| 1 | 1₹86.1 LAccepted-AOC 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | 1 | Accepted-AOC Being lowest | |
| 2 | 2₹90.9 L+₹4.8 L (5.54%)Rejected-Finance A 04 ADGNJ CHANDAN NAGAR OPP IOCL PETROL PUMP RAMPUR ROAD BAREILLY U P 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | 2 | Rejected-Finance Not being lowest | |
| 3 | 3₹93.8 L+₹7.8 L (9.00%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | 3 | Rejected-Finance Not being lowest | |
| 4 | 4₹99.9 L+₹13.8 L (16.1%)Rejected-Finance 67 KAILASH VIHAR TIWARIPUR BAGIA JAJMAU KANPUR 208010 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208010 | 4 | Rejected-Finance Not being lowest | |
| 5 | Rejected-Technical CB 288 RING ROAD NARAINA NEW DELHI 110028 | NEW DELHI | DELHI | 110028 | - | Rejected-Technical Not Recommended being two class below |
Tender Value
₹87.8 L
EMD Value
₹1.8 L
Closing Date
22 Feb 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE Agra
112 Taj Road Agra Cantt
PROVN OF 33 KV HT AUTOMATIC VOLTAGE REGULATOR (AVS) AT 33/11 KV MES NRS AT FATEHGARH
2022_MES_502162_1
86098/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Fatehgarh
MES contractors enlisted in Class C category b(ii) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹1,000
AGE (I) Fatehgarh
₹1.8 L
Yes
26 Mar 2022
18 Jan 2022
28 Feb 2022
18 Jan 2022
22 Feb 2022
8 Feb 2022
18 Jan 2022 - 25 Jan 2022
60 days
Amount
Supply, Installation, testing and commissioning of copper wound HT, AVR suitable for outdoor installation of capacity 5000 KVA, suitable for HV input voltage range of 27 KV to 37 KV, HV output voltage 33 KV (+-) 1% with all standard fittings such as silica gel breather, temperature gauge, Bucholz relay, WTI & OTI trip & alarm controls and indoor control units with all control cables of appropriate rating including by pass connections with all control cables & control units with following technical specifications of HT AVR.( Make: ANDREW YULE/ ICON ENGINEERS/ ELECOM TRANSFORMERS/ ABB/ AREVA.) (a) Construction feature:- oil immersed, Naturally cooled on load, stepless, rolling contact brentford type, automatic voltage controller. (b) Mode of operation :- (i) Manual (ii) Motorised (iii) Automatic (c) Service - Outdoor (d) Output- Stablized at 33000 V (+-) 1%, 3 Phase, 50 Hz, suitable for balanced/unbalanced load. (e) Equipment consists of (i) Step down / Step up unit (ii) Regulator Unit (iii) Buck/Boost unit (iv) Automatic control unit (v) 'E' Reversing 'Q' panel as per requirement (f) Terminals (i) Input - Bare Bushing (ii) Output - Bare Bushing. (g) Temperature rise - 50 ºC rise of top oil over an ambient of 50 ºC (h) Tank and oil- All the units shall be housed inside the sheet steel tank. The number of tanks will depend on design parameter. Items shall be supplied with first filling of oil, confirming to IS 335 (Note : Any items leftout but which is required for proper functional point of view is deemed to be included in the quoted rate )
FITTINGS AND ACCESSORIES (a) Accessories for its successful operation including the following major items as per the requirement. (i) Rating Plate, Roller, Plain oil level gauge and conservator (ii) Drain valve, filter valve, sampling valve with plug & earthing terminals. (iii) Inspection cover, Thermometer pocket & lifting lugs (iv) Silicagel Breather & Buchholz relay with shut off valve (v) Pressed steel radiators with shut off valve (vi) PRV or Expulsion vent, OTI & WTI with Alarm trip contacts (vii) Suitable 33 KV/110V PTs on 33 KV input and output side of AVR to measure 33 KV voltage and relay sensing and 36 KV -01 Set (Set of three) (viii) Remote metering panel & Marshalling Box. (ix) Sensing Relay. (x) Step syn Geared Motor. (xi) Voltmeter for 3 Phase input & output voltage measurement with rotary switch.
Supply, installation, testing and commissioning of out door type 33 KV Porecelain clad VCB 1250 Amp (with required structure) complete all as specified and directed with following technical specifications:- (i) No. of poles- 3 Nos. (ii) Nominal system voltage- 33 KV (iii) Highest system voltage- 36 KV (iv) Rated normal current for bus bar of circuit breaker- 1250A (v) Rated normal current for interrupter- 2000A (vi) Rated short circuit breaker current (rms)- 25KA (vii) Rated short circuit current (peak)- 63KA (viii) One minute power frequency withstand voltage to earth- 70KV (ix) Rated auxiliary supply for spring charge motor, lamp and heater circuit- 230V AC. (x) Rated supply voltage for trip/close coil- 110V DC
Supply and fix UPS for 60 min back up single phase AC input 160 to 260 V and output 230 +- 1% of capacity 2 KVA complete all as specified and directed.
Supply , install , testing and commissioning of emergency battery back up system (inverter) of capacity 2 KVA inclusive of lead acid type battery 12 V,150 AH -02 Nos with necessary wiring with PVC heavy duty 25 mm dia conduit duly saddle on wall/roof from inverter to main distribution box for output supply of 220 volts all as directed and specified
Supply and laying in trenches or passing through pipe or laid in cable duct copper control cable of size 2.5 Sqmm 12 core PVC insulated armoured, electric cable with copper conductor 1100 volts grade complete all as specified and as directed (Make : Havells/Polycab / Grandlay / Plaza)
Supply and lay in trenches or passing through pipe or laid in cable duct copper control cable of size 2.5 Sqmm 4 core PVC insulated armoured, electric cable with copper conductor 1100 volts grade complete all as specified and as directed (Make : Havells/Polycab / Grandlay / Plaza)
Supply, laying & testing cable XLPE insulated screened PVC bedded, 33 (earthed) grade, ISI marked, IS : 7098 (Pt-II) galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, of size 3 core 300 sq mm complete all as specified and as directed
Supply ,laying & testing cable in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 400 Sqmm 3.5 core complete all as specified and as directed
Supply and fix cable jointing kit for 33 KV grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 300 sq mm complete all as specified and as directed
Supply, installation, testing and commissioning of a set of 3 Nos lightening arrestors station class single pole non linear register type as per IS 3070 with all fittings discharge capacity 10 KA, rating 30KV(rms) suitable for 33 KV grounded neutral link system fixed on channels, cross arms including connecting to over head line and up to earth pit complete all as specified and directed
Supply, installation and testing of outdoor type (CTs) 33 KV current transformer -03 Nos oil cooled having CT ratio 200/100/1+1 for connecting 33 KV side of Transformer bushing class 5P 15 VA burden suitable for protection and metering operation complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600x 6 mm thick buried in ground vertically to a depth n.less than 2.25 mtr below normal ground level connected to galvanized steel strip 25 x 4 mm earth lead by means of bolts, nuts and washers made of galavanised iron or steel earth strip protected by 40 mm bore light grade GI pipe and connected for body earthing of HT AVR all as specified and directed incl PCC work as per sketch No 3 of SSR Part -I (2009) pit cover slab of size 300x300x50 mm with handle as shown in drawing funnel, wire mesh 20 mm dia GI pipe medium grade for watering, charcoal and slat in alternate layers incl necessary earth pole and excavation in hard/dense soil and removal etc incl testing complete.
Supply & fixing 33 KV 400 Amp air break switch out door type, three phase, double break, centre rotating type suitable for manual operation. Each pole of isolator shall be provided with two sets of contacts to be poperated in series and the moving contact blades shall rotate in horizental plane and galvanised steel frame operating pipe of 25mm bore medium grade GI pipe suitable for operation while standing on ground for 3 phase complete all as specified and directed.
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. N exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and as directed.
Removing excavated materialn exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed
M&L for PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregate for making platform channels complete all as specified and directed.
M & L for brick work with sub class 'B' bricks straight or curved on plan exc 6 mtr mean radius built in cement mortar 1:4 all as specified and as directed.
M&L for Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed at site.
M&L for RCC (Nominal Mix) Type B1 1:2:4 (using 20 mm graded aggregate) as in Slabs supported on walls,beams and columns in floors,roofs, landings, balconies,canopies, deck slabs and in shelves and the like all as specified and as directed
M& L Mild steel(TMT) bars 10mm dia and over, cut to length, bent to shape required, including cranking,bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire(annealed) not less than 0.9mm dia or securing with clips all as specified and as directed
M & L for 15 mm thick rendering in cement morter (1:4) on fair face of brick or concrete surface finished even and fair all as specified and as directed.
M&L preparing surfaces on wall plastered new surafaces and applying three coat of white wash all as specified and as directed.
Supply, fabricating and fixing of MS channel,Cross-arms, MS angle, flat iron and round bars of any size including drilling of holes, nuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide primer for isolator, LA, PT, CT, structure and earth mat complete all as specified and directed.
BHARAT ELECTRICAL TRADERS
R D Bansal
Ashirwad Contractor and Supplier
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .