| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.4 LAdmitted-Finance | ₹38.4 L | L1 | Admitted-Finance |
| 2 | L2₹38.5 L+₹10,000 (0.26%)Admitted-Finance | ₹38.5 L+₹10,000 (0.26%) | L2 | Admitted-Finance |
| 3 | L3₹38.5 L+₹10,730 (0.28%)Admitted-Finance | ₹38.5 L+₹10,730 (0.28%) | L3 | Admitted-Finance |
| 4 | L4₹45.9 L+₹7.5 L (19.6%)Admitted-Finance GAYATRI HOUSE OPP GOYAL INTERCITY ROW HOUSE DRIVE IN ROAD THALTEJ AHMEDABAD GUJARAT 380054 | AHMADABAD | GUJARAT | 380054 | ₹45.9 L+₹7.5 L (19.6%) | L4 | Admitted-Finance |
| 5 | L5₹53.3 L+₹14.9 L (38.8%)Admitted-Finance | ₹53.3 L+₹14.9 L (38.8%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Avon Electricals L3 | DUBEY ELECTRIC WORKS L2 | Budhiraja Enterprises L1 | MEC ENGINEERS L5 | GAYATRI PRIVATE LIMITED L4 |
|---|---|---|---|---|---|---|---|---|
| 1.00Supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 5 Nos. VCBs totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IEC 62271-100/ IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, motorised/ manually charged and auto/ manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 350 MVA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 630 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 6 NO + 6 NC and equipped with following switchgears and accessories including connections suitable for 3x400/300/240 sqmm size XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc. as required.(Note:- Cost of end termination not included in this item). Note:- The panel shall be fabricated only at the OEM's factory/works as per description of item and approved design of the manufacturer. VCB shall be floor mounted. Cassette type VCB shall not be accepted. | ||||||||
| 1.01630A VCB as Main Incomer ---- 1 No. (a) 1 No. - 11KV/110Volts PT Class 0.5 accuracy and 100VA burden with digital Voltmeter (0-15 KV), selector switch for voltmeter and protection MCB for HT metering up to 12 KV on incomer. (b) 1 No. - (0-300A) digital Ammeter, selector switch for ammeter (c) 1 No. - Microprocessor based numerical relay with O/L, E/F and S/C protection. (d) 1 No. - Set of dual core dual ratio 3CTs 300/150/5/5 A of 15VA burden and accuracy Class-0.5 for metering and class 5P10 for protection. (e) 1 No. - Master Trip Relay (f) 1 No. - Digital Multifunction Meter with RS485 communication port. (g) 1 No. - Trip circuit supervision relay. (h) 1 No. - 6 window annunciator with hooter. (i) 1 No. - Under voltage relay (j) 1 No. - Over voltage relay. | ||||||||
| 1.02630 A VCB as Outgoing ---- 2 Nos. (a) 2 Nos. - (0-100A) digital Ammeter, selector switch for Ammeter. (b) 2 Nos. - Microprocessor based numerical relays with O/L, E/F & S/C protection. (c) 2 Nos. - Set of dual core dual ratio 3CTs 100/50/5/5A of 15VA burden and accuracy Class- 0.5 for metering and class 5P10 for protection. (d) 2 Nos. - Master Trip Relay (e) 2 Nos. - Digital Multifunction Meter with RS485 communication port. (f) 2 Nos. – Auxiliary relay for transformer protection, alarm, trip, and winding. (g) 2 Nos. - Trip circuit supervision relay. (h) 2 Nos. - 6 window annunciator with hooter. | ||||||||
| 1.03630A VCB as Incomer / Outgoing ---- 2 Nos. (a) 2 Nos. - 11KV/110Volts PT Class 0.5 accuracy and 100VA burden with digital Voltmeter (0-15 KV), selector switch for voltmeter and protection MCB for HT metering up to 12 KV on incomer. (b) 2 Nos. - (0-300A) digital Ammeter, selector switch for ammeter (c) 2 Nos. - Microprocessor based numerical relay with O/L, E/F and S/C protection. (d) 2 Nos. - Set of dual core dual ratio 3CTs 300/150/5/5 A of 15VA burden and accuracy Class-0.5 for metering and class 5P10 for protection. (e) 2 Nos. - Master Trip Relay (f) 2 Nos. - Digital Multifunction Meter with RS485 communication port. (g) 2 Nos. - Trip circuit supervision relay. (h) 2 Nos. - 6 window annunciator with hooter. (i) 2 Nos. - Under voltage relay (j) 2 Nos. - Over voltage relay. | ||||||||
| 1.04 | Inbuilt Power Pack converter unit ---- 5 Nos.
Inbuilt Power Pack converter unit with 220 Volt AC input and 24 Volts DC continuous output suitable for closing / tripping / indication of HT Panel board with 2 Nos. 12 Volts 7 AH SMF batteries, charging unit as per manufacture design. | 2 | Set | 18,78,560 ₹37,57,120 | 18,56,000 ₹37,12,000 Lowest | 18,87,000 ₹37,74,000 | 26,00,000 ₹52,00,000 | 22,55,500 ₹45,11,000 |
| 2.00 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required.
2.1 ---- 400 sqmm | 12 | Each | 6,467.5 ₹77,610 | 8,000 ₹96,000 | 4,500 ₹54,000 Lowest | 8,000 ₹96,000 | 4,500 ₹54,000 Lowest |
| 3.00 | Dismantling of existing 11KV Ring Main Unit panel / OCB type HT 4 panel board including repairing of flooring, disconnection of existing 4 Nos. HT incoming and outgoing cables of size 3 X 150/400sqmm in each panel, shifting and handing over of the same from Synergy and Nilgiri Sub-Stations to Main Sub-Station (approx. 0.5 KM and 1.5 KM distance) in safe condition etc. complete as required. | 2 | Job | 7,000 ₹14,000 | 20,000 ₹40,000 | 5,000 ₹10,000 Lowest | 15,000 ₹30,000 | 12,500 ₹25,000 |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
12 Nov 2020, 3:00 pmClosed
Executive Engineer (Electrical)
Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
Replacement of 11KV OCB type HT Panel and Ring Main Unit Panel with 11KV VCB type HT Panel boards in Nilgiri and Synergy Sub-Stations at IIT Delhi.
2020_IIT_592220_1
IITD/WORKS(SP-3204)/2020
Open Tender
Miscellaneous Works
Works
120 days
IIT Delhi, Hauz Khas New Delhi
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹1.1 L
18 Dec 2020
21 Oct 2020
13 Nov 2020
21 Oct 2020
12 Nov 2020
21 Oct 2020
Amount
Supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 5 Nos. VCBs totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IEC 62271-100/ IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, motorised/ manually charged and auto/ manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 350 MVA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 630 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 6 NO + 6 NC and equipped with following switchgears and accessories including connections suitable for 3x400/300/240 sqmm size XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc. as required.(Note:- Cost of end termination not included in this item). Note:- The panel shall be fabricated only at the OEM's factory/works as per description of item and approved design of the manufacturer. VCB shall be floor mounted. Cassette type VCB shall not be accepted.
Inbuilt Power Pack converter unit ---- 5 Nos. Inbuilt Power Pack converter unit with 220 Volt AC input and 24 Volts DC continuous output suitable for closing / tripping / indication of HT Panel board with 2 Nos. 12 Volts 7 AH SMF batteries, charging unit as per manufacture design.
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required. 2.1 ---- 400 sqmm
Dismantling of existing 11KV Ring Main Unit panel / OCB type HT 4 panel board including repairing of flooring, disconnection of existing 4 Nos. HT incoming and outgoing cables of size 3 X 150/400sqmm in each panel, shifting and handing over of the same from Synergy and Nilgiri Sub-Stations to Main Sub-Station (approx. 0.5 KM and 1.5 KM distance) in safe condition etc. complete as required.
DUBEY ELECTRIC WORKS
Avon Electricals
GAYATRI PRIVATE LIMITED
MEC ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .