Loading…
Loading…
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
8 Oct 2026, 3:00 pmDue tomorrow
EE(E)/ELD-5/DDA
CENTRAL NURSERY SECTOR 5 DWARKA NEW DELHI
Running, maintenance..................housing in Sector 14 Pkt 5 Dwarka
2026_DDA_928663_1
24/EE/ELD-5/DDA/2026-27
Open Tender
Electrical Works
Works
365 days
EE(E)/ELD-5/DDA
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹2.2 L
05.10.2026
1 Oct 2026
1 Oct 2026
9 Oct 2026
1 Oct 2026
8 Oct 2026
1 Oct 2026
5 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Running and Operation of D.G. sets, Fire Fighting Pump sets, Fire Alarm Systems,Ventilation & Pressurisation system,submersible pump sets, AMF Panels & allied accessories as per inventory, terms and conditions attached. | 12 | Month | 3,54,931 | ₹42,59,172 |
| 2 | Providing Rescue operator for OMEGA Make lifts installed as per invertory, terms and conditions attached. | 12 | Month | 4,61,423 | ₹55,37,076 |
| 3 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. a)100 A,30KA,FPMCCB | 2 | Each | 8,127 | ₹16,254 |
| 3.1 | a) 250 A,36KA,FPMCCB | 1 | Each | 18,372 | ₹18,372 |
| 3.2 | b)400 A,50KA,FPMCCB | 2 | Each | 44,663 | ₹89,326 |
| 4 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range-5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mmFRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C)
a)18-22 Watt | 600 | Each | 681 | ₹4,08,600 |
| 5 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
a) 1X1.5 sq. mm | 1,000 | Mtr. | 51 | ₹51,000 |
| 5.1 | b)2X4 sq. mm | 400 | Mtr. | 160 | ₹64,000 |
| 6 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
a)Single Pole | 10 | Each | 285 | ₹2,850 |
| 6.1 | b)Double Pole | 10 | Each | 696 | ₹6,960 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.49 MB
BOQ_975923.xls
BOQ • 0.35 MB
NIT24.pdf
Tender Documents • 6.15 MB
MINUTESOFPREBIDMEETING.pdf
PDF • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .