Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | I₹1.2 LAccepted-Finance 58 KAILASHPURAM GOVINDPURAM GAZIABAD | GHAZIABAD | UTTAR PRADESH | I | Accepted-Finance ACCEPT | |
| 2 | III₹1.2 LRejected-Finance | III | Rejected-Finance REJECT | |
| 3 | II₹2.0 LRejected-Finance GMD ROAD MORADABAD MORADABAD UTTAR PRADESH 244001 | MORADABAD | UTTAR PRADESH | 244001 | II | Rejected-Finance REJECT |
Tender Value
Refer Docs
EMD Value
₹1,500
Closing Date
17 Aug 2021, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE
132 KV S/S Bharua Sumerpur
WORK OF MAJOR OVERHAULING AND REPAIRING OF 33 KV VACUUM CIRCUIT BREAKERS AT 132 KV SUBSTATION PANWARI AND PATARA, HAMIRPUR UNDER ETD HAMIRPUR
2021_UPTCL_610306_1
TS-40/ETD(H)/2021-22
Open Tender
Electrical Works
Lump-sum
30 days
132 KV S/S Bharua Sumerpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹177
Yes
Executive Engineer
₹1,500
Yes
21 Aug 2021
11 Aug 2021
18 Aug 2021
11 Aug 2021
17 Aug 2021
11 Aug 2021
90 days
Amount
Details of Work.
Major overhauling and repairing of following 33 KV VCB type circuit breaker at 132 KV S/S Panwari :-
(A) 33 KV VCB CGL Make of Jamala feeder (Mfg Year - 2013) (B) 33 KV VCB CGL Make of Bharwara feeder (Mfg Year - 2013) (C) 33 KV VCB CGL Make of Panwari feeder (Mfg Year - 2013) (D) 33 KV VCB CGL Make of Mahobkanth feeder (Mfg Year - 2013) (E) 33 KV VCB CGL Make of 20 MVA T/F-I (Mfg Year - 2013) (F) 33 KV VCB CGL Make of 20 MVA T/F-II (Mfg Year - 2013) By doing following works in each circuit breaker :- (i) Cleaning of porcelain of drive insulator and porcelain of vacuum interrupter from inside and outside of each pole. (ii) Checking & adjustement of snatch gap, travel of drive insulator rod & tie rod of each pole. (iii) Opening, repairing of mechanism by welding, drilling, machning and filling of material as per requirement and proper fitting of it in breaker cubicle. (iv) Oiling & greasing of crank gears by opening of lock circlip etc. (v) Replacement of worn out parts such as bush, rings, lock pins and latch etc. (vi) Checking & adjustment of oil daspot of breaker for its damping action. 2. After major overhauling and repairing of above VCB, following tests are to be carried out :- (i) Opening & closing time of breaker of each pole. (ii) Carrying out Contact Resistance Measurement (CRM test) of each pole. (iii) Checking of megger values of breaker poles. (iv) Checking triping of breaker at 70% DC voltage. (v) Checking the CLOSE/OPEN operation of breaker from REMOTE & LOCAL. (vi) Prepare and submit the site ovehauling report of each breaker.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
P S Enterprises
M/S SATKAR TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .