Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.6 LAccepted-AOC RAWALPORA WANABAL PATI YAYIL POST OFFICE SANAT NAGAR SRINAGAR 190005 J K | SRINAGAR | JAMMU AND KASHMIR | 190005 | L1 | Accepted-AOC L1 | |
| 2 | L2₹50.5 L+₹10.9 L (27.6%)Rejected-Finance 1A BASEMENT 30 31 RAJA HOUSE NEHERU PLACE NEW DELHI | NEW DELHI | NEW DELHI | DELHI | L2 | Rejected-Finance L2 |
Tender Value
₹42.6 L
EMD Value
₹85,280
Closing Date
29 Oct 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 134 Wks Engr
HQ 134 Wks Engr PIN 914134 c/o 56 APO
PROVN OF 01 X 7.5 KVA DG SET, 1 X 15 KVA DG SET, 1 X 62.5 KVA DG SET, 1 X 100 KVA STABILIZER, 1 X 100 KVA TRANSFORMER AND SOLAR WATER HEATING SYSTEM AND INCLUDING ALLIED WORKS AT VARIOUS LOCATIONS UNDER GE 861 EWS.
2022_MES_555464_1
134 WE-50(T)/2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
Srinagar
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE 861 EWS
₹85,280
Yes
6 Dec 2022
1 Oct 2022
31 Oct 2022
1 Oct 2022
29 Oct 2022
15 Oct 2022
1 Oct 2022 - 8 Oct 2022
Amount
Supply, installation, testing and commissioning of diesel engine driven generating set, water cooled of capacity 15 KVA, 415 Volts, 0.8 power factor at an altitude of 6155 feet above MSL, mounted on common base plate with flexible coupling, with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 15 KVA DG set complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.50 mtr and independently supported AVM pads, battery starter type, DG Set should be capable of operating in temperature range (-)15º to (+) 39º Celcius with and including the following :- Note : Cost of foudation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 15 KVA at an altitude of 6155 feet above MSL, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer’s recommendation & mounted common plate through flexible coupling with following fittings :- (i) RPM cum hour meter. (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling.
(vi) Oil temperature gauge. (vii) Safety control with tripping facility for the following :- (a) Low lubricant oil pressure. (b) Over speed. (c ) High water temprature. (viii) Starting equipment comprising of following :- (a) Battery as per manufacturer's recommendation Make :- Exide / Luminus / Amron (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(B) Alternator :- Alternator's rating 15 KVA, 3 Phase, 50 cycle, 415 Volts, 4 wire supply at NTP 0.80 power factor at an altitude of 6155 feet above MSL, running @ 1500 RPM self excited, self regulated, mounted on strong steel fabricated steel frame suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be conforming to BS-2613 OR IS-4722.
(D) Other fitting (a) Battery Charger - Battery charger having electric circuit consisting of triodes, rectifies, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to battery charges through control panel or electric power point. (b) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer’s instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer`s design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (c) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, openable and locable door with air light rubber gasket, interior lighting arrangement.
Supply, installation, testing and commissioning of diesel engine driven generating set, water cooled of capacity 7.5 KVA, 415 Volts, 0.8 power factor at an altitude of 6835 feet above MSL, mounted on common base plate with flexible coupling, with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 7.5 KVA DG set complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.50 mtr and independently supported AVM pads, battery starter type, DG Set should be capable of operating in temperature range (-)15º to (+) 39º Celcius with and including the following :- Note : Cost of foudation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 7.5 KVA at an altitude of 6835 feet above MSL, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer’s recommendation & mounted common plate through flexible coupling with following fittings :- (i) RPM cum hour meter. (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling.
(vi) Oil temperature gauge. (vii) Safety control with tripping facility for the following :- (a) Low lubricant oil pressure. (b) Over speed. (c ) High water temprature. (viii) Starting equipment comprising of following :- (a) Battery as per manufacturer's recommendation Make :- Exide / Luminus / Amron (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(B) Alternator :- Alternator's rating 7.5 KVA, 3 Phase, 50 cycle, 415 Volts, 4 wire supply at NTP 0.80 power factor at an altitude of 6835 feet above MSL, running @ 1500 RPM self excited, self regulated, mounted on strong steel fabricated steel frame suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be conforming to BS-2613 OR IS4722
(D) Other fitting (a) Battery Charger - Battery charger having electric circuit consisting of triodes, rectifies, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to battery charges through control panel or electric power point. (b) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer’s instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer`s design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (c) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, open able and locable door with air light rubber gasket, interior lighting arrangement.
Supply, installation, testing and commissioning diesel engine driven generating set water cooled of capacity 62.5 KVA, 415 volts, 3 phase, 4 wire, 0.8 power factor at an altitude of 5243 feet above MSL with relay panel and switch gear for automatic starting on main failure, control panel having meters and sound proof canopy as per CPCB norms of approved make as per OEM and with necessary foundation as recommended by OEM, mounted on common base plate with flexible coupling with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 62.5 KVA DG set complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.50 mtr and independently supported AVM pads, battery starter type foundation as per manufacturer's design (Including foudation of DG set as per manifacturer's size and specification), DG Set should be capable of operating in temperature range (-)15º to (+) 39º Celcius with and including the following :- Note : Cost of foudation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 62.5 KVA at an altitude of 5243 feet above MSL, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer’s recommendation & mounted common plate through flexible coupling with following fittings :- (i) RPM cum hour meter. (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling.
(vi) Oil temperature gauge. (vii) Safety control with tripping facility for the following :- (a) Low lubricant oil pressure. (b) Over speed. (c ) High water temprature. (viii) Starting equipment comprising of following :- (a) Battery as per manufacturer's recommendation Make :- Exide / Luminus / Amron (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(B) Alternator :- Alternator's rating 62.5 KVA, 3 Phase, 50 cycle, 415 Volts, 4 wire supply at NTP 0.80 power factor an altitude of 5243 feet above MSL, running @ 1500 RPM self excited, self regulated, mounted on strong steel fabricated steel frame suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be conforming to BS-2613 OR IS 4722.
(D) Other fitting (a) Battery Charger - Battery charger having electric circuit consisting of triodes, rectifies, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to battery charges through control panel or electric power point. (b) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer’s instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer`s design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (c) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, open able and locable door with air light rubber gasket, interior lighting arrangement.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 35 Sqmm 3.5 core, laid in trenches, fixing on wall/pole, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 70 Sqmm 3.5 core, laid in trenches, fixing on wall/pole, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 95 Sqmm 3.5 core, laid in trenches, fixing on wall/pole, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 185 Sqmm 3.5 core, laid in trenches, under road crossing etc, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
Supply, laying, commissioning & testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts (earthed) grade, cross sectional area 95 Sqmm 3 core, laid in trenches, complete all as specified and directed by Engr-in-Charge. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of BOQ.
S&F cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories, suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm 3 Core, complete all as specified and directed.
M&L for earthing complete with GI steel earth plate electrode of size 600mm x 600mm x 6mm thick, burried directly in ground pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the Galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised steel, connected to earthing test point with and including necessary excavation and earthwork and earth electrode, earthing lead from electrode to eqpt/sub stn, adequated quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-1 (using 20mm graded stone aggregate), 40mm thick RCC (type B-1) cover reinforced with 8mm dia TMT bar both ways with 12mm dia round bar handle and 20mm bore GI light grade watering pipe with funnel and wiremesh and 40mm bore GI pipe light grade for protection of earth lead upto equipments max length 7.5 mtr, complete all as shown on electrical plate No. 3 of MES SSR Part-I (2009) and directed by Engr-in-Charge. Note :- On testing after completion if the desired resistenance is not obtained, the contrator shall redo the earthing without any extra cost to the department.
M&L for earthing complete with GI steel earth plate electrode of size 600mm x 600mm x 6mm thick, burried directly in ground pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the Galvanised iron strip of size 25x4mm by means of bolts, nuts, check nuts and washers of galvanised steel, connected to earthing test point with and including necessary excavation and earthwork and earth electrode, earthing lead from electrode to eqpt/sub stn, adequated quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-1 (using 20mm graded stone aggregate), 40mm thick RCC (type B-1) cover reinforced with 8mm dia TMT bar both ways with 12mm dia round bar handle and 20mm bore GI light grade watering pipe with funnel and wiremesh and 40mm bore GI pipe light grade for protection of earth lead upto equipments max length 7.5 mtr, complete all as shown on electrical plate No. 3 of MES SSR Part-I (2009) and directed by Engr-in-Charge. Note :- On testing after completion if the desired resistenance is not obtained, the contrator shall redo the earthing without any extra cost to the department.
S&F ON LOAD change over switch 415 volt in sheet metal enlosures 4 pole of capacity 160 Amps, complete all as specified and directed.
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 metre in depth for foundation for laying cables/pipes etc. including getting out any type of soil, complete all as specified and directed by Engr-in-Charge.
M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable after laying, complete all as specified and directed. Note :- Punned thickness of sand shall be measured & paid.
M&L for sub class 'B' brick, old size, as in covering or protection of electric cable, laid dry flat transversally along the length of cable on sand cushioing with width equal to length of brick etc, complete all as specified and directed.
Supplying and laying unreinforced precast concrete cable cover, class LV, type 2 with peak flat of size 300mm x 180mm x 40mm, laid flat length wise perpendicular to the axis of cable, complete all as specified and directed.
Supplying and laying unreinforced precast concrete cable cover, class HV, type 2 with peak flat of size 450mm x 180mm x 40mm, laid flat length wise perpendicular to the axis of cable, complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick, complete all as specified and directed.
Removing excavated material (soil) to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
M&L for 80mm bore GI pipe, light grade with all fittings, for protection of cable, laid in trenches, road crossing and fixed to pole/wall with MS clamps of suitable size, nuts and bolts and including two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer after preparation of surface, complete all as specified and directed by Engineer-in-Charge.
Supply, installation, commissioning and testing of Voltage Stabilizer for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 300 V to 460 V with output voltage stabilized at 415 with accuracy ± 1% and speed of correction 6 Volts per second and of capacity 100 KVA, complete all as specified and directed.
Supply, installation, commissioning & testing LT distribution panel board, outdoor type, double door, pedastal mounted, overall size not less than 900mm x 450mm x 1200mm, CPRI approved, IP-54, made out of 3.15mm thick CRCA sheet duly powder coated, mounted on angle (65x65x6mm) iron frame of height 450mm from PCC bedding, factory assembled compartmentalized construction, free standing type including 3 Phase & neutral 400 Amps current carrying capacity copper bush bar with epoxy insulated coating with colour code and insulated support, cable galleries inter connecting bus bar connection/linkage complete and conforming to IS-8623 of protection as per IS-2147 complete including making connection of cables of incoming and outgoing with thimble/lugs including the accessories, complete and mounting the panel on ground / floor with PCC 1:3:6 bedding upto a height of 30cm above ground level, complete all as specified and directed and comprising as under:-
Supply, installation, commissioning & testing LT distribution panel board, outdoor type, double door, pedastal mounted, overall size not less than 900mm x 450mm x 1200mm, CPRI approved, IP-54, made out of 3.15mm thick CRCA sheet duly powder coated, mounted on angle (65x65x6mm) iron frame of height 450mm from PCC bedding, factory assembled compartmentalized construction, free standing type including 3 Phase & neutral 600 Amps current carrying capacity copper bush bar with epoxy insulated coating with colour code and insulated support, cable galleries inter connecting bus bar connection/linkage complete and conforming to IS-8623 of protection as per IS-2147 complete including making connection of cables of incoming and outgoing with thimble/lugs including the accessories, complete and mounting the panel on ground / floor with PCC 1:3:6 bedding upto a height of 30cm above ground level, complete all as specified and directed and comprising as under:-
Supply, installation, commissioning & testing of highly energy efficient, outdoor type oil immersed naturally cooled (ONAM) transformer copper wound type of capacity 200 KVA as per latest IS code, conforming to IS-1180, Level-II with off load tap changer on primary side to vary secondary voltage within limit (+) 5% to (-) 7.5% in step to 2.5% including standard fittings and first filling to transformer oil as per IS-335 of 1980 with cooling system. The transformer shall be provided with cable termination box to terminate outdoor type termination of suitable size on HT side 11 KV & LT side 1100 volts. Transformer step down ratio 11000 volts/ 433 volts, 3 phase 4 wire, impedance as per oil type, ONAM cooled, suitable for outdoor installations and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibration and noise. The winding shall be copper and shall be designed for full load current and with stand the thermal and electro magnetic stresses arising due to the through fault current vector group shall be DYN 11 including supply of all standard fittings & fixtures and comprising of the followings :- Make : Voltamp / Crompton Greaves / GEE Industries / Indian Transformer Ltd (ITL)
(a) HT cable termination box. (b) LT cable termination box. (c) Rating and diagram plate. (d) Earthing terminals. (e) Lifting lugs. (f) Oil level indicator with minimum level marking. (g) Thermometer pocket. (h) Conventional conservator with oil filling hole with cap and drain cum sampling valve. (j) Air release plug. (k) Silica gel breather. (l) Off circuit tap changer with locking provision. (m) Bi-directional rollers. (n) Jacking Pads. (o) Radiators/ Fins and all (Epoxy painted). (p) Danger Notice Board.
M&L for base for placing of transformer of capacity 200 KVA, size of base 3.0 mtr x 3.0 mtr x 1.0 mtr above ground level and 0.30 mtr below ground level (in foundation) including necessary excavation and earth work in any type of soil, PCC 1:4:8 type D-2 in foundation, earth & hardcore filling as required at site, brick work with sub class bricks old size built in CM 1:4, 100mm thic PCC 1:3:6 type C-2 in sub base of floor, 100mm thick PCC 1:2:4 type B-1 in floor, 15mm thick rendering in CM 1:4, two coats synthetic enamel paint over a coat of red oxidide primer (as required at site) and three coats of whie wash, complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of 'Solar Hot Water System', Flat Plate Collector type, based on indirect transfer of heat of capacity 300 LPD and including stainless steel hot water tank with electrical heating backup, complete all as specified and directed. Note :- The make of solar water heater system shall be approved by GE and the same should be approved in MES. .
M&L for hot water pipe duly insulated with glass wool and aluminium cladding 15mm bore, complete all as specified and directed.
S&F ball brass valve, high pressure, with polythene float and flynut complete, screwed for 15mm bore iron pipe or brass ferrule, complete all as specified and directed.
M&L for 20mm bore GI water tube, medium grade with all fittings and fixtures, complete to walls and ceiling or laid in floors, complete all as specified and directed.
S&F 20mm bore gun-metal, globe or gate valve, with iron wheel head, screwed both end for iron pipe and fixed, complete all as specified and directed.
S&F 500 ltrs capacity rotational moulded polyethylene water storage tank (three layered) cylindrical vertical with closed top, hoisted and fixed in position with connecting, complete all as specified and directed.
M&L for cross arms, bracings, supports, clamps and back plates, fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide zinc chrome primer and one under & finishing coat of synthetic enamel paint for staging for cold water tank of salor system, complete all as specified and directed.
M&L for PCC 1:3:6, type C-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete, complete all as specified and directed.
M&L for sub main wiring using FRLSH insulated unsheathed, multistandard coper conductor PVC cable 2 runs of size 4 Sqmm for phase and neutral and 1x4 Sqmm for earthing drawn through rigid PVC conduit of suitable size, fixed on wall/ground/ceiling etc, complete all as specified and directed. Notes :- (a) Phase should be red/yellow/blue, neutral should be black and earthing wire should be green in colour. (b) Two runs of cable for phase/neutral and one run of cable for earth including conduit will be measured and padid as one unit length.
S&F sheet metal enclosure, factory made, double door shutter type for DB SPN, 240 Volts, 4 ways with 200 Amps rated copper bus bar, neutral link, earth bar, IP-43 protection with and including flush to wall with all cutting and making good disturbed surfaces of wall to match with existing surface, complete all as specified and directed.
S&F MCB SPN 32 Amps, 230 Volts 'B' series, 50 Hz, AC, 10 KA, complete all as specified and directed.
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .