Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹48.5 L
EMD Value
₹70,000
Closing Date
29 Sept 2023, 2:00 pmClosed
Superintending Engineer
Superintending Engineer, E.W.C., 177, Alenganj, Prayagraj
Supply of Materials for Construction of 33 KV Line, Increasing Capacity of Power T/F installed at various Sub-Stations, Repairing and Replacement of 33 KV Switchyard equipments etc. and Installation of Batter and Battery Charger under EDC-II, Praya
2023_PVVNV_837926_1
06/EWCP/2023-24
Open Tender
Electrical Works
Turn-key
360 days
Prayagraj
Supply of Materials for Construction of 33 KV Line, Increasing Capacity of Power T/F installed at various Sub-Stations, Repairing and Replacement of 33 KV Switchyard equipments etc. and Installation of Batter and Battery Charger under EDC-II, Praya
2 documents required · 2 mandatory
₹4,130
Account Number 914020010003107
₹70,000
Yes
7 Oct 2023
14 Sept 2023
30 Sept 2023
14 Sept 2023
29 Sept 2023
14 Sept 2023
Increasing capacity of 33/11 KV S/S (1x5) MVA to (1x10) MVA Aamepur, Karanaipur, Handiya Tahasil and (8+10) MVA to (10+10) MVA Soraon
ERECTION OF WORK AS PER RESSPO NORMS.
Erection of complete structure for 33 KV lightening arrestor in switch yard. as per RESPO drawing. Work includes Erection of 3 Nos.33 KV Lightening arrestor, its fitting and mounting with care. Grouting of structure with L.C, of 1:3:6 construction of plinth size 0.90x0.45x 0.45 cum. plastering the plinth with cement mortar with cement and sand in ratio 1:4. Works includes cost of clamp concrete material, labour T&P and cement, which shall be provided by the contractor. 33 KV lightening arrestor and Structure Provided by the Department.
Erection of complete 33 KV VCB with Singl Control Pannel with structure in switchyard and grouting of VCB Structures. C.T. Structure by cement, sand, brick ballast mortar in ratio 1:3:4. Work includes complete fitting of VCB and C.T. on structure carefully with making all connections of control cable for operating the VCB and C.T. Only VCB, C.T., Battery and battery chargar and their structure shall be provided by the department. All other item like cement, concrete material, T&P shall be provided by the contractor. Work also includes installation and commissioning of Battery and Battery charger.
Installation of 33 KV transformer control pannel in the switchgear room and grouting the pannel by rag bolt using cement, sand mortar in ratio 1:3. Work includs fitting of all accessories in all respect with complete connection of control cable with pannel.Grouting material will be provided by the Contractor.
Repairing of Existing T/F plinth size 4.46 x 3.46 x 1.0 Mtr.
Dismantling of Switchyard fencing for safe shifting of old 5/8/10 MVA power T/Fs
Safe Shifting & dragging of old 5 MVA T/F from inside to out side of Switch Yard after detaching its accessories i.e. Radiator, conservator etc and empting the T/F i.e taking out the T/F oil and disconnecting all 33 KV and 11 KV connections as well as dismantling of 11 KV cable stand and neutral stand. All tools & T&P shall be provided by the contractor.
Safe shifting and dragging of 10 MVA Power Transformer from outside of Switch Yard to inside of Switch Yard taking precautions to avoid damage of bushings of Transformer and other accessories. All tools, T&P etc shall be provided by the contractor.
Erection of 10 MVA Power Transformers on plinth, fixing of all accessories like radiator, conservator tank etc. complete and filling of T/F oil in Transformer complete in all respect.
Special earthing of neutral and body of 10MVA T/F with the help of 3 Nos.G.I. pipe 40 M.M. dia. length 20 feet. G.I. pipe for making of delta, and 2 nos for body earthing complete in all respect and connected with 50x6 m.m GI Strip. G.I. Pipe, G.I. Strip etc. required for completion of work in all respect shall be provided by the Contractor.
Earthing of 11 KV indoor equipments, switch gears as per RESPO Drawing. with G.I. Strip of Size 50x6 mm, provided by which will be the contractor.
Special earthing of T/F neutral by boring 2” dia 20 feet long G.I. pipe in the wet earth and connecting it with 35x6 mm. G.I. strip to T/F neutral giving half round turn at the T/F. Two separate earthing to be provided to T/F body by connecting it with earth mat by special earthing arrangement for earthing work. Material Like Strip of size 50x6/35x6 mm and G.I. pipe 2” dia 2.9 mm thick shall be provided by the contractor used in above work.
painting of All structure and equipment inside the switch yard with two coats of red oxide primer and thereafter two coats of aluminium paint, giving silver white finish, painting is to be done after proper cleaning of the structures. paint, primer, thinner etc. required shall be provided by the contractor himself.
Laying of 11 KV 3 x /120/185/300 Sqmm. XLPE power cable by digging 0.75 Mtr. deep trench, putting layer of sand in the bottom, ramming it, laying of cable over it RMT and covering the cable from sides and top by laying bricks, finally covering the same by earth and levelling of the same, all the materials, except cable, will be provided by the contractor. Rates may be quoted per RMT
Cartage of materials from store center Naini to site, like all Sub station structure, 11 KV Switch gears, Earth mat material, poles, station T/F, All Equipment (TPMO, LA, Fuse set, C.T, P.T. Isolators, VCB, Conductor, Cable, etc.)
11 KV 3 x 120/185/300 Sqmm. Joniting Kits
Indoor
Outdoor
Protection Equipment and Repairing Switchyard Accessories of 33/11 KV Substations Distt. Pratapgarh
Replacement of Complete Lighting Arrester and Dismentling of damage Lighting Arrester Labour & T&P etc. Shall be Provided by the Contractor. Lighting Arrester with Structure Provided by the Department.
Erection of complete 33 KV VCB with Single T/F Control Pannel, C.T with structure in switchyard and grouting of VCB Structures. C.T. Structure by cement, sand, brick ballast mortar in ratio 1:3:4. Work includes complete fitting of VCB and C.T. on structure carefully with making all connections of control cable for operating the VCB and C.T. Only VCB, C.T., and their structure shall be provided by the Department . All other item like cement, concrete material, T&P shall be provided by the contractor.
Instalation and Commissioning of 24 Volt Battery & Battery Charger. Material Proveded by the Department
Earthing Indoor Equipment provided by the contractor.
Control cables
Control cable 4x2.5 mm2 provided by the contractor.
Control cable 2x2.5 mm2 provided by the contractor.
M/s Samdariya and Company
M/s Amrawati Enterprises
Shiv Enterprises
Dinesh Traders
Urmila Associates
PRANIKA ENTERPRISES
MONU ENTERPRISES
J.L. Enterprises
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .