Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance GRAM AEMANPUR DISTRICT BULANDSHAHR UTTAR PRADESH | BULANDSHAHR | BULANDSHAHR | UTTAR PRADESH | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹5,500
Closing Date
2 May 2023, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Talkatora Power House, Lucknow
04/E.U.D.C.-III/2023-24
2023_MVVNL_799093_1
04/E.U.D.C.-III/2023-24
Open Tender
Electrical Works
Fixed-rate
365 days
E.U.D.D- Uptron
As per Tender document
2 documents required · 2 mandatory
₹1,180
E.U.T.D.-VIII
₹5,500
16 May 2023
27 Apr 2023
3 May 2023
27 Apr 2023
2 May 2023
27 Apr 2023
Amount
Safe carriage, loading and unloading of following material from ESC Daliganj, Lucknow to work site/J.E. dump store.
PCC Pole 8.5/9 Mtr. long.
S.T.P. Pole 9/11 Mtr. long.
25 K.V.A. Transformer.
63 K.V.A. Transformer.
100 K.V.A. Transformer.
ACSR RABBIT/DOG/RACOON/WEASEL Conductor.
11 K.V. XLPE Cable (3X70/120/185 Sq.mm.)
ABC (3X120/95/70/25/16 Sq.mm.)
11 K.V. pilfer resistant metering cubical.
11 K.V. Pole mounted C.T./P.T.
D.P. Box 3 phase.
11 K.V. 3X70 Sq.mm. XLPE Cable Out door Jointing Kit.
11 K.V. 3X70 Sq.mm. XLPE Cable Indoor Jointing Kit.
Fabrication, Erection of Sub-Station type Double Pole on 8.5 mtr. long S.T.P/P.C.C. pole with necessary clamps, accessories required including fixing of Top Channel 125X65X6 mm. (2240 mm long) one No., Dropper Channel 100X50 mm. (2028 mm long) 01 Nos. with arrangment of fixing of 06 Nos. Pin Insulator. Sub-Station base angle of 65X65X6 mm. (2250 mm.) channel 02 Nos. Grouting with cement, sand and brick ballast in ratio 1:4:8 making plinth upto width of 300 mm. Painting of poles with primer and enamel paint as per RESPO specification complete in all respect.
Dragging of S.T./P.C.C. Pole to pit site, digging of pit erection and grouting (as per RESPO norms) of 11 K.V. 9/11/8.5 mtr. Long S.T./P.C.C. pole with fixing of necessary items, such as V-type X-arm, F-Bracket, 11 K.V. Pin/Disc insulator, guarding angle (1.8 mm. 65X65X6 mm.) with nuts & bolts its ramming as per RESPO specification. Only pole & insulator shall be supplied by the department.
Ordinary earthing by M.S. earth rod 2500 mm. long as per RESPO specification. (Only G.I. wire and earth rod shall be supplied by the depatment.)
Grouting and nozzeling of Stay set complete of size 16X1800 mm. with cement, sand, brick-ballast 1:3:6 as per RESPO specification. (Only stay wire shall be provided by department)
Laying and sagging of 3 phase 3 wire 11 K.V. line on ACSR Weasel/Rabbit/Racoon/Dog conductor as per RESPO specification and direction of E/I.
Laying of 11 K.V. XLPE cable size 3X70/120/185 Sq.mm. in single circuit as per ISS norms including all the required material.
Earthing of 11/0.4 KV Distribution Transformer's body & neutral by way of boring and lowering of ISI marked two nos. G.I pipe 1.5" dia 20 m deep from the ground level with solid cone at the lower end of G.I pipe. One end of G.I strip of size 50X6 mm. will be connected with neutral / body of the Transformer & other end will be clamped & welded with G.I Pipe as per UPPCL norms (All the material will be arranged by contractor at their own cost.)
Earthing of 11 K.V. Pilfer resistance Metering body/neutral by way of boring and lowering of ISI marked two Nos. G.I pipe 1.5" dia 20 m deep from the ground level with solid cone at the lower end of G.I pipe. One end of G.I strip of size 50X6 mm. will be connected with neutral and body of the Bus Coupler & other end will be clamped & welded with G.I Pipe as per UPPCL norms (All the material will be arranged by contractor at their own cost.)
Installation of 11 K.V. Pilfer resistance Metering Unit with safe emergisation.
Mounting of double meetering unit on double pole, only double metering unit shall be supplied by department.
AB Conductor Stringing & sagging of 3 phase with necessary clamps, Eye hook, Suspension clamp, A-B type connector etc. on ABC New line as per RESPO specification and direction on E/I. ABC shall be supplied by department.
Fixing of 3 phase distribution box/Kiosk on the L.T. Poles including all clamps and material required for mounting connection and sealing.
Hosting of 11 K.V. XLPE cable will be passed through M.S. Pipe of required size duly clamped with pole at the bottom, middle and top of the pole.
Safe installation 25 K.V.A. Transformer on double pole by providing and fixing of all accessories along with making H.T./L.T. connections and its commissioning.
Safe installation 63 K.V.A. Transformer on double pole by providing and fixing of all accessories along with making H.T./L.T. connections and its commissioning.
Safe installation 100 K.V.A. Transformer on double pole by providing and fixing of all accessories along with making H.T./L.T. connections and its commissioning.
Note :- 1- All the material provided by contractor shall be as per norms of UPPCL/RESPO. 2- One carriage including loading/unloading from dump site to pit site is included in scope of work. 3- During execution of work all risk will be of the contractor. 4- Contractor will provide all T & P, vehicle and man power. 5- All the old and used material should be taken on book. 6- The quantity may be vary ±10%. 7- GST will be paid extra as legally applicable.
SYED TRADERS
OREON PROJECTS
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .