Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹3.7 LAccepted-Finance | L-1 | Accepted-Finance 1st Lowest Bidder | |
| 2 | L-2₹3.7 L+₹1,150 (0.31%)Rejected-Finance | L-2 | Rejected-Finance 2nd Lowest Bidder | |
| 3 | L-3₹3.7 L+₹2,020 (0.55%)Rejected-Finance 92 M DHARAMPUR DHARAMPUR SHAHPUR VILLAGE TOWN SHAHPUR CITY GORAKHPUR GORAKHPUR UTTAR PRADESH 273006 INDIA | GORAKHPUR | UTTAR PRADESH | 273006 | L-3 | Rejected-Finance 3rd Lowest Bidder | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-Firm has not submit Latest Balance Sheet , Labour License and "A" Class Electrical Contractor License. |
Tender Value
₹3.7 L
EMD Value
₹4,500
Closing Date
14 Jul 2025, 5:00 pmClosed
Superintending Engineer
Electricity Transmission Circle, UPPTCL, Pareshan Bhawan, Mohaddipur , Gorakhpur
WORK OF OVERHAULING OF 145 KV SF-6 CIRCUIT BREAKER, GENERAL MAINTENANCE AND SERVICING OF 36 KV VCB AND REPAIRING OF BATTERY CHARGER AT 132 KV S/S KASIA, RAJAPAKAR AND LAXMIPUR UNDER ETD-I, GORAKHPUR
2025_UPTCL_1048187_1
E-Tender No. 11-ETC(G)/2025-26
Open Tender
Electrical Works
Item Rate
60 days
Gorakhpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC, Gorakhpur
₹4,500
23 Jul 2025
12 Jun 2025
15 Jul 2025
12 Jun 2025
14 Jul 2025
12 Jun 2025
Amount
PART-A (WORK)
Servicing , Repairing and Rectification of Fault of 110V / 200AH Battery Charger JVV Make including replacement of all defective parts as supplied above with associated works like complete dedusting of charger by using vacum cleaner , checking charging and discharging current and its limit , cleaning of all cards with Klinit / Standard cleaning agent etc with all other associates work to complete the job satisfactory at 132 KV S/s Kasia & Rajapakar . (service code-S0083/400999)
Work of configuration , testing , commissioning of Siemens make numerical type O/C , O/C & E/F relay towards HV side after retrofiting in existing T/F C&R Panel by use of special means and testing kit , extraction of D.R and relay data . The job also includes dismantling of existing old & obsolete electromagnetic IDMT O/C and E/F relay of 40 MVA T/F-I , providing new ferrule as per numerical relay drawing , reconnection of cables as per drawing , performing satisfactory operation from local , remote and protection relay with all other associated works to complete the job satisfactory . (service code-401551/S0049)
Major Overhauling of mechanism assembly of 145 KV SF-6 C.B spring type installed at different feeders and T/F bays at various substation under ETD-I , Gorakhpur . The work includes overhauling of control block assembly , opening latch , closing latch , support latch , anti-pumping assembly . Opening , cleaning and greasing of motor charging system , replacement of worn out parts like roller-D valve seat , O-ring P-80 , O-ring P-7 and other damaged ring not specified here . Checking of shock absorber , closing damper , etc . Adjustement of all gaps , cleaning and greasing of levers , connecting rods , cam , disc cam etc . Checking of mechanism assembly for wear and tear , rectification / repairing of worn out parts . Checking of limit switch , power contactors , auxiliary contractors for proper fuctioning . Checking and retightening of all electrical connections . Checking and attending the gas leakage of circuit breakers . Measurement of closing / tripping time of circuit breakers . Measurement of contact resistance of circuit breakers with digital meter . Work shall include submission of analysis of closing / tripping time & contact resistance measured for each CB along with any further necessary recomendation for healthy future life of CBs. (service code-401042/S0083)
132 KV S/s Kasia , Kushinagar .
132 KV NISM Bay , (ABB Make) MFY-2006 , Sr. No. 1702028
General maintenance & servicing of operating mechanism , spring charging mechanism of 33 KV V.C.Bs at below mentioned 132 KV S/s including travel measurement of moving rod , checking of 33 KV V.C.B cobtact continuity , dismatling of tie rod assembly , cleaning & greasing of its all roller pins and its re-assembly , cleaning of all moving parts and their greasing , checking and rectification of problem in electrical circuits including Aux. contact block , checking of auto opreation of spring charging motor , setting of limit switches , meaurement of contact resistance of all the pole susing contact resistance meter , Measurements of closing and tripping time of all the poles with the help of digital time measurement equipment , checking healthiness of the vacumm interrupter unit by using vacuum interrupter tester and finally checking of operation of the vacuum circuit breakers via remote / local as well protection mode with all other associated work to complete the job satisfactory (Each breakers test report shall be provided by firm to engineer incharge) .
132 KV S/s Kasia , Kushinagar .
132 KV S/s Rajapakar , Kushinagar .
132 KV S/s Laxmipur .
PART-B (SUPPLY)
Supply of Float controller card (TPEC-1) suitable for 110V / 200AH Battery charger JVV Make . (4100000202)
Supply of Boost controller card (TPEC-2) suitable for 110V / 200AH Battery charger JVV Make . (4100000202)
Supply of Flat Rectifire Thyristor - Diode Module 45A/1200V , Ratanshah/Naina/Hirect/IR/Semikrone Make . ( 4000000274)
Supply of Boost Rectifire Thyristor - Diode Module 70A/1200V , Ratanshah/Naina/Hirect/IR/Semikrone Make . ( 4000000273)
Float Free wheeling & blocking diode , diode-diode module (D4-BDI) , 56A/1200V , Ratanshah /Naina/Hirect/IR/Semikrone make . (4000000222)
Boost Free wheeling & blocking diode , diode-diode module (D4-BDI) , 70A/1200V , Ratanshah /Naina/Hirect/IR/Semikrone make . (4000000221)
Supply of HRC Fuse HQ type size A3 , 50A suitable for above charger . (4100000212)
Supply of 22 Pin Card connector. (4000002467)
Supply of Float Filter capacitor FC-1 , 10000mfd/250V DC Alcon/Sarda/CTR make . (4000000215)
Supply of Boost Filter capacitor FC-2 , 10000mfd/250V DC Alcon/Sarda/CTR make . (4000000216)
110 VDC Trip coil suitable for 132 KV circuit breakers ABB Make (Mfg Year-2006) for fitting in overhauling work.
110 VDC Close coil suitable for 132 KV circuit breakers ABB Make (Mfg Year-2006) for fitting in overhauling work.
Sampada Trading Company (BID ID -5321381)
M/S V P ASSOCIATES WORKS PRIVATE LIMITED (BID ID -5327588)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .