| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.2 LAccepted-AOC 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L1 | Accepted-AOC L1 bidder rate quoted liable | |
| 2 | L2₹21.5 L+₹23,002 (1.08%)Rejected-Finance 26 740 35 KESARI HOUSE NEAR RICO INDUSTRIAL AREA DEVIPURA SIKAR RAJASTHAN 332 001 | SIKAR | SIKAR | RAJASTHAN | 332001 | L2 | Rejected-Finance BIDDER QUOTED RATE IS HIGH | |
| 3 | L3₹25.4 L+₹4.2 L (19.8%)Rejected-Finance 1A BASEMENT 30 31 RAJA HOUSE NEHERU PLACE NEW DELHI | NEW DELHI | NEW DELHI | DELHI | L3 | Rejected-Finance BIDDER QUOTED RATE IS HIGER |
Tender Value
₹20.1 L
EMD Value
₹40,300
Closing Date
18 Apr 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF JAISALMER
HQ CWE AF Jaisalmer
REVERTING OF BACK FEED CONFIGURATION IN POWER RING MAFI PROJECT AND ALLIED WORKS AT AIR FORCE STATION JAISALMER
2022_MES_568852_4
80217E8
Open Tender
Civil Works
Item Rate
180 days
GE AF JAISALMER
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF JAISALMER
₹40,300
Yes
24 Apr 2023
23 Mar 2023
20 Apr 2023
23 Mar 2023
18 Apr 2023
5 Apr 2023
Amount
Supply, install, commission and test Stepup Transformer 250 KVA capacity, copper wound, outdoor type. 433/11000 Volts (at no load), 3 phase AC, 50 HZ as per IS-2026, ONAN, oil cooled, oil immersed with oil tank and filled with ISI marked insulating oil (IS-335) up to the top level in oil tank with oil level indicator, Breather assembly with silica gel, lifting hook, drain valve, air vent valve , wheel with channel and locking arrangement to put on the plinth with external cooling tubes, core type, delta star connected in accordance with vector symbol DYN-11(vector group-4) with neutral brought on (LV) side & having tapppings in 7 steps in equal steps of 2.5%, (Plus/Minus 7.5 % on plus and minus side to vary the secondary voltage primary side by means of hand operated off load tap changing gear, so as to change/correct HV voltage on secondary side including provision of all necessary standard fittings including all jointing materials, connecting with electrical system, earthing, testing and commissioning all as conforming to Level -1, IS 1180 (Pt-I)/2014 and mainly comprising of :- (a) One cable end box on HV side having cable glands suitable for 95 sqmm 3 core XLPE 11 KV HT cable (consisting of 3 Nos porcelain H.T bushings with brass/gun metal bushing rods complete with nuts and washers). (b) One cable box on secondary (LV) side consisting of 4 Nos porclain bushings with GM bushing rods complete with GM nuts, and washers and suitable size extended copper bus bar strip for connecting of 400sqmm 3.5 core cable with two No cable gland suitable for reception of 1 run of INCOMING LT PVC sheathed armoured cables of size 400 sqmm 3.5 core. (c) Oil conservator with filter type, drain valve and oil level gauge. (d) Dehydrating breather assembly with first fill of denydrating agent. (e) Explosive vents. (f) Thermometer pocket on tank cover.
(g) One temperatoure indicator 150mm dia with alarm and trip contact, and one winding temperature indicator with alarm and trip contact with marshalling box and connector in and including providing of suitable core control cable, armoured to connect Marshalling box to RMU/VCB complete and testing on completion (h) Rating plate owith terminal markings. (i) Two earthing terminals on tank /tank cover to facilitate fixing of 32x 6m GI earth strip. (j) Oil level guage. (k) Oil drain and filter valves. (l) Oil filter hole with cap /plug wityh connections complete. (m) Lifting lugs. (n) Air relief valve plug. (o) Four plan solid cast steel detachable rollers. (p) First fill of fresh oil conforming to relvant IS and testing upto 40 KV dielectric strength. (q) Extra bushing for neutral outside the LT cable box for providing independent earthing for neutral. (r) Buchholz relay with alarm and trip contact and shut off valves and connecting to marshalling box or RMU/VCB for making Buchholz functional complete. (s) Provision of 2 Nos of danger boards 250x200 mm size made out of 1.6 mm thick M>S> plate , vitreous enameled white, with letters, figures of voltage and conventional skull and bones in signal red colour, one at HT side and other on LT side. (t) Any other fittings/accessories so as to conforming to Level -1, IS 1180 (Pt-I)/2014. (u) PCC plateform of size 2.5m x 2.5m x 1.25m and rolled mild steel channel MC100 as directed by Engineer-in-Charge for mounting of transformer
Note :- 1. The transformer will have its initial oil filling to appropriate level. Cost of oil including testing with desired dielectric strength shall be deemed to be included in the unit rate qouted by the bidder/tenderer. 2. Unit rate qouted by the bidder/tenderer shall be deemed tobe included for PCC plateform of size 2.5m x 2.5m x 1.25m constructed with cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate and surface finished even and smooth finish using extra cement including 02 Nos of of MS channel of size MC100.
Supply, install, commission and test 11 KV Outdoor Type Extensible Ring Main Unit (RMU) floor mounted with and including internal copper bus bars consisting of combinations of 630 Amp Load Break Switches (LBS) manual type-03 Nos as outgoings and Vacuum Circuit Breaker (VCB) manual spring charging-01 No as incommer. All live parts, bus bars, LBSs, VCBs connections of RMU should be enclosed in Stainless Steel tank & sealed for life robotically welded non magnetic and non ferrite 304 grade stainless steel tank of 3 +/-0.5mm thick having IP67 degree of protection filled with SF 6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. RMU shall have solid earthing system. The earthing busbar shall be provided throughout the length of switchgear & shall be provided in each cable compartment. RMU should complete with all accessories such as Terminal boots, VPIS, cable supports, mechanical indications for Load break switch ON/OFF, VCB ON/OFF, Spring charge, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 1000m as per IEC 60120. Internal arc type tested for AFLR 20kA for 1 sec with gas release provision from top side. Bushings bolted type mounted outside the tank for connection of external bus bar. The complete enclousere of RMU shall be of IP 54 Protection class. The outer door of enclouser shall cover entire front part of the switchgear including cable compartment in and including the following :-
The configuration of the RMU will be 01 No VCB as incomer and 03 Nos LBS as outgoing. Each Vacuum Circuit Breaker module should consist of following accessories :- (a) 630A Vacuum Circuit Breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (b) Short time current - 21KA/ 3 sec. (c) Making Capacity - 50KA. (d) Power frequency withstand voltage - 28KV. (e) Impulse withstand voltage - 75KV. (f) Nominal operating gas pressure - 1.4 Bar abs. (g) Front cover mechanism - IP2X. (h) Cable covers - 3X with outer enclouser IP54. (i) Stored energy mechanical for manual operation. (j) Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable. (k) Right angle boots (push on type). (l) Arc proof cable covers with self Interlocking mechanism with earth switch. (m) Capacitive voltage indication fixed type system as per IEC61243. (n) Mechanical Indications for Load break switch ON, OFF, EARTH. (o) Self Powered Over Current and Earth Fault protection relay. (p) Ring core current transformer with suitable ratio 100/5-5, 2.5VA, 10P10 for protection
(q ) Make of Vacuum Interrptor and RMU Manufacturer should be the same. (r) 630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 95kV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation and pad-lockable Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Note - RMU shall be placed on PCC plateform of size and design recommended by manufacturer and the cost of the same shall be deemed to be included in unit quoted rates.
Design, supply, erection, install, commission and test; LT Feeder Pillar box, Factory Made, Dust, Weather and Vermin proof, indoor type, double door, suitable for 3 phase 4 wire, 415 Volts AC supply and having 4 Nos Copper bus bar not less 630 Amps for distribution system and type tested at CPRI, fabricated in factory having modern fabrication and testing facility which includes seven (07) tanks pre treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032.The feeder pillar box shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The feeder pillar box shall be made out of 3.15mm thick CRCA (cold rolled close annealed) mild steel sheet and 3.15mm thick gland plate duly compartmentalized for each control gear and bus-bar, front door (02 layer) and rear Door (01 layer) opening facility and mild steel channel (75 MC) base frame at bottom and having welded equal angle of 75mmx75mmx6mm of length 0.9m, 04 nos, 30cm of angle shall be embedded in PCC (1:2:4) using 20mm graded crushed stone agregate below GL level and 30cm shall be above ground level of size as directed by Engineer-in-Charge at site. The feeder pillar box shall be provided with ventilation facility in the form of louvers for better heat dissipation. Necessary cable gland shall be provided for all incoming and outgoing cables. The Feeder Pillar Box shall be comprising of the followings and all as shown in drawings :-
CONTROL WIRING : All control wirings shall have to be carried out with 1100 Volts rated FRLSH grade PVC insulated multi-stranded type copper wire of cross sectional area 1.5 Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. INCOMING : MCCB 400 Amps, 4 poles, thermal megnetic releases, 415 Volts. 50KA. 50 Hz with cable terminal links-01 No. OUTGOING (a) Bakelite fuse holder with 5 Amps HRC type control fuse - 03 Nos. (b) LED Pilot Lamp suitable for 230 Volts AC supply with integral circuit and cluster LED of following colours : (i) RED - 01 No, (ii) YELLOW - 01 No, (iii) BLUE - 01 No. (c) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 Nos(d) Digital Ammeter 96mm x 96mm suitable to read 0 to 400 Amps, accuracy class 1% - 01 Nos (e) Current transformer (CT) of rating 400/5, tape wound, rated burden 5 VA - 03 Nos (f) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1set of 03 Nos (Red - 01, Yellow- 01, Blue - 01)(h) 02 Nos.Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber.(Note : 1. TheLT Feeder Pillar Box shall be designed in such a way that adequate workable space is made available inside the compartments and the front area of the panel shall not be less than 1 sqm and 500mm depth). 2. The contractor shall submit the design and drawings for LT Feeder Pillar Box poanel to the Garrison Engineer for approval before procurement of material.
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground, (Earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5m below normal ground level ,connected to and including galvanised iron earth strip 32 X 6mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in Electrical Plate No. 3 of MES SSR 1991 Part-I. (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, 40 mm thick PCC 1:2:4 type B-1 as in Pre-cast RCC cover with suitable handle, reinforced with welded steel wire fabric weighing not less than1.87 Kg/Sqm. (c) Funnel with watering pipe of GI 20mm nominal bore light grade and lugs etc complete all as specified and directed (d) 50mm nominal bore medium grade GI protection pipe and GI earth strip upto 7.5m length shall be deemed tobe included in unit rate qouted bythe bidder. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Excavating in trenches in hard soil., n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, for pipes and electric cables etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as speified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. Returning, filling including spreading, leveling watering & well ramming in layers not exc. 25 cm for soft/loose soil.
Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete.
M&L for providing dry tibba sand in trenches as sand cushioning to underground cable including punning down of sand in layer all as speciied. (Note :- 18 cm punned thickness shall only be reckoned for the purpose of measurement and paymentmeasured and paid).
M& L for 40 to 50 mm thick rough dressed Jodhpur type stone slab 25 to 35 cm in width of 80 cm long laid dry abutting each other for protection to under ground cable complete including taking up of old protection material all as specified and directed.
Supply, lay, joint, test and commission XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured overall PVC sheatehed electric power cable heavy duty with aluminium conductor of size 3.5 core 400 sqmm crosssectional area, 1100 Volts grade (LT), laid in trenches, fixed on wals,roofs and poles, laid in ducts and floors etc complete all as specified and directed. Note : Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid for separately under respective items of BoQ
Supply, lay, joint, test and commission XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured overall PVC sheatehed electric power cable heavy duty with aluminium conductor of size 3 core 95 sqmm crosssectional area, 11000 Volts grade Earthed (11 KV earthed system), laid in trenches, fixed on wals,roofs and poles, laid in ducts and floors etc complete all as specified and directed. Note : Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid for separately under respective items of BoQ
Supply, lay and fix 80 mm bore galvanised iron light grade pipe with fittings (ISI Marked) as protection pipe for electric cables, laid in trenches, fixed on poles, walls and ceilings or laid in floors, laid in road crossing /hard standing/pole protection fixed with clamps as per site requirement etc complete all as specified and as directed.
S&F Cable jointing kit, heat shrinkable, end termination joint, outdoor type with jointing materials and accessories suitable for HT XLPE cable of size 95 Sqmm 3 core aluminium conductor, armoured 11000 Volts grade heavy duty complete all as speicified and directed by Engineer-in-Charge.
S&F Cable jointing kit, heat shrinkable, end termination joint, indoor type with jointing materials and accessories suitable for HT XLPE cable of size 95 Sqmm 3 core aluminium conductor, armoured 11000 Volts grade heavy duty complete all as speicified and directed by Engineer-in-Charge.
S&F Cable jointing kit Heat shrinkable straight through joint suitable for HT XLPE cable of size 95 Sqmm to 120 sqmm, 3 core armoured 11000 Volts grade heavy duty complete all as speicified and directed by Engineer-in-Charge
S&F 32x6mm GI strip earth continuity conductor or main earthing lead fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit pipe /pipe or fixedto poles or ant other indicated situation for loop earthing etc, complete all as specified and directed at site
HUMERS INFRATECH
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .