Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.5 LAccepted-AOC | L1 | Accepted-AOC lowest bid quoted | |
| 2 | L2₹38.2 L+₹3.0 L (8.42%)Rejected-Finance | L2 | Rejected-Finance Highest bid quoted | |
| 3 | L3₹38.5 L+₹3.3 L (9.28%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L3 | Rejected-Finance Highest bid quoted | |
| 4 | L4₹39.7 L+₹4.4 L (12.6%)Rejected-Finance H NO 90 VILLAGE REWLA KHANPUR PO NAJAFGARH NEW DELHI 110043 | NEW DELHI | WEST DELHI | DELHI | 110043 | L4 | Rejected-Finance Highest bid quoted | |
| 5 | L5₹39.7 L+₹4.5 L (12.7%)Rejected-Finance NOT FOUND | L5 | Rejected-Finance Highest bid quoted |
Tender Value
₹44.5 L
EMD Value
₹89,000
Closing Date
21 Jun 2022, 6:00 pmClosed
GE (AF) Gurgaon
Gurgaon
SPECIAL REPAIR REPLACEMENT OF EXISTING WORKOUT LT UG CABLE, LOOP BOXES AND DISTRIBUTION SYSTEM OF PERIMETER SECURITY LIGHTS, POLES AND ALLIED WORKS AT RADAR AND TROPO AREA AT AF STN AYANAGAR UNDER GE AF GURGAON
2022_MES_527605_1
GE/GUR-/NIT-10/2022-23
Open Tender
Miscellaneous Works
Piece-work
240 days
GE (AF) Gurgaon
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
₹89,000
18 Jul 2022
31 May 2022
23 Jun 2022
31 May 2022
21 Jun 2022
14 Jun 2022
Amount
Dismantling Steel/ PCC/ RCC pole / strut any size and transporting to store complete all as specified and as directed.
Dismantling cross arms of MS channel or angle sections etc complete and setting for reuse or tpt to store complete all as specified and as directed.
Disamntling insulators any type any size complete all as specified and as directed.
Dismantling stay assembly complete ( demolition of concrete and excavation to be measured and paid separately) complete all as specified and as directed.
Dismatling earth wire or copper conductor , service feedre or distribution span complete all as specified and as directed.
Dismantling of ACSR or AAC conductor complete all as specified and as directed.
Supply and fixing prestressed concrete pole 9 meters long 102 mm x 152 mm at top and 102 mm x 289 mm at bottom of class 10 complete, Including disconnecting and taking out old damage PCC pole complete all as specified and as directed.
Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete, Including disconnecting and taking out old damage PCC pole complete all as specified and as directed.
Supply and lay XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and as directed. Note : The cable length shall be cut not less than 25 Mtr lenght in one span rate. Rate quoted by the contractor deemed to inclusive of suitable size of aluminium lugs at both end termination in desired length/span. The cable shall be terminated at TPN DB's/LT panels etc including provision of one No. cable gland at entry and exit.
Supply and lay XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core complete all as specified and as directed. Note : The cable length shall be cut not less than 25 Mtr lenght in one span rate. Rate quoted by the contractor deemed to inclusive of suitable size of aluminium lugs at both end termination in desired length/span. The cable shall be terminated at Street light loop box/TPN DB's/LT panels etc including provision of one No. cable gland at entry and exit.
S & F pole box for street light dust and vermin proof make : Sintex model GSJB 3020 or equivalent in Universal complete with aluminum bus bar 04 nos. of capacity 200 amps on epoxy insulators incl one MCB SP C series 06 amps 10 KA capacity-01 nos. for Security light connection including suitable size PVC glands-02 nos at bottom for cable entry and exit complete all as specified and as directed. Make Shall be : Sintex/Universal/National. Note : MS Clamps shall be measured and paid seperately under relevant items.
Supply and fix cable 1.5 Sq mm 1100 V FR HR grade three runs/3 core from Pole box to fitting coonector in PVC FR grade conduit 20 mm dia fixed to ples with PVC straps in every 80 cm complete all as directed of length 7.5 mtr long complete all as specified and as directed.
Supply and fixing TPN DB's 4 way "vertical type" 415 V, double door suitable for housing of 100 Amps MCCB as main incoming complete all as specified and as directed.
Supply and fixing MCCB 63 Amps, 4 Pole, 16 KA, fixed type, suitable to be fixed in 4 way TPN DB complete all as specified and directed.
Supply and fix MCB SP 40 Amps, 10 KA 240 V complete all as specified and as directed.
Fabricate, Supply install test and commissioning of CPRI approved outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame, 04 Nos legs made out of 50 x 50 x 5 mm MS angle not less than 600 mm with MS plate of square size 80 mm x 80 mm at bottom of legs, 2 mm thick CRCA sheet (Make -Tata/ sail) ( load bearing members 2 mm thick and non load bearing members such as doors partitions etc of thick ness 2 mm thick ), with gland plates at bottom with suitable Brass chromium plated glands, with cadmium plated high tensile nut and bolts washers, suitable barrel Aluminium lugs for cable terminations complete, with locking arrangements complete ,sheets bend, folded, cut with CNC machine for the accuracy of diamensions +/-0.5%, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -03 nos on incoming side interconnections from bus bars MCCB's with suitable size Aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and directed and comprising of the following ( Radar Area and Tropo Area security light panel). Make of MCCB's Shall be Havells/L&T/Indo Asian/Legrand. Note : Rate quoted by the contractor deemed to inclusive of PCC work 1 : 2 : 4 for embedding of panel complete
(a) Bus bar Aluminum - 250 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves. .
(b) MCCB four pole 440 V, 100-125 Amp, 36 KA , with thermal and magnetic settings - 01Nos (Main Incomer).
(c) MCCB 3 pole, 40 Amps, 16 KA with thermal and magnetic setting - 05 Nos for O/G feeder to different area of security lights
(d) MCB SPN 40 Amps 'C' series- 04 Nos (Spare)
(g) ON/OFF LED indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 1Set of three
i) LED Multifunction meter accuracy class 1.0,input voltage 17 to 520V Ac, flush typ, 96x96 mm size, Model Vega of L&T / equivalent make of ABB/ siemens, suitable to measure parameters such as A,V,F,KW,KVA,KVAr,KVARh,Phase angle ,THD etc-01 Nos,
Fabricate, Supply install test and commissioning of CPRI approved outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame, 04 Nos legs made out of 50 x 50 x 5 mm MS angle not less than 600 mm with MS plate of square size 80 mm x 80 mm at bottom of legs, 2 mm thick CRCA sheet (Make -Tata/ sail) ( load bearing members 2 mm thick and non load bearing members such as doors partitions etc of thick ness 2 mm thick ), with gland plates at bottom with suitable Brass chromium plated glands, with cadmium plated high tensile nut and bolts washers, suitable barrel Aluminium lugs for cable terminations complete, with locking arrangements complete ,sheets bend, folded, cut with CNC machine for the accuracy of diamensions +/-0.5%, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -03 nos on incoming side interconnections from bus bars MCCB's with suitable size Aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and directed and comprising of the following ( Radar Area Gaurd post panel). Make of MCCB's Shall be Havells/L&T/Indo Asian/Legrand. Note : Rate quoted by the contractor deemed to inclusive of PCC work 1 : 2 : 4 for embedding of panel complete
(a) Bus bar Aluminum - 320 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves. .
(b) MCCB four pole 440 V, 160 Amp,36 KA , adjustable thermal and magnetic setting - 01 Nos (Main incomer)
(c) MCCB Three pole, 63 Amps, 16 KA, with thermal setting - 04 Nos for Guard post.
(d) MCB SPN 40 Amps 'C' series-04 Nos (Spare)
g) ON/OFF LED indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 1Set of three
h) LED Multifunction meter accuracy class 1.0,input voltage 17 to 520V Ac, flush typ, 96x96 mm size, Model Vega of L&T / equivalent make of ABB/ siemens, suitable to measure parameters such as A,V,F,KW,KVA,KVAr,KVARh,Phase angle ,THD etc-01 Nos,
Fabricate, Supply install test and commissioning of CPRI approved outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame, 04 Nos legs made out of 50 x 50 x 5 mm MS angle not less than 600 mm with MS plate of square size 80 mm x 80 mm at bottom of legs, 2 mm thick CRCA sheet (Make -Tata/ sail) ( load bearing members 2 mm thick and non load bearing members such as doors partitions etc of thick ness 2 mm thick ), with gland plates at bottom with suitable Brass chromium plated glands, with cadmium plated high tensile nut and bolts washers, suitable barrel aluminium lugs for cable terminations complete, with locking arrangements complete ,sheets bend, folded, cut with CNC machine for the accuracy of diamensions +/-0.5%, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -03 nos on incoming side interconnections from bus bars MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and directed and comprising of the following ( Tropo Area main panel). Make of MCCB's Shall be Havells/L&T/Indo Asian/Legrand. Note : Rate quoted by the contractor deemed to inclusive of PCC work 1 : 2 : 4 for embedding of panel complete
(a) Bus bar Aluminum - 400 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves. .
(b) MCCB four pole 440 V, 200 Amp,36 KA , adjustable thermal and magnetic setting - 01 Nos (Main incomer)
(c) MCCB four pole 440 V, 100 Amp, 16 KA , with thermal and magnetic settings - 04 Nos (Outgoing feeders)
(d) MCB SPN 40 Amps 'C' series-04 Nos (Spare)
g) ON/OFF LED indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 1Set of three
h) LED Multifunction meter accuracy class 1.0,input voltage 17 to 520V Ac, flush typ, 96x96 mm size, Model Vega of L&T / equivalent make of ABB/ siemens, suitable to measure parameters such as A,V,F,KW,KVA,KVAr,KVARh,Phase angle ,THD etc-01 Nos,
Supply and fix in repair three phase 25 KW ( 63 amps ) timer switch with SMC elcosure and 3 nos. power contactors , 3 nos incoming MCBs & 3 nos outgoing MCBs . Including dismantling and taking out warn out timer complete . Make- Nature switches . Cat No.- SWADEEP-02EC25kW3p or equivalent Make out of makes specified in list of makes.
Supply and fixing in repair high efficiency energy saving IP 66 protection cast aluminium roadway luminaire with high power LED light of 45 watt and making connection with street light loop box . Cat No. ENDURAPEARLNEOSL45WLED757PASYTOPC or equivalent Make out of makes specified in list of makes.
Supply and fixing in repair high efficiency energy saving IP 66 protection dia cast aluminium roadway luminaire with high power LED light of 60 watts and making connections with street light loop box. Cat No. ENDURAPEARLNEOSL60WLED757PASYTOPC or equivalent Make out of makes specified in list of makes.
Supply and lay XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified and as directed Note: Rate quoted by the contractor deemed to inclusive of suitable size of aluminium lugs at both end termination in desired length/span. The cable shall be terminated at TPN DB's/LT panels etc including provision of one No. cable gland at entry and exit. (for TROPO Main panel near main gate (DG Set)
Supply and lay XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and as directed. Note: Rate quoted by the contractor deemed to inclusive of suitable size of aluminium lugs at both end termination in desired length/span. The cable shall be terminated at TPN DB's/LT panels etc including provision of one No. cable gland at entry and exit. (for Radar area Guard post panel near proposed security panel)
Demolition of cement concrete of any description for laying of pipes/cables and making good to the disturbed surfaces to match with existing complete all as specified and directed. Note : Providing PCC work shall be measured and paid separately under relevant items.
Cutting existing road surfaces or hard standing 0.45 mtr depth and 0.3 mtr width (22 CM thick comprising bituminous topping) for laying of pipes/cables and making good to the disturbed surfaces to match with existing complete all as specified and directed. Note : Rate quoted by the contractor deemed to be inclusive of PCC 1:2:4 to be required to making good the disturbed surface to match with existing.
M & L for Horizontal drilling hole at a depth upto 1 mtr below the normal ground level of suitable size to insert pipe upto 40-80 mm dia across the road across the horizontal position at different location complete all as specified and as directed.
M & L for GI tubing (light grade) with all necessary fitting laid in trenches/under road crossing, or fixed on poles/walls/under floor etc complete all as specified and as directed for the following sizes:-
a) 40 mm dia bore
b) 50 mm dia bore
c) 80 mm bore
Excavation in trenches in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for pipes and getting out complete all as specified and directed.
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed.
M&L for sand cushning to U/G cable in layers of 23cm thick( 8 Cm before laying the cable and 15Cm thick after laying the cable) and punned to 18cm in trenches, complete all as specified and directed.
Supply and lay well burnt brick class B as protection to cable in cable trenches all as specified and directed
Excavation in trenches in hard/dense soil not exc. 1.5 metre wide and but exc. 1.50m deep for poles and getting out complete all as specified and directed.
S & F sub main wiring for circuit of size 10 sq mm 2 core (FRLS) alongwith earth wire of 6 sq mm single core of FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor including PVC conduit of suitable size complete all as specified and directed by Engr-in-Charge. (FOR SPN DB's)
Material and labour for cement concrete in foundations, filling and mass concrete Type D2 1:4:8 (40 mm graded aggregate) incl form work (for sub base for protection of pipe and LT pole foundation) complete all as specified and as directed
Material and labour for cement concrete in foundations, filling and mass concrete Type D2 1:2:4 (40 mm graded aggregate) incl form work (for top surface) complete all as specified and as directed
Material and labour for coping to street light poles with PCC Type B1, 1:2:4 (20mm graded aggregate incl form work) complete all as specified and as directed
M & L for taking down existing security light brackets of any type and any size including 02 Nos MS clamps with nuts and bolts and Suuply and fixing street light brackets made out of GI tubing medium grade, 32/40 mm dia, 1200 mm long bent to as directed shape at 120 degree, fixed on pole by providing MS clamp 02 Nos made up to flat iron 50 x 6 mm including nuts and washer of suitable size complete all as specified and directed. Note : MS Clamps shall be measure and paid seperately under relevant items.
M&L for earthing complete withGI plate electrodes 600x600x6mm thick buried directly in ground earth pit not less than 2.25m deep below normal ground level with top edge of earth plate not less than 1.5m below ground level connected to G I strip 25x4 mm as earthing lead fixed by means of nut bolt washer of brass as shown in electrical plate No.3 of SSR Pt-I 2009 including necessary excavation and earth work in any strata, GI pipe 20mm dia light grade for watering and 40 mm dia light grade for protection of earth strip upto 7.5 mtrs, charcoal & salt etc and PCC chamber in PCC 1:3:6 type C1 covered with 40mm thick RCC 1:2:4 type B1 using 20mm graded stone aggregate reinforced with 8mm dia MS bar @ 75mm C/C both ways cover, funnel & wire mesh including making of test point all as specified testing on complete.
All as per item No. 39 Above but with earth wire 4 mm dia and 15 mm dia GI pipe light grade for protection upto 7.5 mtrs complete all as specified and as directed
M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop as required of size 25 x4 mm galvanised iron strip as earth continuty lead complete all as specified and as directed.
M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop as required of size 4mm dia galvanised iron as earth continuty lead complete all as specified and as directed.
M&L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed. (for loop boxes and fixing of GI pipe with pole) complete all as specified and as directed.
A B K Enterprises
M/S Anand Enterprises
Ish Engineers and Contractors
shiv shanker enterprises
J B Electricals
Parveen Builders
M/s.sagar enterprises
Surjit and Sons
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .