Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-AOC | L1 | Accepted-AOC Accepted being lowest | |
| 2 | L2₹8.2 L+₹81,920 (11.1%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹8.1 L
EMD Value
₹16,200
Closing Date
30 Sept 2019, 6:00 pmClosed
GE (I) (P) Ratnagiri
Military Engineer Services Garrison Engineer (I) (P) Ratnagiri SLUY Shed Plot, W19-23, MIDC Mirjole, Ratnagiri - 415 639
PROVN OF AIR CONDITIONING AT ICGAS RATNAGIRI AND PROVN OF AIRCRAFT WASHING POINT AT ICGAS RATNAGIR
2019_MES_276921_1
8098/E8
Open Tender
Civil Works
Item Rate
180 days
Ratnagiri
Please refer tender documents
6 documents required · 6 mandatory
₹500
GE (I) (P) Ratnagiri
₹16,200
Yes
28 Jan 2020
26 Aug 2019
7 Oct 2019
26 Aug 2019
30 Sept 2019
9 Sept 2019
Amount
Supply,Install,test and commissioning hi wall split unit indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality of capcity 2 TR with 5 star inverter all as specified and directed.
Supply and install voltage stablizer for automatic operation, single phase copper wound naturally air cooled indoor type and desingned for input variation between 170 volt to 260 volt with output voltage stablized at 220/230 volt with accuracy of 2.5% of capacity 5 KVA.
S&F MCB DB TPN 4 way, having degree of protection as IP 43- with metal door (double door), 415 V, complete with 200 amps rated copper bus bar and neutral link all as specified and directed.
S&F MCB TPN 63 Amps 415 V, 'C' series all as specified and directed
S&F MCB SPN 40 Amps 240 V, 'C' series all as specified and directed
Supply, Lay, Testing and commissioning UG cable XLPE insulated, armored heavy duty electric cable, 1100 volts grade with stranded aluminium conductor of size 16 Sqmmx 4 core all as specified as directed.
M&L for submain wiring with 2 runs of single core PVC insulated FRLS unsheathed suitable for 1100 volts, multistranded copper conductor conforming to IS:694:1990 with ISI marked cable of size 6.0 Sqmm and one run of 1100 Volts grade PVC insulated FRLS unsheathed 4.0 Sqmm multistranded copper conductor cable 1100 volts green colour as continuous earth conductor drawn in and including PVC conduit medium grade of size 25 mm dia , ISI marked for sub-main wiring on surface in wall/roof etc. with required accessories complete all as specified and directed.
S&F single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps
Supply,Installed,test and commissioning of Submersible pump, electric driven 415 V,3 Phase,2900 rpm,20 Mtr head,discharge 12 LPS capacity 5 HP suitable for 80 X 60 mm dia suction and delivery pipe alongwith automatic star delta starter of suitable capacity all as specified and directed.
Supply and lay pipe galvanized, medium grade including fittings 80 mm dia laid in trenches all as specified & directed.
Supply and lay pipe galvanized, medium grade including fittings 50 mm dia laid in trenches all as specified & directed.
Supply and lay pipe galvanized, medium grade including fittings 40 mm dia laid in trenches all as specified & directed.
Supply and lay pipe galvanized, medium grade including fittings 25 mm dia laid in trenches all as specified & directed.
Supply and fix sluice valve of size 80 mm dia duly flanged and confirming to IS -14846 and of class PN 1.0 complete all as specified and directed.
S&F gun metal, globe or gate valves size 50 mm dia with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
S&F glun metal, globe or gate valves size 25 mm dia with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
Supply and fix Reflux valve with by pass arrangement, 80 mm dia all as directed.
Supply, Lay, Testing and commissioning submersible cable flat type,pvc insulated & pvc sheathed size 6 Sqmm X 3 core, 1100 volts all as specified as directed.
Supply install test and commissioning of LT panel board 3 phase 4 wire , 415 volts with 200 Amps aluminium bus bar, outdoor type cubical type ,IP-54 dust and vermin proof fabricated out of CRCA sheet not less than 3.15 mm thick fixed on angle iron frame of 50x50x6mm duly powder coated , front openable double door hinged with locking arrangements , CPRI approved compete including necessary PCC platform of suitable size etc complete with following items:- 1) MCCB 63 A 25 KA TPN - 01 No (As Incomer) 2) MCCB 32 A 16 KA 4P - 02 (As Outgoing) 3) MCB TPN 32 A, 16 KA - 01 4) Space for provn of starter.
Supply and fix 4 pole MCCB 63 Amps , 50 Hz, 415 V with rupturing capacity 25 KA all as specified and directed.
M&L for Earthing complete with GI plate electrode of size 60 Cm X 60 Cm X 6 mm thick, burried directly in ground vertically ,erath pit not less than 2.25 mtr.deep below normal ground level with the top edge of the earth plate at a depth not less 1.5 mtr below normal ground level connected to GI stip earth lead of size 32 x6 mm by means of bolts, nuts,washers made of galvanised iron and connected to main control board /switch gear/pannel boards all as specified and shown in Electrical plate of MES Schedule (SSR) part-1 including funnel with watering pipe size 20 mm med grade,Protection pipe size 40 mm dia med grade, and necessary excavation and earth work in any type of soil,charcoal dust,salt and PCC 1:2:4 type B1 in chamber RCC 1:2:4 type, B1 cover slab with 6 mm dia mild steel bars at 100 mm center to center both ways and with 6mm dia MS hook compleate and testing resistence all as specified and as directed.
Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers , welding , bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of one coat of primer , one under coat and one finishing coat of paint
Supply and lay GI pipe light grade as cable protection laid on trench/floor, fixed on pole/wall etc of following size 40 mm dia all as specified and directed.
Excavation in trenches n. exc 1.5 m wide and n exc 1.5 mtr in depth and getting out in soft/disinteglated rock for UG cable & GI Pipe all as directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/disinteglated rock etc all as specified.
Removing excavated material to a distance not exceeding 50 m and depositing where directed at level n.exc 1.5 m above the starting point.
Supply and lay fine sand cushion in trenches for cable protection, spreading, levelling, Punning and consolidating complete all as specified
Supply and laying un re-inforced precast concrete cable cover, class LV, type-I flat, size 250 mm x 150 mm x 40 mm in trenches over and across the cable complete all as specified
m/s Pravin s Bhosale
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .