Executive Engineer
Electric Division JPDCL Udhampur
erection of poles and shifting of substation
2022_PDD_175097_1
ED/UDH/15 of 2022-23 dt. 20-06-2022
Open Tender
Electrical Works
Turn-key
90 days
at Nagulta A and Konard, Reyal of Nagulta B 1
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Executive Engineer, Electric Division JPDCL
₹10,000
8 Aug 2022
21 Jun 2022
15 Jul 2022
21 Jun 2022
13 Jul 2022
21 Jun 2022
21 Jun 2022 - 28 Jun 2022
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Providing/Erection of 11 KV Isolation Point at Pyt. Nagulta A.
GI Channel X-arm including clamps and Angle for braces
11 KV GO Switch 3 phase, 3 pole, 200 Amp. Vertical Type
0.03 ACSR Weasel Conductor
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
Galvanized Nuts and Bolts
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of electric station by way of Replacement of LT Cable for 4 No 25 KVA Sub Station and 1 no 100 KVA Sub Station at Pyt. Nagulta A.
70 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
185 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
MS Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Switch including Angle/Flat of Sizes including clamp/Busbar insulator/Aluminium busbar (50X6mm)
LT Shackle insulator
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm sq. ACSR Weasel Conductor for Shifting of 63 KVA Transformer at Pyt. Nagulta B W.No. 2 Konard.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
0.03 ACSR Weasel conductor
PG Clamps for 30mm² ACSR Conductor
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
Galvanized Nuts and Bolts
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm for LT
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Shifting of 63 KVA Transformer at Pyt. Nagulta B W.No. 2 Konard.
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
MS Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Switch including Angle/Flat of sizes including clamps/Busbar insultor/Aluminium busbar strip (50X6mm).
Painting of substation with one coat of red oxide and two coat of aluminium paint
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Shifting of 63 KVA Transformer at Pyt. Nagulta B W.No. 7 Reyal.
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Switch including Angle/Flat of sizes including clamps/Busbar insultor/Aluminium busbar strip (50X6mm).
Painting of substation with one coat of red oxide and two coat of aluminium paint
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 phase 4 wire LT mm² line on 8 mtr. ST poles for shifting of 63 KVA transformer to roadside at Pyt. Nagulta B W.No. 2 Konard.
8 mtr. Long ST Pole (ST-410 SP15)
GI M-Clamp for shackle insulator
0.03 ACSR Conductor Weasel.
16 KV Polymer Shackle Insulators
Galvinized Nuts and Bolts.
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
AJAY KAPOOR
ADITYA SHARMA
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .