to brick wall, tray etc., as required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using termination socket and connector. | — | — | — | 5,900 | |
| — | 400.00 | — | — | ||
| Supply of 8 SWG GI wire for proper connection of earthing. | — | — | — | 7,080 | |
| — | 400.00 | — | — | ||
| Laying of 8 SWG GI wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding. | — | — | — | 3,776 | |
| — | 400.00 | — | — | ||
| Supply of 8 SWG Cu wire for proper connection of earthing. | — | — | — | 28,320 | |
| — | 400.00 | — | — | ||
| Laying of 8 SWG Cu wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding. | — | — | — | 4,720 | |
| — | 300.00 | — | — | ||
| Supply of 12 SWG Cu wire for proper connection of earthing. | — | — | — | 26,550 | |
| — | 300.00 | — | — | ||
| Laying of 12 SWG Cu wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding. | — | — | — | 3,540 | |
| — | 200.00 | — | — | ||
| Supply of 25mmx06 mm Cu Flat strip for proper connection of earthing. | — | — | — | 1,08,560 | |
| — | 200.00 | — | — | ||
| Laying of 25mmx06 mm Cu Flat bar , clamped to brick wall, cable tray, etc., as required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding | — | — | — | 11,800 | |
| — | 50.00 | — | — | ||
| Supply of Danger notice plate of l.6mm thick Stainless steel vitreous enameled white with letters, figures and conventional skull and bones in signal red colour for HT and LT (25 x 20 cm) size. The prior approval of design and content shall be taken from railway authority before supply. | — | — | — | 29,500 | |
| — | 50.00 | — | — | ||
| Erection and fixing of Danger notice plate as mentioned at item no 37 with stainless steel clamps, bolts and nuts of approved size for HT & LT (25 x 20 cm) size as per direction of railway representative. | — | — | — | 2,950 | |
| — | 60.00 | — | — | ||
| Supply of HT Cable route Markers (stainless steel) for HT cable route marking. | — | — | — | 17,700 | |
| — | 60.00 | — | — | ||
| Erection of HT Cable route Markers as mentioned at item no 39 at every 15 mtrs interval on the cable route and also at cable routes turning points on a concrete structure/ foundation. | — | — | — | 10,620 | |
| — | 20.00 | — | — | ||
| Supply of Shock Treatment Chart with teak wood frame and glass cover [Size minimum 90 cm x 60 cm] as approved by Electrical Inspector/ railway authority. | — | — | — | 59,000 | |
| — | 20.00 | — | — | ||
| Installation of Shock Treatment Chart with teak wood frame and glass cover as mentioned at item no 41 with stainless steel clams/ screws etc as per site requirement. | — | — | — | 2,360 | |
| — | 98.00 | — | — | ||
| Supply of 8 way double door Vertical TPN DB with cable end box & Blank plates , wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3 , double door, powder coated complete with TPN copper busbar [having current capacity of 250A] with earth terminal, neutral link and suitable upto 250A MCCB incomer , Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per relevant IS standard. | — | — | — | 18,85,625.84 | |
| — | 98.00 | — | — | ||
| Installation and commissioning of 8 way double door Vertical TPN DB as mentioned at item no 43, along with installation of MCCB/MCB as per site requirement and direction of railway authority (MCCB/MCB will be provided from railway store).Its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987).DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority. | — | — | — | 2,09,424.04 | |
| — | 290.00 | — | — | ||
| Supply of 18 Way SPN DB with cable end box & Blank plates, wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard. | — | — | — | 26,31,860.2 | |
| — | 290.00 | — | — | ||
| Installation and commissioning of 18 Way SPN DB as mentioned at item no 45, along with installation of MCB,SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority. | — | — | — | 2,92,238.8 | |
| — | 10.00 | — | — | ||
| Supply of 18 Way SPN DB with cable end box & Blank plates, wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 67, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard. | — | — | — | 90,753.8 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of 18 Way SPN DB as mentioned at item no 47, along with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority. | — | — | — | 10,077.2 | |
| — | 290.00 | — | — | ||
| Supply of 16 Way SPN DB with cable end box & Blank plates, wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard. | — | — | — | 25,74,370.6 | |
| — | 290.00 | — | — | ||
| Installation and commissioning of 16 Way SPN DB as mentioned at item no 49, along with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority. | — | — | — | 2,85,737 | |
| — | 10.00 | — | — | ||
| Supply of 16 Way SPN DB with cable end box & Blank plates, wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 67, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard. | — | — | — | 88,771.4 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of 16 Way SPN DB as mentioned at item no 51, along with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority. | — | — | — | 9,853 | |
| — | 70.00 | — | — | ||
| Supply of 125A,36kA, FP MCCB, 4pole, capacity 125A, with Spreader link for each pole, rated voltage 415V, 50Hz, 3-phase AC, conforming to IS/IEC 60947-1&2, breaking capacity 30KA, insulation voltage 690V AC or higher, capable to withstand 50 degree c ambient temperature, fitted with adjustable thermal magnetic overload release and fixed magnetic short circuit release, impulse withstanding voltage capacity of 8KV or higher, having indication of ON/OFF/Tripped with locking arrangement in OFF position to avoid accidental ON position, maximum overall mechanical dimension of 140mm width. 195mm depth and 184mm height. MCCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 12,87,981.8 | |
| — | 28.00 | — | — | ||
| Supply of 250A,36kA, FP MCCB, 4pole, capacity 250A,with Spreader link for each pole rated voltage, 415V, 50Hz, 3-phase AC, conforming to IS/IEC 60947-1&2, breaking capacity 36KA, insulation voltage 690V AC or higher, capable to withstand 50 degree c ambient temperature, fitted with adjustable thermal magnetic overload release and fixed magnetic short circuit release, impulse withstanding voltage capacity of 8KV or higher, having indication of ON/OFF/Tripped with locking arrangement in OFF position to avoid accidental ON position, maximum overall mechanical dimension of 140mm width. 195mm depth and 184mm height. MCCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 10,19,184.88 | |
| — | 48.00 | — | — | ||
| Supply of 63A,10kA, FP MCB with metal (CRCA sheet minimum thickness 1.6 mm) enclosure, ISI marked, Instantaneous tripping range: B, no. of poles: 4 pole with 4PP (PP=protected pole), rated voltage 415V AC, rated current:63 Amps, conforming to IS/IEC 60898-1:2015 (Reaffirmed Year:2024) or latest, with rated short circuit current capacity 10KA, fixed Un adjustable time current characteristics and suitable for use in protection of industrial, commercial and domestic electrical installations. MCBs shall be suitable for 50 Hz AC main supplies. MCBs shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017 (Reaffirmed Year:2024) or latest. MCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 1,26,873.6 | |
| — | 48.00 | — | — | ||
| Supply of 63A,10kA, TP MCB,ISI marked, Instantaneous tripping range: B, no. of poles: 3 pole with 3PP (PP=protected pole), rated voltage 415V AC, rated current:63 Amps, conforming to IS/IEC 60898-1:2015 (Reaffirmed Year:2024) or latest, with rated short circuit current capacity 10KA, fixed Un adjustable time current characteristics and suitable for use in protection of industrial, commercial and domestic electrical installations. MCBs shall be suitable for 50 Hz AC main supplies. MCBs shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017 (Reaffirmed Year:2024) or latest. MCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 1,01,725.44 | |
| — | 600.00 | — | — | ||
| Supply of 63A,10kA, DP MCB, ISI marked, Instantaneous tripping range: B curve, no. of poles: double pole with 2 PP (PP=protected pole), rated voltage 240V AC, rated current: 63 Amps, conforming to IS/IEC: 60898-1:2015 (Reaffirmed Year:2024) or latest, with rated short circuit current capacity 10KA, fixed Un adjustable time current characteristics and suitable for use in protection of industrial, commercial and domestic electrical installations. MCBs shall be suitable for 50 Hz AC main supplies. MCBs shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017 (Reaffirmed Year:2024) or late. MCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 8,44,644 | |
| — | 1000.00 | — | — | ||
| Supply of 63A,10kA, SP MCB, ISI marked, Instantaneous tripping range: B curve, No. of poles: single pole with 1 PP (PP=Protected pole), rate voltage 240V AC, rated current: 63 Amps, conforming to IS/IEC 60898-1:2015 (Reaffirmed Year:2024) or latest, with rated short circuit current capacity 10 KA, fixed Un adjustable time current characteristics and suitable for use in protection of industrial, commercial & domestic electrical installation. MCBs shall be suitable for 50 Hz AC main supplies. MCBs shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017. MCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 6,04,160 | |
| — | 3500.00 | — | — | ||
| Supply of 10-32A,10kA, DP, Type A, 30 mA RCBO,[B or C] tripping curve, conforms to IEC61009-1, IS 12640-2, EN 61009-1/latest, and all other items as per relevant specifications and as per IS standard along with all relevant accessories, suitable for use in protection of industrial, commercial & domestic electrical installation. It shall be suitable for 50 Hz AC main supplies and shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017. RCBO shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 1,31,78,830 | |
| — | 600.00 | — | — | ||
| Supply of Type 2 AC Surge protection device (320V), DP,20kA, conforms to IEC 61643-11:2011, EN 61643-11: 2012, IEC 61643-21 latest, all other items as per relevant specifications along with all relevant accessories. It shall be suitable for 50 Hz AC main supplies and shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017. SPD shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 8,39,688 | |
| — | 50.00 | — | — | ||
| Supply of DP change over switch 63A capacity confirms to IS 60947-3, latest, all other items as per relevant specifications along with all relevant accessories. It shall be suitable for 50 Hz AC main supplies and shall have fixing arrangement for mounting on steel rails of top Hat section Rail TH:35-7.5 conforming to IS/IEC 60715:2017. Change over shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 1,40,597 | |
| — | 20.00 | — | — | ||
| Supply of 250A,50kA, FP MCCB, 4pole, capacity 250A,with Spreader link and SS enclosure for each pole rated voltage, 415V, 50Hz, 3-phase AC, conforming to IS/IEC 60947-1&2, breaking capacity 50KA, insulation voltage 690V AC or higher, capable to withstand 50 degree c ambient temperature, fitted with adjustable thermal magnetic overload release and fixed magnetic short circuit release, impulse withstanding voltage capacity of 8KV or higher, having indication of ON/OFF/Tripped with locking arrangement in OFF position to avoid accidental ON position. MCCB shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 8,28,950 | |
| — | 20.00 | — | — | ||
| Fixing and commissioning of 250A, 50kA, MCCB with SS enclosure as mentioned at item no 62. Fixing and commissioning will be done along with installation of MCCB as per site requirement and as per direction of railway authority .Enclosure will be fixed by cutting to the wall with re-finishing the wall as like original by necessary plastering, painting as per direction of railway authority and MCCB connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. | — | — | — | 82,883.2 | |
| — | 4.00 | — | — | ||
| Supply of Feeder Pillar Box Outdoor type (IP-65) comprising of: 2x250A FP MCCB 36kA as Incoming , Buscuppler-1x250A FP MCCB 36kA, Outgoing: FP MCCB 5 x 125A (36kA) with all required material , Ammeter, Voltmeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side and protective circuit , appropriate spreader link for MCCB with suitable Cu. Bus bar and all required accessories as per site requirement. MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications, as per IS Standard and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025 or latest. Before fabrication firm has to submit the requisite drawing of Feeder Pillar Box. The earthing connection work shall follow the code of practice as per IS 3043 (1987). Switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 8,99,197.76 | |
| — | 4.00 | — | — | ||
| Installation, testing and commissioning of Feeder Pillar box as mentioned at item no 64. The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required PCC foundation as per advice of Rly. authority, grouting/installation of the materials as per site requirement, along with its connection with incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing , tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 89,916 | |
| — | 3.00 | — | — | ||
| Supply of Feeder Pillar Box Outdoor type (IP-65) comprising of: 2x400A FP MCCB 50kA as Incoming , Buscuppler-1x400A FP MCCB 50kA , Outgoing: FP MCCB 4 x 250A (36kA), FP MCCB 4 x 125A (36kA) with all required material , Ammeter, Voltmeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side and protective circuit , appropriate spreader link for MCCB with suitable Cu. Bus bar and all required accessories as per site requirement. MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications, as per IS Standard and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025 or latest. Before fabrication firm has to submit the requisite drawing of Feeder Pillar Box. The earthing connection work shall follow the code of practice as per IS 3043 (1987). Switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc. | — | — | — | 12,00,718.44 | |
| — | 3.00 | — | — | ||
| Installation, testing and commissioning of Feeder Pillar box as mentioned at item no 66. The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required PCC foundation as per advice of Rly. authority, grouting/installation of the materials as per site requirement, along with its connection with incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing , tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 1,20,069.72 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 4 Core x 6 Sq mm copper conductor, armored power cable (Shall be supplied by Railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 10,030 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 3 Core x 10 Sq mm copper conductor, armored power cable (Shall be supplied by the railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 7,670 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 4 Core x 2.5 Sq mm copper conductor, armored power cable (Shall be supplied by the railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 4,425 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 3 Core x 6 Sq mm copper conductor, armored power cable (Shall be supplied by the railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 7,080 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 3 Core x 4 Sq mm copper conductor, armored power cable (shall be supplied by the railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 4,720 | |
| — | 500.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 3 Core x 2.5 Sq mm copper conductor, armored power cable (Shall be supplied by the railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 2,950 | |
| — | 700.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 1 Core x 25 Sq mm copper conductor, armored power cable (shall be supplied by railway). The cable shall be laid in indoor trenches / cable trays as required. The cable shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 24,780 | |
| — | 100.00 | — | — | ||
| Supply of PVC insulated 24 Core x 1.5 Sq mm copper conductor, armored , Multistrand, PVC sheathed, Flame Retardant Low Smoke and Halogen (FR-LSH), PVC insulated (flexible) of 1100V Grade, Type-C PVC Compound as per IS 5831, Conforming to IS 694-2010 (Reaffirmed 2020) with all amendments, ISI marked. | — | — | — | 59,000 | |
| — | 100.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 24 Core x 1.5 Sq mm copper conductor, as mentioned at item no 75. It shall be laid in indoor trenches / cable trays as required and shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 4,130 | |
| — | 100.00 | — | — | ||
| Supply of PVC insulated 19 Core x 1.5 Sq mm copper conductor, armored , Multistrand, PVC sheathed, Flame Retardant Low Smoke and Halogen (FR-LSH), PVC insulated (flexible) of 1100V Grade, Type-C PVC Compound as per IS 5831, Conforming to IS 694-2010 (Reaffirmed 2020) with all amendments, ISI marked. | — | — | — | 59,000 | |
| — | 100.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 19 Core x 1.5 Sq mm copper conductor, as mentioned at item no 77. It shall be laid in indoor trenches / cable trays as required and shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 3,540 | |
| — | 100.00 | — | — | ||
| Supply of PVC insulated 10 Core x 2.5 Sq mm copper conductor, armored , Multistrand, PVC sheathed, Flame Retardant Low Smoke and Halogen (FR-LSH), PVC insulated (flexible) of 1100V Grade, Type-C PVC Compound as per IS 5831, Conforming to IS 694-2010 (Reaffirmed 2020) with all amendments, ISI marked. | — | — | — | 45,076 | |
| — | 100.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 10 Core x 2.5 Sq mm copper conductor, as mentioned at item no 79. It shall be laid in indoor trenches / cable trays as required and shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 2,242 | |
| — | 200.00 | — | — | ||
| Supply of PVC insulated 24 Core x 2.5 Sq mm copper conductor, armored , Multistrand, PVC sheathed, Flame Retardant Low Smoke and Halogen (FR-LSH), PVC insulated (flexible) of 1100V Grade, Type-C PVC Compound as per IS 5831, Conforming to IS 694-2010 (Reaffirmed 2020) with all amendments, ISI marked. | — | — | — | 1,60,480 | |
| — | 200.00 | — | — | ||
| Laying of 1100 V grade, PVC insulated 24 Core x 2.5 Sq mm copper conductor, as mentioned at item no 81. It shall be laid in indoor trenches / cable trays as required and shall be clamped at regular intervals to the supports in trench or to cable trays or brick wall using GI/SS clamps and fasteners. Rate shall exclude the cost of cable trays, excavation. The necessary termination to be done with copper lugs, brass cable gland, tapping, crimping etc as per site requirement. | — | — | — | 8,260 | |
| — | 80.00 | — | — | ||
| Supply of 4 x400/ 300/240 sq.mm Heat Shrinkable type Cable End Termination kit for LT XLPE cable. | — | — | — | 56,923.2 | |
| — | 80.00 | — | — | ||
| Installation and termination of 4 x400/ 300/240 sq.mm. Heat Shrinkable type Cable End Termination kit for LT XLPE cable. | — | — | — | 20,484.8 | |
| — | 120.00 | — | — | ||
| Supply of 4 x 150/120 sq.mm. Heat Shrinkable type Cable End Termination kit for LT XLPE cable. | — | — | — | 44,745.6 | |
| — | 120.00 | — | — | ||
| Installation and termination of 4 x 150/120 sq.mm. Heat Shrinkable type Cable End Termination kit for LT XLPE cable. | — | — | — | 30,727.2 | |
| — | 50.00 | — | — | ||
| Supply of LV cable end termination for 4 Core x 6 Sqmm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 14,750 | |
| — | 50.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 4 Core x 6 Sqmm Copper cable. | — | — | — | 2,065 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 3 Core x 10 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 3,009 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 3 Core x 10 Sq mm Copper cable. | — | — | — | 236 | |
| — | 100.00 | — | — | ||
| Supply of LV cable end termination for 4 Core x 2.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete | — | — | — | 27,140 | |
| — | 100.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 4 Core x 2.5 Sq mm Copper cable. | — | — | — | 1,770 | |
| — | 4.00 | — | — | ||
| Supply of LV cable end termination for 3 Core x 6 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete | — | — | — | 1,085.6 | |
| — | 4.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 3 Core x 6 Sq mm Copper cable. | — | — | — | 47.2 | |
| — | 60.00 | — | — | ||
| Supply of LV cable end termination for 3 Core x 4 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 15,222 | |
| — | 60.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 3 Core x 4 Sq mm Copper cable. | — | — | — | 708 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 3 Core x 2.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 2,242 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 3 Core x 2.5 Sq mm Copper cable. | — | — | — | 118 | |
| — | 30.00 | — | — | ||
| Supply of LV cable end termination for 1 Core x 25 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 5,841 | |
| — | 30.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 1 Core x 25 Sq mm Copper cable. | — | — | — | 885 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 24 Core x 1.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete | — | — | — | 6,136 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 24 Core x 1.5 Sq mm Copper cable. | — | — | — | 885 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 24 Core x 2.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 6,136 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 24 Core x 2.5 Sq mm Copper cable. | — | — | — | 885 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 19 Core x 1.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 5,074 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 19 Core x 1.5 Sq mm Copper cable. | — | — | — | 885 | |
| — | 10.00 | — | — | ||
| Supply of LV cable end termination for 10 Core x 2.5 Sq mm Copper cable with copper lugs, brass Single compression cable glands, tapping, crimping, etc. Complete. | — | — | — | 4,484 | |
| — | 10.00 | — | — | ||
| Installation and commissioning of LV cable end termination for 10 Core x 2.5 Sq mm Copper cable. | — | — | — | 354 | |
| — | 500.00 | — | — | ||
| Supply fixing of heavy-duty GI Conduit pipe Dia meter of 25mm compliance to IS 9537 with suitable angle, circular box, bend etc. Fixing shall be concealed or recessed to the wall (as per site requirement) as per relevant IS duly re-filling and re-finishing the wall as like original by plastering and painting (for concealing). | — | — | — | 1,39,830 | |
| — | 500.00 | — | — | ||
| Supply fixing of heavy-duty GI Conduit pipe Dia meter of 40 mm compliance to IS 9537 with suitable angle, circular box, bend etc. Fixing shall be concealed or recessed to the wall (as per site requirement) as per relevant IS duly re-filling and re-finishing the wall as like original by plastering and painting (for concealing). | — | — | — | 3,32,170 | |
| — | 6500.00 | — | — | ||
| Supply and Laying of Single-Phase Point Wiring (includes Phase, Neutral and Protective Earth wire) from Modular Switch Board to equipment's (light, Ceiling fan, Exhaust Fan, calling bell etc.) ceiling rose through wall concealed PVC conduit of size 25sq mm or more. Modular Switch Board, modular switch, wiring, PVC conduit, wall cutting, wall refilling/finishing, Ceiling rose, copper lugs for termination etc. are inclusive in the point wiring. Wiring shall be done by cutting of the wall to accommodate PVC conduit, utilizing of proper bends wherever required, re-fill and re- finish the wall as like original by plastering and painting after wiring. Size of Phase, Neutral and Protective earth wire shall be 1.5sqmm, 1.5 sqmm & 2.5 sq mm respectively. Socket of 6 A, if required, shall be provided in the modular board and shall be considered as half point. The detailed specification of different component of point wiring is provided in explanatory note. | — | — | — | 44,48,600 | |
| — | 1500.00 | — | — | ||
| Supply of Modular Switch Board flush type with GI Enclosure & Cover made of tough non-ignitable insulating material with 01 no Modular Switch of 16A (IS:3854/1997) and 01 no Modular Socket 6Pin 16/6A(IS 1293-2019). The detailed specification of different component is provided in explanatory note. | — | — | — | 3,41,610 | |
| — | 1500.00 | — | — | ||
| Fixing and commissioning of switch socket board (Power) as above (Item No.-112) includes wall cutting to accommodate & flush the modular switch board GI enclosure with modular type switch and socket, all the wire connection and termination with properly crimped Lugs and connector (copper) and re-filling and re-finishing the wall as like original by plastering and painting after fixation of modular board. This work shall follow the code of IS 732 (1989).The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 17,700 | |
| — | 15000.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 2.5 sqmm) through wall concealed PVC conduit of size 25sq mm or more. Wiring shall be done by wall cutting to accommodate PVC conduit, utilizing of proper bends wherever required, re-fill and re-finish the wall as like original by plastering and painting after wiring. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. PVC conduit and 1 mtr wall cutting to accommodate the whole wiring and re-fill and re-finish the wall as like original by plastering and painting after wiring] . The detailed specification of different component is provided in explanatory note. | — | — | — | 14,33,700 | |
| — | 12000.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 4.0 sqmm) through wall concealed PVC conduit of size 25sq mm or more. Wiring shall be done by wall cutting to accommodate PVC conduit, utilizing of proper bends wherever required, re-fill and re-finish the wall as like original by plastering and painting after wiring. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. PVC conduit and 1 mtr wall cutting to accommodate the whole wiring and re-fill and re-finish the wall as like original by plastering and painting after wiring] . The detailed specification of different component is provided in explanatory note. | — | — | — | 19,96,560 | |
| — | 8000.00 | — | — | ||
| Supply and laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 6.0 sqmm) through wall concealed PVC conduit of size 25sq mm or more. Wiring shall be done by wall cutting to accommodate PVC conduit, utilizing of proper bends wherever required, re-fill and re-finish the wall as like original by plastering and painting after wiring. All the connection/termination shall be done with properly crimped Lugs and connector (copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. PVC conduit and 1 mtr wall cutting to accommodate the whole wiring and re-fill and re-finish the wall as like original by plastering and painting after wiring]. The detailed specification of different component is provided in explanatory note. | — | — | — | 14,63,200 | |
| — | 500.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 2.5 sqmm) through heavy duty rigid GI Steel Conduit Pipe as per IS: 14927 (Pt.II)/latest/IS: 9537 (Pt.III)/latest etc. Wiring shall be done fixing GI Steel Conduit Pipe , utilizing of proper bends wherever required, using stainless steel screw or saddle. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. GI Steel Conduit Pipe and fixation] . The detailed specification of different component is provided in explanatory note. | — | — | — | 2,13,580 | |
| — | 500.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 4.0sqmm) through heavy duty rigid GI Steel Conduit Pipe as per IS: 14927 (Pt.II)/latest/IS: 9537 (Pt.III)/latest etc. Wiring shall be done fixing GI Steel Conduit Pipe , utilizing of proper bends wherever required, using stainless steel screw or saddle. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. GI Steel Conduit Pipe and fixation] . The detailed specification of different component is provided in explanatory note. | — | — | — | 2,47,210 | |
| — | 1000.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral and Protective Earth wires, each 6.0sqmm) through heavy duty rigid GI Steel Conduit Pipe as per IS: 14927 (Pt.II)/latest/IS: 9537 (Pt.III)/latest etc. Wiring shall be done fixing GI Steel Conduit Pipe , utilizing of proper bends wherever required, using stainless steel screw or saddle. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. GI Steel Conduit Pipe and fixation] . The detailed specification of different component is provided in explanatory note. | — | — | — | 6,80,860 | |
| — | 1000.00 | — | — | ||
| Supply and Laying of main service/sub-service line Single Phase (includes Phase, Neutral, each 10 sq mm and Protective Earth wire 6.0sqmm) through heavy duty rigid GI Steel Conduit Pipe as per IS: 14927 (Pt.II)/latest/IS: 9537 (Pt.III)/latest etc. Wiring shall be done fixing GI Steel Conduit Pipe , utilizing of proper bends wherever required, using stainless steel screw or saddle. All the connection/termination shall be done with properly crimped Lugs and connector ( copper) as per site requirement Rate per Mtr. shall means supply and laying of 1 Mtr. phase wire, 1 Mtr. neutral wire, 1Mtr. earth wire through 1 Mtr. GI Steel Conduit Pipe and fixation] . The detailed specification of different component is provided in explanatory note | — | — | — | 8,21,280 | |
| — | 50.00 | — | — | ||
| Supply of Modular Switch Board flush type with GI Enclosure & Cover made of tough non-ignitable insulating material with 01 no Modular Switch of 16A (IS:3854/1997) and 01 no Modular Socket 6Pin 16/6A(IS 1293-2019), 1 no indicator & 1 no 16Amps SP MCB type B for Geyser. The detailed specification of different component is provided in explanatory note. | — | — | — | 26,550 | |
| — | 50.00 | — | — | ||
| Fixing and commissioning of switch socket board (Power) as above (Item No.-121) includes wall cutting to accommodate & flush the modular switch board GI enclosure with modular type switch and socket, all the wire connection and termination with properly crimped Lugs and connector (copper) and re-filling and re-finishing the wall as like original by plastering and painting after fixation of modular board. This work shall follow the code of IS 732 (1989).The earthing connection work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 4,425 | |
| — | 200.00 | — | — | ||
| Supply of Switch Board flush type with GI Enclosure & Cover mad with 20 Amps Industrial socket and plug top outlets[3 pin (Phase neutral and Earth)] confirm to IEC 60309 controlled by 1 No 20 Amps DP MCB Type B, 15 kA. | — | — | — | 8,26,000 | |
| — | 200.00 | — | — | ||
| Fixing and commissioning of Industrial socket assembly as above (Item No.-123) includes wall cutting to accommodate & flush the Industrial socket assembly with GI enclosure, all the wire connection and termination with properly crimped Lugs and connector (copper) and re- filling and re-finishing the wall as like original by plastering and painting after fixation of board. This work shall follow the code of IS 732 (1989).The earthing connection work shall follow the code of practice as per IS 3043 (1987).After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor). | — | — | — | 70,800 | |
| — | 15.00 | — | — | ||
| Supply of Switch Board flush type with GI Enclosure & Cover with 32 Amps Industrial socket and plug top outlets for 3 phase 4 wire and protective conductor system confirm to IEC 60309 controlled by 1 No 32 Amps FP MCB Type B, 15 kA. | — | — | — | 97,350 | |
| — | 15.00 | — | — | ||
| Fixing and commissioning of industrial switch socket assembly as above (Item No.- 125) includes wall cutting to accommodate & flush the industrial switch socket assembly with GI enclosure, all the wire connection and termination with properly crimped Lugs and connector (copper) and re-filling and re-finishing the wall as like original by plastering and painting after fixation of board. This work shall follow the code of IS 732 (1989).The earthing connection work shall follow the code of practice as per IS 3043 (1987).After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor). | — | — | — | 5,310 | |
| — | 10.00 | — | — | ||
| Supply of Switch Board flush type with GI Enclosure & Cover with 63 Amps Industrial socket and plug top outlets for 3 phase 4 wire and protective conductor system confirm to IEC 60309 controlled by 1 No 63 Amps FP MCB Type B, 10 kA. | — | — | — | 1,52,078.4 | |
| — | 10.00 | — | — | ||
| Fixing and commissioning of industrial switch socket assembly as above (Item No.- 127) includes wall cutting to accommodate & flush the industrial switch socket assembly with GI enclosure, all the wire connection and termination with properly crimped Lugs and connector (copper) and re-filling and re-finishing the wall as like original by plastering and painting after fixation of board. This work shall follow the code of IS 732 (1989).The earthing connection work shall follow the code of practice as per IS 3043 (1987).After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor). | — | — | — | 7,599.2 | |
| — | 50.00 | — | — | ||
| Supply of recess/surface mounting LED luminaire 36 W with BEE 5 star rating ,white powder coated ,CRCA housing with LED's seamless front frame with flat white high transmission opal glass diffuser size ( 2ft X 2ft ) suitable to operate 230V , AC supply, compliance to IS:10322/part 5/sec-2/2012 and IS 16107 (Part 2/Sec 1): 2012,Driver Efficiency >=85, luminous efficiency minimum 130 Lm/watt, , inbuilt surge protection (more than 2.5Kv) and connector ( copper) as per site requirement. with supply of all requisite materials & arrangement. | — | — | — | 84,665 | |
| — | 50.00 | — | — | ||
| Fixing and commissioning of recess/surface mounted LED luminaire 36 W as above (Item No.- 129) as standard manner using GI/SS screw (if required) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 4,189 | |
| — | 350.00 | — | — | ||
| Supply of recess/surface mounted round LED Down light of 12 W (Warm white/White), compliance to IS:10322/part 5/sec-2/2012 and IS 16107 (Part 2/Sec 1): 2012 for Recess type, aluminium die cast material and opal glass diffuser suitable to operate 230V/50Hz, AC supply Driver Efficiency >=85, luminous efficiency minimum 130 Lm/watt, , inbuilt surge protection (more than 2.5Kv) and connector ( copper) as per site requirement. with supply of all requisite materials & arrangement. | — | — | — | 1,84,198 | |
| — | 350.00 | — | — | ||
| Fixing and commissioning of recess/surface mounted round LED Down light 12 W as above (Item No.- 131) as standard manner using GI/SS screw (if required) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 9,086 | |
| — | 10.00 | — | — | ||
| Supply of 80W environment friendly & robust Medium bay /Highbay LED luminaire compliance to IS:10322 (Part-5/sec 2 ):2012. with high efficacy (100 lm/W) with toughened glass, Driver Efficiency >=85, inbuilt surge protection (more than 2.5Kv) and connector (copper) as per site requirement | — | — | — | 80,004 | |
| — | 10.00 | — | — | ||
| Fixing and commissioning of 80W environment friendly & robust Mediumbay /Highbay LED luminaire as above (Item No.- 133) as standard manner using GI/SS screw, Nut Bolt, clamp, Fastners (if required) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 4,000.2 | |
| — | 50.00 | — | — | ||
| Supply of LED Batten 18 watt (Luminous Efficacy (Im/W)±10% - 100 Im/W)(6000K Lum.) luminaries new generation energy saving and environmental friendly basic all purpose surface and wall mounted LED batten & integrated electronic driver, compliance to IS:10322 (Part-5/sec 2 ):2012, Life of LED minimum 50000 hrs , suitable to operate 230V , AC supply . | — | — | — | 8,378 | |
| — | 50.00 | — | — | ||
| Fixing and commissioning of LED Batten 18 watt as above (Item No.- 135) as standard manner using GI/SS screw (if required) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 826 | |
| — | 20.00 | — | — | ||
| Supply of 100W environment friendly LED street light made up of pressure die cast aluminum housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOP Opening separate driver compartment with IP66 protection and impact resistance of IK07,compliance to IS:10322 (Part-5/sec 2 ):2012, with high efficacy (100 lm/W) , Driver Efficiency >=85, inbuilt surge protection (more than 2.5Kv). | — | — | — | 1,45,871.6 | |
| — | 20.00 | — | — | ||
| Fixing and commissioning of100W environment friendly LED streetlight as above (Item No.- 137) as standard manner using GI/SS screw, Nut Bolt, clamp, Fastners (if required) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 7,268.8 | |
| — | 30.00 | — | — | ||
| Supply of 600 mm Silent Operation 3 Blade metal body Wall Fan, Energy efficient, with feature of Oscillation & Vertical Adjustable Tilt Mechanism, higher range Air Delivery of minimum -16000 CMPH, Rated Voltage: 230 V, 50Hz, Single phase AC, Motor Winding Material: Copper, No. of Blades-3, Provided speed control mechanism with minimum 3 speed steps with supply of all requisite materials | — | — | — | 98,978.4 | |
| — | 30.00 | — | — | ||
| Fixing and commissioning of Wall Fan as above (Item No.- 139) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase & neutral and continuous earth/ protective wire of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 4,920.6 | |
| — | 30.00 | — | — | ||
| Supply of Exhaust Fan (600mm) Energy efficient 700 RPM, Silent operation high air delivery of minimum 7100 CMPH with ISI marked, having Self closing damper compatible with exhaust fan, suitable for 230V,50Hz, AC supply, with other requisite accessories etc. | — | — | — | 1,40,644.2 | |
| — | 30.00 | — | — | ||
| Fixing and commissioning of Exhaust Fan (600mm) as above (Item No.- 141) and necessary connection to be done with 1.5 sq. mm, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective conductor of 2.5 sq. mm, Copper Conductor(flexible).The detailed specification of different component is provided in explanatory note. | — | — | — | 7,009.2 | |
| — | 200.00 | — | — | ||
| Supply of LED Board of different size made out of 3mm thick ACP Sheet to lit the name in three languages (Hindi , English , local ) with toughened glass 3-dimensional letter made of Acrylic of depth minimum 01 inch, letter size as per site requirement and direction of consignee with LED having IP 66 protection along with power supply having driver efficiency >85%, luminous efficiency minimum 130 Lm/watt inbuilt surge protection more than 2.5kv with all associated materials. For design and content , prior approval to be taken from railway authority before supply of materials. | — | — | — | 2,98,304 | |
| — | 200.00 | — | — | ||
| Fixing and commissioning of LED Board as mentioned at item no 143, along with fixed GI/SS structure as standard manner using GI/SS screw, Nut Bolt, clamp, Fastners (if required) and necessary connection to be done with 1.5 sq. mm and above as per site requirement, Copper Conductor (flexible), as phase and neutral and continuous earth/ protective wire of 2.5 sq. mm and above as per site requirement, Copper Conductor(flexible) through PVC flexible Conduit Pipe of Nominal Size 25 mm (with suitable clamping arrangement as per site requirement) and all the wire connection and termination should be done with properly crimped Lugs and sleeves. | — | — | — | 29,736 | |
| — | 20.00 | — | — | ||
| Making of RCC cable trench and cover with RCC slab (M 15 Grade material), inclusive supply of all required materials related to the civil work .Internal size of the trench is 1 feet width and 1 feet 6 inch depth with sand filling. The prior approval for design location wise shall be taken by the firm before execution. | — | — | — | 88,665.2 | |
| — | 6000.00 | — | — | ||
| Removal of un-serviceable and damaged cables on ground, walls of buildings, at substation, panels room, pump house and other location with taking proper safety and without disturbing the power supply as per direction of railway authority. Released cable to be handed over to SSE/P/GRC store. | — | — | — | 2,30,580 | |
| — | 200.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width 1000 mm, Height 50 mm, Tray thick ness 2.0 mm,) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 1080mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot- dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 5,06,550.4 | |
| — | 200.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width 1000 mm, Height 50 mm, Tray thick ness 2.0 mm,) as mentioned at item no 147 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 50,654 | |
| — | 500.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension ( (width 600 mm, Height 50 mm, Tray thick ness 2.0 mm) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 680mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot- dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 8,05,704 | |
| — | 500.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width 600 mm, Height 50 mm, Tray thick ness 2.0 mm) as mentioned at item no 149 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 80,570 | |
| — | 500.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension ( width450 mm, Height 50 mm, Tray thick ness 2.0 mm) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 530mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot-dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 6,33,420 | |
| — | 500.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width450 mm, Height 50 mm, Tray thick ness 2.0 mm) as mentioned at item no 151 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 63,340 | |
| — | 1500.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension ( width 150 mm, Height 50 mm, Tray thick ness 2.0 mm,) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 230mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot- dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 7,26,405 | |
| — | 1500.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width150 mm, Height 50 mm, Tray thick ness 2.0 mm) as mentioned at item no 153 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc | — | — | — | 72,640.8 | |
| — | 1000.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension ( width200 mm, Height 50 mm, Tray thick ness 2.0 mm,) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 280mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot-dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 6,91,000 | |
| — | 1000.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width200 mm, Height 50 mm, Tray thick ness 2.0 mm) as mentioned at item no 155 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 69,100 | |
| — | 1000.00 | — | — | ||
| Supply of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width300 mm, Height 50 mm, Tray thick ness 2.0 mm,) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 380 mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less . Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot-dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 9,20,400 | |
| — | 1000.00 | — | — | ||
| Fixing commissioning of GI Hot Dip Perforated Type Cable Tray wall mountable of dimension (width300 mm, Height 50 mm, Tray thick ness 2.0 mm) as mentioned at item no 157 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 92,040 | |
| — | 300.00 | — | — | ||
| Supply of GI Hot Dip ladder type cable tray wall mountable of dimension (width 200 mm, Height 75 mm, Tray thick ness 2.0 mm) along with two nos. Coupler Plate and minimum 08 set of nut-bolts & washers for coupling. The tray is to be supplied along with all the required accessories for wall mounting such as Support brackets, Nut-Bolts, Washers, Fasteners & Clamps etc. Width of support bracket shall be minimum 280 mm so that tray can be mounted at a distance 50mm from wall. The quantity of Support bracket and associated accessories should be suitable for supporting & mounting of Cable-tray at a distance of 2 Meter or less. Support brackets, Coupler Plates, Nut-Bolts & Washers, Fasteners & Clamps etc. shall be of either Stainless Steel (SS) or Hot-dip Galvanized Iron (GI). Galvanizing Hot dip shall be as per IS 2629/4759 for cable tray and associated accessories. | — | — | — | 1,87,195.2 | |
| — | 300.00 | — | — | ||
| Fixing commissioning of GI Hot Dip ladder type Cable Tray wall mountable of dimension (width 200 mm, Height 75 mm, Tray thick ness 2.0 mm) as mentioned at item no 159 , Fixation will be done as per direction of railway authorized representative, cost of the fixation includes all the materials cost as per standard for fixation of cable tray hanging from roof/ceiling and wall structure using necessary standard Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) support, Stainless Steel (SS) or Hot-dip Galvanized Iron (GI) nut bolts etc. | — | — | — | 18,717 | |
| — | 4000.00 | — | — | ||
| Laying of cable (cable will be supplied by Rly.) in air/wall/wooden structure /cable tray with supply & fixing of suitable GI/SS clamp/saddle/fixtures/covers/encasing etc. (minimum clamping/saddle interval 30cm) including termination, connection with the electrical equipment/installations by suitable gland/socket/lugs/ Bimetallic lugs etc., testing and commissioning of cables as per site requirement inclusive of supply of all requisite materials required for the same. The location/place and actual length of laying depends upon the specific site requirement and as advised by Railway. | — | — | — | 1,98,240 | |
| — | 2000.00 | — | — | ||
| Laying of cable underground: Excavation and Digging of cable trench in any kind of soil along the Road/Path, across the Road/Path if feasible, as per exact field requirement, generally as per CEE/GRC's drawing No.CEE/G/A3/P-134 (MOD.-1), however width and depth of the trench shall be as per critical field requirement and as advised by Railway for all kinds of soil. The cost also includes Brick boxing and laying of cable (cable will be supplied by Rly.) in cable trench along the Road/Path, across the Road/Path if feasible, as per field requirement as per IS 1255(1983), refilling of the trench by sand and soil with re-dressing of the Road/Path way etc. as like original, providing cable route marker embossing SSE/EL/P/GRC with date of laying at suitable intervals and termination of cable to the switchgears, pillar box, DB etc by suitable gland/socket/lugs/ Bimetallic lugs etc. as per site requirements. The contractor shall supply good quality bricks & sand. | — | — | — | 2,83,200 | |
| — | 500.00 | — | — | ||
| Laying of cable underground: Micro drilling using directional drilling method (using machinery) and laying of cable (cable will be supplied by railway) in underground as per exact field requirement with supply of all requisite materials and arrangement of all equipment, labours with contractor's own cost. | — | — | — | 4,63,150 | |
| — | 50.00 | — | — | ||
| Supply of class RCC Hume pipe of 300 mm Dia for embedding in wall / floor / below ground level as per relevant IS standard. | — | — | — | 35,400 | |
| — | 50.00 | — | — | ||
| Laying of RCC Hume pipe of 300 mm Dia embedded in wall / floor / below ground level. The rate shall include excavation, laying of pipe, refilling, consolidating, making the chase in the brick wall, embedding the pipes and redoing the surface. | — | — | — | 5,900 | |
| — | 3.00 | — | — | ||
| Supply installation testing and commissioning of EARLY STREAMER LIGHTNING PROTECTION SYSTEM confirms to NFC 17-102 standard(2011) and IEC 62305, Design- Non-Electronic / Electronic Early Streamer Emission(ESE) with no external power source, Material -Stainless steel - suitable for any environmental conditions, minimum radius of protection 107 mtr at level IV, lightning test current- 200KA & Short circuit current-1kA, Stainless steel mounting mast (minimum dia 60mm) with base plate, height- as per standard and requirement, Down conductor -Pure copper having size minimum 70 sqmm, length as per standard and requirement, having features of lightning strike count (Electronically controlled, register every strike between 1000A to 200kA for a 8/20 micro second peak current. Tested in a High Voltage Laboratory (at CPRI Bangalore), Chemical Earth pit as per standard. with Copper Bonded Grounding Rod minimum 20mm dia 3 mtr long. M20 grade RCC foundation block having minimum size of 450mmx450mm shall be used for mounting mast and for guy wire support. All the nut bolt, clamp, base plate, Fastners, guy wire etc shall be made of Stainless Steel. | — | — | — | 11,62,111.2 | |
| — | 60.00 | — | — | ||
| Supply of Earth cone including sump box and chemical compound etc as per CEEGRC's Drawing no :CEE/G/A3/P-150,Alt.1 and CEE/G/A3/P-134 (MOD.-1) with supply of all requisite items. | — | — | — | 91,402.8 | |
| — | 60.00 | — | — | ||
| Fixing and commissioning of Earth cone including sump box as above (Item No.- 167) with supply of all requisite items. The Cost includes excavation of pit either manual or by machine in any kind of soil, pit making and making of sump box with salt, charcoal etc. and construction of RCC Cover for sump box of minimum dimension of 1.5ftx1.5ftx1.5 ft. Cost also includes connection of 8 SWG GI. wires/ GI strips between earth cone and main switch/DB/Street light pole/LT /HT panels etc. as per site supervisor's instruction. Cost also includes earth clamp of size 50 X 6 mm GI testing of earth resistance jointly with Railway representative and the earth value shall be printed on the earth sump box. The work shall follow the code of practice as per IS 3043 (1987). | — | — | — | 26,266.8 | |
| — | 1.00 | — | — | ||
| Preparation of Electrical Designs and Drawings (SLD, earthing layout, Lighting protection layout etc.) along with inclusion of details of cable sizes, cable route, DB locations, panel locations, specification of different electrical components in the estimate such as Panels, UPS, DG, Riser bus duct etc. as per the relevant IS, NBC and fire safety guidelines for central hospital GRC and NAB to modify & upgrade the electrical power supply system. | — | — | — | 1,18,000 | |
| — | 100.00 | — | — | ||
| Supply of G.I Pipe of size of 80mm dia medium duty (class -B) ,conforming to Is : 1239,Part-1 (2004). | — | — | — | 99,002 | |
| — | 2.00 | — | — | ||
| Supply of ARC FLASH SAFETY KIT (Large size) with head protection, Eye protection, Gloves, Full body Arc flash clothing, Safety shoes etc as per standard for voltage rating-33 KV , confirms to NFPA 70E (Standard for Electrical Safety in the Workplace) and IEC 61482 (Protective clothing against the thermal hazards of an electric arc), hazard risk category (HRC) 4. | — | — | — | 1,52,692 | |
| — | 8.00 | — | — | ||
| Supply of Heavy Duty Combinational Ratchet Socket Wrench Spanner Chrome Vanadium Hand Tool Kit Set (with minimum 14 no Square Drive Socket Set) with box. | — | — | — | 38,722.88 | |
| — | 10.00 | — | — | ||
| Supply of Adjustable Spanner with specification of:- Height: 10 centimeter, Length: 25.5-millimeter, Size: 10 inch, Width: 3 centimeter, Weight: 70 gram, Hardness (Hrc): 40,Type: Adjustable with kit box. | — | — | — | 2,997.2 | |
| — | 5.00 | — | — | ||
| Supply of 4½ Digit / 20,000 Count Digital Multimeter for AC & DC voltage current, resistance with Holster, Live Wire Check, Infrared Remote-Control Check, Capacitance, Frequency, hFE Test, Diode Test, Audible Continuity, Data Hold and APO functions with all accessories. | — | — | — | 18,219.2 | |
| — | 5.00 | — | — | ||
| Supply of 3¾ Digit / 6000 Count 2000A DC /2000A AC TRMS Auto ranging Clamp meter with 60 Segment Bar graph with Frequency, Capacitance, Duty Cycle, RPM, MIN-MAX, RELD, Diode Test, Audible Continuity, Data Hold and APO functions with all accessories. | — | — | — | 41,246.9 | |
| — | 3.00 | — | — | ||
| Supply of 500V - 200M Ohm Digital Insulation Tester with all accessories. | — | — | — | 5,356.02 | |
| — | 3.00 | — | — | ||
| Supply of 1000V - 200M ohm Digital Insulation Tester with all accessories. | — | — | — | 5,356.02 | |
| — | 2.00 | — | — | ||
| Supply of Clamp - On Earth / Ground Resistance and Leakage Current Tester (Non Contact Type) with Range : 0.010V - 1000V, 0.5mA - 30.00mA AC, Data Storage Memory, Data Hold, Auto ranging, Auto Power Off functions, Jaw Opening : up to Earthing Strip of 65 x 32 mm" with all accessories. | — | — | — | 93,942.16 | |
| — | 5.00 | — | — | ||
| Supply of Digital LUX Meter : 0 - 2,00,000 lux / 0 - 20,000 fc, MAX / MIN, Backlight, Auto Power Off with all accessories. | — | — | — | 13,239.6 | |
| — | 3.00 | — | — | ||
| Supply of Handheld Thermal Imaging Camera : -20 C to 300 C / -4 F to 572 F, Resolution : 60 x 60, Pixels : 3600, Memory : 32GB Micro SD Card with all accessories. | — | — | — | 1,63,912.62 | |
| — | 2.00 | — | — | ||
| Supply of Laser Distance Meter : 0.05 - 100m, Units : Meter / Inches / Feet, Functions : Addition, Subtraction, Area, Volume, Pythagorean, Data Storage. | — | — | — | 15,283.36 | |
| — | 2.00 | — | — | ||
| Supply, Unloading, Installation, testing & commissioning of 40 KVA/ 36 kW UPS with three phase input & three phase true sine wave output and sealed maintenance free batteries for minimum 30 minutes backup complete with all accessories such as suitably rated TPN MCB /MCCB isolators on both I/P and O/P sides, 150mm Height Base frame for UPS Mounting, open type powder coated racks for Battery, Battery Circuit Breaker with Under Voltage coil, Battery cables(DC) with Min 20 Mtrs Length, termination of cables etc., complete as required with SNMP Battery (output PF is 0 9)" | — | — | — | 14,39,600 | |
| — | 50.00 | — | — | ||
| Supply of Multi-Functional Emergency Rechargeable LED Lantern(5 W) with LED head light having 3 Lighting Modes and Dimmability Brightness Control Method , equipped with minimum Lithium-Ion 2200 mAH Battery. | — | — | — | 62,422 | |
| — | 1.00 | — | — | ||
| Supply, Unloading , Installation, testing & commissioning of Hybrid panels consisting of 800KVAR Apfc and 600A AHF assembly with all requisite materials Such as Circuit breaker, Control circuit protection, Controller, Active power filter Auto manual selector, Capacitor Bank, Connecting wires, 2.0 mm CRCA sheet enclosure with copper Bus Bar & forced cooling (Fans), complete in all respect. Before supply of the material, prior approval from the railway side is required for the design, drawing, make & model etc. | — | — | — | 40,59,200 | |
| — | 5.00 | — | — | ||
| Supply, Unloading , Installation, testing & commissioning of 10 KVA rating Online UPS with Minimum Battery Backup of 120 minutes, Conforming to IEC 62040-1:2017 or latest. UPS shall be with inbuilt Isolation Transformer, Pluggable UPS type A, Rack mountable, with IGBT-PWM type, suitable for both linear and non-linear loads, with IP 65 or higher Degree of Protection, Insulation Class F materials, temperature rise limited to 110 Degree C, Temperature limits for transformer winding with Designation-F, suitable for input supply of AC Single phase (160 V-260 V) 50 Hz/ ambient temperature up to 50 degree C/ relative humidity up to 95%, Output voltage will be 230 V ± 1% 50 Hz.. Overall Efficiency (%) of UPS without Battery will be 95%. All features of Protection, Earthing, Alarms, Indications, Name plate, Markings, other provisions shall comply IS/IEC mentioned above. External Battery set of SMF-VRLA type conforming to JISC: 8702 (Pt. I, II & III) with flammability class HB or better. UPS shall be supplied with Rack for UPS mounting (Annex GG of IEC) with Cabinet for mounting of External battery bank, external battery bank, Flexible cord and connectors etc. | — | — | — | 12,39,949.9 | |
| — | 3.00 | — | — | ||
| Supply of electrical LOOP IMPEDANCE TESTER 3 ½ digit LCD (2000-count), Backlight function, loop measurement current shall be within the limit of leakage current of RCBO, Convenient and easier for users to measure the loop impedance directly without bypassing the wires, Wiring check function, Built-in voltmeter. Built-in earth tester, Built-in loop/psc tester, Safety standard : EN 61010-1 CAT III 300V EN 61326-1 complete set. | — | — | — | 71,996.52 | |
| — | 2.00 | — | — | ||
| Supply and Commissioning of MCB test kit complete set having features of Mains Isolated AC Injection Currents , easily portable for " ON- Site", Compatible for NO/ NC auxiliary trip contact ,4 digit auto ranging Time interval meter,2 in one test kit to test miniature circuit breaker and relays up to 63A as well as molded case circuit breaker upto 500 Amps, Mode selector switch for MCB or MCCB test. | — | — | — | 98,999.64 | |
| — | 20.00 | — | — | ||
| Supply of 11 kv grade hand gloves set with chalk powder including weatherproof transparent box with lock and key. | — | — | — | 35,400 | |
| — | 60.00 | — | — | ||
| Supplying & Installation Insulating Mat for Electrical purpose of Width 1 Meter., thickness 2.5 mm ±10%, Class B type, Mechanical Properties of Mats suitable for ambient temperature of -10 to 55 degree C, Category III (Mats resistant to acids, alkali and oil and low temperature), Minimum Die-electric Strength of 45 KV ac (rms), should Conform to IS 15652: 2006 with Amendment No. 1 & 2 or latest and ISI marked. The Insulating Mat shall be packed in rolls as per clause 10 of IS. Insulating Mat should be got type tested from NABL accredited laboratory. Type Test certificate, Routine Test Certificate shall be attached with the supply. | — | — | — | 99,544.8 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Mandatoryaccesoriesforwiring.pdf
ATTACHMENT
GCCUpdateduptoACS-7.pdf
ATTACHMENT
SpecialtermsandConditions_1.pdf
ATTACHMENT
Generalexplanatorynoteofthetender.pdf
ATTACHMENT
SpecificationofHTpanel.pdf
ATTACHMENT
cabletraydimensionnew.pdf
ATTACHMENT
TenderForms.pdf
ATTACHMENT
GCC2022ACS8to11-compressed1.pdf
ATTACHMENT
RevisedDescriptionfor3PhaseLTDistributionPanelRevision2.pdf LT panel specification
ATTACHMENT
CEEGA3P-150Alt.1.pdf
ATTACHMENT
CEEGA3P-134Mod.1.pdf
ATTACHMENT
RevisedDescriptionfor3PhaseLTDistributionPanelRevision2.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].