Execution Left out portion of UG Cable for the godown 01 03 05 AND 06 and C wall lightning at CW Bodhan TG
2026_CWC_283545_1
CWC/RO-Engg. /HYD/26-27/NIT.07
Open Tender
Electrical Works
90 days
BODHAN
Please refer Tender documents.
7 documents required · 7 mandatory
₹590
Central Warehousing Corporation
₹56,000
9 Jul 2026
9 Jul 2026
16 Jul 2026
9 Jul 2026
15 Jul 2026
9 Jul 2026
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (Main 3 phase DB). (All Main DBs must be kept at middle of each godowns)
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A (in Three phase MDB) (INCOMER TO MAIN DB)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 2.5 sq. mm (Polycab) (For tapping from Main Cable to the light fixture of each street light)
Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.=0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (72 WATTS)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. (upto 35 sq. mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (25 MM)
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (28 MM)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. (upto 35 sq. mm)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. (from 35 sq. mm to 95 sq. mm)
Description
Supplying installing testing and comissioning of AC SPD Single Phase 2 Pole 320V, Surge Protection Device AC SPD - Type 2 in the Exisitng DB as per the instructions of the Engineer Incharge
SITC of 3 phase 70 KVA air cooled voltage servo stabilizer with digital control, AC synchronous motor control drive, automatic operation with IP 20 ingress protection with insulation resistance with IS9815 standard, floor mounting indoor use type with wide voltage range control of 310 V AC to 480 V AC, efficiency greater than 97 percent with single phase prevention failure, neutral failure, phase failure and surge protection.
Supply of 6.0 m hot-dip galvanized octagonal pole fabricated in single piece from 3 mm thick HT steel plate for shaft conforming to BSEN-10025 or Equivalent with bottom dia 130 mm, top dia 70 mm, with base plate 220 × 220 × 12 mm, including Galvanizing of Shaft as per IS 2629, along with smart pack terminal box with door size 400 × 100 mm with provision for fixing connector & MCB, and 1.0 m long single-arm bracket, etc., complete with necessary bolts, nuts, cable entry gland, lifting sockets and protective packing, delivered to site.
Supplying and fixing of astronomical digital timer and 25A, with 2 nos. of 4 pole AC contactor inside existing Security Room Main DB for automatic street light control, including all connections, testing and commissioning (At the Main DB feeder of street lights)
From Street Light MDB to 11 groups of Street Lights (group 1)"The 4 core 10 sq. mm AL armored cable shall be laid upto the last pole. At each pole location, the cable shall be looped through HDPE or GI pipe rising 600 mm above ground. Inside the pole inspection door, the cable shall not be cut. Tapping for individual light connection shall be done using aluminium parallel connectors (split bolt connectors) of appropriate size. From the connector, 2.5 sq. mm FRLS copper wire shall be drawn to a 6A SP MCB (for single light) or 10A SP MCB (for two lights if combined). The outgoing phase from MCB shall connect to the LED driver input. Neutral shall be tapped from main neutral core using similar connector. Earth continuity shall be maintained through the armour and supplemented by 8 SWG GI wire/strip if required. Phase assignment shall be R, Y, B in sequence to balance the load."
Supply & testing of XLPE insulated aluminium conductor steel armoured power cable of 1.1 KV grade confirming to IS :7089 (part 1) 1988 or latest amendment and as per instructions of official-in-charge. 4 X 16 sq. mm. (Polycab)
Supply & testing of XLPE insulated aluminium conductor steel armoured power cable of 1.1 KV grade confirming to IS :7089 (part 1) 1988 or latest amendment and as per instructions of official-in-charge. 4 X 50 sq. mm. (Polycab)
Supply, installation, testing and commissioning of MV compartmentalized, modular design electrical panel, suitable for 415 V, 3 phase, 50 Hz, 4 wire system, Sheet thickness not less than 2.00 mm for load bearing members and 1.60 mm for doors, with following ratings aluminium bus bars, free standing, totally enclosed, with following incoming and outgoing switches, meters, inter connections with suitable size aluminium cables / bars, complete with terminating arrangements, powder coating the panel, earthing, with cable chamber, busbar chamber, bottom/top cable entry etc., as per below description and in conjunction with technical specifications suitable for incoming and outgoing bus bar trunking/cable termination complete as required. Base supports shall be of size 75x75x8 mm GI MS angle iron duly primered and enamel painted. Each 1.00 2,00,254.00 2,00,254.00 Extra Item 4 A) INCOMMER : 100A, 4Pole, MCCB --- 1 No with shunt trip/release, 50 KA (Ics=100%Icu), 415V, Microprocessor release for over current, earth fault & short circuit protection, with rotary operating handle mechanism, Spreader terminals with RS 485 communication module and all other accessories etc. as required (provide extended bus-bar for out-going cable termination as required) B) BUS-BAR: 100A Capacity strip Aluminium bus bars (100% neutral) with heat shrinkable coloured sleeves and suitable supports -1 set. C) OUTGOINGS : .i) 6 A feeder - 3 Nos. Each comprising of 6A, 30 KA, 4 Pole , MCCB with Thermal Magnetic release for over current & short circuit protection, with rotary operating handle mechanism front drive kit, Spreader terminals and all other accessories etc complete as required. ii) 16 A feeders - 6 nos. Each comprising of 16A, 30 KA, 4 Pole , MCCB with Thermal Magnetic release for over current & short circuit protection, with rotary operating handle mechanism front drive kit, Spreader terminals and all other accessories etc complete as required. D) METERING :i) Electronic Multi data meter (KW, KWH, KVA, PF, A, V) with suitable CTs as per the requirement. ii) 'RYB' indication lamps connected with suitable control fuse/MCB -1 Set.
Description
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement- All work up to plinth level: 1:1½:3 (1 cement :1 ½ coarse sand : 3 graded stone aggregate 20 mm nominal size)
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-incharge.
Steel Reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete at alll levels : TMT Bars of Fe grade 500 D or more
Centering and Shuttering including strutting, propping etc. and removal of form for:
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 50 mm dia
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 50 mm dia
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 50 mm dia
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. 15.2.1 Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level: 1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20mm nominal size derived from natural sources)
Total Amount (in Rs.)
Total Amount (in Rs.)
Total Amount (in Rs.)
Items of works
All Items of Civil works based on DSR Electrical 2025
Market Rate
All Items of Civil works based on DSR Civil 2023