Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.6 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹27.9 L+₹3.3 L (13.6%)Rejected-AOC | L2 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 3 | L3₹28.5 L+₹4.0 L (16.2%)Rejected-AOC 3838 2ND FLOOR SECTOR 46 C CHANDIGARH UT 160047 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160047 | L3 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 4 | L4₹31.7 L+₹7.1 L (29.0%)Rejected-AOC SECTOR 10 PANCHKULA | PANCHKULA | PANCHKULA | HARYANA | L4 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 5 | L5₹32.4 L+₹7.8 L (31.8%)Rejected-AOC | L5 | Rejected-AOC OTHER THAN LOWEST BIDDER |
Tender Value
₹33.0 L
EMD Value
₹65,900
Closing Date
1 Oct 2022, 6:00 pmClosed
Rahul Meena, IDSE, EE, Garrison Engineer
MES OFFICE GE KASAULI DISTT SOLAN HP
PROVN OF SERVO VOLTAGE STABILIZER 500 KVA AT 14 GTC SUBATHU AND SPECIAL REPAIR/ REPLACEMENT OF PUMPING SET OF VARIOUS SIZES AGAINST BER AT GAMBER PUMP HOUSE UNDER GE KASAULI
2022_MES_547552_2
GEK-48/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SUBATHU UNDER GE KASAULI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE KASAULI
₹65,900
Yes
18 Oct 2022
12 Sept 2022
8 Oct 2022
12 Sept 2022
1 Oct 2022
19 Sept 2022
Amount
Schedule 'A' Section - I
Supply Install, connecting and commissioning and testing of Servo controlled voltage stabilizer of capacity 500 kVA (Confirming as per BIS: 9815: Part 1: 1994 reaffirmed 2019) 3-phase,4 wire 50Hz, with Naturally Oil Cooled, Indoor, Unbalanced Type, insulation A class type, Pure Electrolyte Copper Wound only, Digital Display Type, Relay Free Smooth, with Over load/short circuit protection,High & Low voltage cut off, By pass arrangements, single phase preventor and Silent Operation with 1st filling of Transformer oil (IS335: 1993 reaffirmed 2005) qty of oil should not be less than 1700 Ltr of having following specification:- (1) Incoming - ACB 1600 Amps, 415 V,50 KA ( ii) By pass arrangement - Change over 800 Amps, 415 V. (2) Input voltage 210V- 480V ( 3 phase) , 124 V - 280 V ( 1 phase) or as per ground requirements. (3) Output voltage stabilized at any designed/desired voltage 415V ± 1% (Adjustable in 3 phase) / 240 V ± 1% (Adjustable in 1 phase). (4) Rated frequency 50 Hz. (5) No distortion in wave form. (6) Response time not to exceed 10 mille seconds. (7) Sensitivity (±)1%. (8) Rate of correction of voltage shall not be less than 6 Volt/second between phase and netural. (9) No load losses less than 0.5%. (10) Full load losses less than 2.5%. (11) Duty cycle - continuous 24 x 7. (12) The efficiency of Servo Voltage Stablizer shall not be less than 95% as per clause No. 9.6 of BIS. (13) Type of load: 3 phase, unbalanced type. (14) Digital display Voltmeter/Ampmeter. (15) No load losses - Less than 1%. (16) Full load losses - Less than 3%. 17) CRGO Core - M4 Grade. NOTE:- Testing of Servo voltage stabilizer shall be carried out at the manufacture's work shop in presence of Representative of Accepting Officer and test results shall be signed by both Contractor and inspecting officer before dispatch of Servo Voltage Stabilizer to the work site for installation and copies of the test certificates shall be furnished to the Department . The Contractor shall at his own expense provide all facilities for testing including equipment .
Note for Srl Item No. 1.00 :- 1. Over load/Short circuit protections 2. High/Low voltage cut off 3. By pass arrangement in case of emergency - Change over 800 Amps should be provided 4. Single phase sequence change protection 5. CT of desired qty and capacity should be provided 6. PCC work for installation of voltage stablizer shall be deemed in quoted rate. 7. Making suitable size of shed for stabilizer.
Supply, laying, testing and commissioning of cable LT XLPE insulated, PVC sheathed armoured, 1.1KV grade using stranded conductor aluminium of size 300 Sqmm 3.5 core confirming to IS specification complete incl fixing with aluminum lugs complete all as specified and directed. ( Cable should be laid in existing trench).
Supply, instal, tesing and commissioning 15 HP centrifugal pump horizontal spindle, horizontal/radial split casing End suction, close impeller type , Single stage suitable having discharge capacity 30.6 Ltr / Sec at a head 32 mtrs WMC suitable for nominal speed of 1470 RPM for lifting raw/ treated water (with CI casing (IS:210 Gr FG260 confirming to PN 16), impeller made of CF8 (ASTM A743 Gr CF8), bearing, neckring & bush made of CF8 (ASTM A743 Gr CF8), shaft sleeves & shaft made of SS ASTM A 276 CL 410 with Gland Seal with Max allowable soft solid size-55mm. Directly long coupled with 22 kW , 4P, IE3 ,415 Volts 50 Hz AC nominal speed-1470 RPM electric driven motor. Specifications for motor- TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection.Both pump and motor, mounted on and including a common steel base frame. It shall be placed on PCC / RCC foundation as specified by OEM including form work etc complete all as per manufacturer's instructions. ( Note:- Rate of foundation, Base frame and inlet / outlet pipe of required length, size and dia with existing system deemed to be included in the quoted rate)
Note:- 1. Capacity of pump- 30.6 Ltr / Sec at 32 meters head. 2. Suction Pipe - 125 mm dia and delivery - 100 mm dia 3. Capacity of Motor -22 KW ,415 Volts 50 Hz AC, 1470 RPM , TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection electric driven motor. 4. Place of installation- Raw Water Pump House Gamber. 5. Rate shall deemed to be included for following:- (a) Addition/alteration of suction and delivery side of existing pipes and water connections etc. (b) Pressure gauge, air release valve & balancing valves (pointed towards earth), steel frame for pump and motor. (c) Commissioning of complete pump set shall be done in presence of maufacturer's Engineer and not by any authorized dealer/workshop/ rep/sister concern etc.
Supply, instal, tesing and commissioning 20 HP centrifugal pump horizontal spindle, horizontal/radial split casing End suction, close impeller type , Single stage suitable having discharge capacity 19 Ltr / Sec at a head 30.5 mtrs WMC suitable for nominal speed of 1465 RPM for lifting raw/ treated water (with CI casing (IS:210 Gr FG260 confirming to PN 16), impeller made of CF8 (ASTM A743 Gr CF8), bearing, neckring & bush made of CF8 (ASTM A743 Gr CF8), shaft sleeves & shaft made of SS ASTM A 276 CL 410 with Gland Seal with Max allowable soft solid size-36 mm. Directly long coupled with 15 kW , 4P, IE3 ,415 Volts 50 Hz AC nominal speed-1465 RPM electric driven motor. Specifications for motor- TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection. Both pump and motor, mounted on and including a common steel base frame. It shall be placed on PCC / RCC foundation as specified by OEM including form work etc complete all as per manufacturer's instructions.( Note:- Rate of foundation, Base frame and inlet / outlet pipe of required length, size and dia with existing system deemed to be included in the quoted rate)
Note:- 1. Capacity of pump- 19 Ltr / Sec at 30.5 meters head. 2. Suction Pipe - 80 mm dia and delivery - 65 mm dia 3. Capacity of Motor - 15 KW ,415 Volts 50 Hz AC, 1465 RPM , TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection electric driven motor. 4. Place of installation- Raw Water Pump House Gamber. 5. Rate shall deemed to be included for following:- (a) Addition/alteration of suction and delivery side of existing pipes and water connections etc. (b) Pressure gauge, air release valve & balancing valves (pointed towards earth), steel frame for pump and motor. (c) Commissioning of complete pump set shall be done in presence of maufacturer's Engineer and not by any authorized dealer/workshop/ rep/sister concern etc.
Supply, instal, tesing and commissioning 15 HP centrifugal pump horizontal spindle, horizontal/radial split casing End suction, close impeller type , Single stage suitable having discharge capacity 181.58 Cum / Hrs at a head 15.26 mtrs WMC suitable for nominal speed of 1460 RPM for lifting raw/ treated water (with CI casing (IS:210 Gr FG260 confirming to PN 16), impeller made of CF8 (ASTM A743 Gr CF8), bearing, neckring & bush made of CF8 (ASTM A743 Gr CF8), shaft sleeves & shaft made of SS ASTM A 276 CL 410 with Gland Seal with Max allowable soft solid size-11.5 mm. Directly long coupled with 11 kW , 4P, IE3 ,415 Volts 50 Hz AC nominal speed-1460 RPM electric driven motor. Specifications for motor- TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection. Both pump and motor, mounted on and including a common steel base frame. It shall be placed on PCC / RCC foundation as specified by OEM including form work etc complete all as per manufacturer's instructions. ( Note:- Rate of foundation, Base frame and inlet / outlet pipe of required length, size and dia with existing system deemed to be included in the quoted rate)
Note:- 1. Capacity of pump- 181.58 Cum/Hr at 15.26 meters head. 2. Suction Pipe - 150 mm dia and delivery - 125 mm dia 3. Capacity of Motor - 11 KW ,415 Volts 50 Hz AC, 1460 RPM , TEFC,sq cage, 50 Hz + 5%, 415 V + 10%, confirming to IE3, confirming to IP -65 degree of protection electric driven motor. 4. Place of installation- Back wash Pump House Gamber. 5. Rate shall deemed to be included for following:- (a) Addition/alteration of suction and delivery side of existing pipes and water connections etc. (b) Pressure gauge, air release valve & balancing valves (pointed towards earth), steel frame for pump and motor. (c) Commissioning of complete pump set shall be done in presence of maufacturer's Engineer and not by any authorized dealer/workshop/ rep/sister concern etc.
Ayushmat Contractors
naina devi constructions
M/s Friends Engineering Works
Harsh India Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .