Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹22.7 LAccepted-AOC | ₹22.7 L Quoted ₹23.6 L | L-1 | Accepted-AOC L-1 |
| 2 | L-2₹23.8 L+₹19,865 (0.84%)Rejected-AOC 42 INDUSTRIAL ESTATE GWALIOR MP 474004 | GWALIOR | GWALIOR | MP | 474004 | ₹23.8 L+₹19,865 (0.84%) | L-2 | Rejected-AOC L-2 |
| 3 | L-3₹28.3 L+₹4.8 L (20.3%)Rejected-AOC | ₹28.3 L+₹4.8 L (20.3%) | L-3 | Rejected-AOC L-3 |
| 4 | L-4₹32.8 L+₹9.3 L (39.3%)Rejected-AOC 15 CP COLONY MORAR GWALIOR MP 474 006 | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | ₹32.8 L+₹9.3 L (39.3%) | L-4 | Rejected-AOC L-4 |
Tender Value
Refer Docs
EMD Value
₹67,200
Closing Date
28 Apr 2022, 6:00 pmClosed
GE I RND DELHI
MILITARY ENGINEER SERVICE, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPAIR /REPLACEMENT OF LT PANEL, APFC PANEL, PERIMETER LIGHT, STREET LIGHTS, SECURITY LIGHTS, GATE/GARDEN LIGHTS AND OTHER CONNECTED WORKS AT DRDE GWALIOR UNDER GE (I) RND DELHI
2022_MES_514998_1
GE/RND-118/GWL/2021-2022
Open Tender
Civil Works
Item Rate
270 days
Gwalior
Class-D, cat b(i)
2 documents required · 2 mandatory
₹500
GE I RND DELHI
₹67,200
Yes
14 May 2022
23 Mar 2022
2 May 2022
23 Mar 2022
28 Apr 2022
16 Apr 2022
Amount
S&F automatic power factor control relay of 12 stage operating Voltage - 230 V AC and current Input - 1A or 5 A,Steps- 12 relay outputs ,Supply Voltage - 1Ph 415 VAC (-40% to +20% ),Measurement Voltage : 3Ph 3 wire 415 VAC (-40% to +20% ) ,Operating temperature : 0 to 70 º C , of M/S EPCOS CAT NO.BR6000,PFC CONTROLLER-BR-6000-R-12- Material Code - B44066R6012R 230N-1 or equivalent including testing, connecting, commissioning in such a way to avoid "controller hunting" complete all as specified and directed having following features:- (a) Microcontroller logic for measurement. (b) User friendly operation. (c) Control mode : binary , unequal and user defined. (d) Multifunctional LCD display. (e) Single CT sensing for balanced loads. (f) Individual harmonic measurement upto 15th order. (g) Three CT sensing for unbalanced load. (h) Dual target Power Factor setting useful for utility and DG mode operation, (j) Automatic synchronization. (k) Separate 3 CT monitoring of healthiness of Capacitor within Panel. (l) Data logging. (m) RS 232 in front and RS 232/485 switchable connection at rear. (n) Step operation indication on LCD display plus LED which facilitates viewing from a distance. (o) Unique facility of including 'Fixed Capacitor Bank' for purpose of Transformer compensation. This can be set such that the controller doesn't ‘see' this capacitor. (p) Unique external temperature sensing by PT100. (q) Settable alarm facility - undervoltage,overvoltage and so on. (r) Settable auxiliary outputs - 2 Nos for Alarm, etc. (s) Dynamic Power Factor Controller (Transistorised) available in16 steps without PT100 facility available. (u) EMI/EMC type tested complete all as specified and directed.
M&L for repair of unserviceable APFC panel by servicing and renewals of burnt / unserviceable Power/Control wiring and spare parts to achieve Power Factor upto 0.99 for the capacity upto 75 KVAR complete all as specifies and directed.
All as per item ser No 2 above but for capacity 100 to 150 KVAR.
All as per item ser No 2 avobe but for capacity 175 KVAR
Note for item 2 to 4 (i) Rate quoted by contractor deemed to be included for renewal of burnt copper wiring, copper lugs and other necessary screws,nuts and bolts etc. (ii) The spare parts to be replaced shall be measured and paid separately as per respective items of the schedule. (iii) Penalty will charged @ Rs 100.00/day/panel till the completion of the work to contractor in case of average PF falling below 0.98 after the period of two months of the date of acceptance of tender.
S & F in repairs 10 KVAR power factor correction capacitor Heavy Duty Long life rectangular box type, self standing units of modular construction with sheet metal enclosure, self healing property, PU resin as impregnant with safety device in the form of pressure sensitive (over pressure) mechanical interrupter including wire for use on 440V (AC), 3 phase, 50 Hz,(Series B32459) AC conformance to Standards IEC 60831-1 2/96, IS 13340 with MPP film with heavy edge including testing, commisioning as in repairs complete all as specified and directed
All as per item ser No 5.00 above but of capacity 15 KVAR .
All as per item ser No 5.00 above but of capacity 20 KVAR .
All as per item ser No 5.00 above but of capacity 25 KVAR
S&F in repair power capacitor duty contactor 240 volts suitable for 10 kVAR including testing connecting commissioning complete all as specified and directed.
All as per item ser No 9.00 above but for 15 KVAR .
All as per item ser No 9.00 above but for 20 KVAR
All as per item ser No 9.00 above but for 25 KVAR.
S&F in repair HRC fuse link,Type HG,offset, size F1, 2 - 16 amps cap base/holders complete all as specified and directed.
S&F in repair HRC fuse link,Type HG,offset, size A2, 16 To 32 amps cap , Fuse base/holders. complete all as specified and directed
S&F in repair HRC fuse,Type HQ,offset, size A3, 35 to 63 amps cap ,Fuse base/holders complete all as specified and directed.
S&F in repair HRC fuse,Type HQ,offset, size A4, 125 amps cap ,Fuse base/holders complete all as specified and directed.
S&F in repair Fuse holder A2 type, suitable for 4 to 32 Amps bolted fuse links complete all as specified and directed.
S&F in repair Fuse holder A3 type, suitable for 35 to 63 Amps bolted fuse links complete all as specified and directed.
S&F in repairs Fuse holder A4 type, suitable for 80 to 125 Amps bolted fuse links complete all as specified and directed.
S&F in repairs Solid state relay of 55 to 60 Amp swithing the capacitor bank complete all as specified and directed.
S&F in repairs thyrestor controller relay 75 amp complete all as specified and directed.
S&F in repairs thyrestor controller relay 125 amp complete all as specified and directed.
M&L for control wiring of the panel with 440V 10 Sq mm PVC insulated stranded single core copper conductor cable (FR-LS) conforming to IS for power circuit, the wire ends will be copper ferruled including disconnecting and removing the unserviceable wire connecting testing complete all as specified and directed.
All as per item ser No 23.00 above but 2.5 Sqmm cable.
S&F in replacement of old unserviceable digital Ammeter for measuring alternating current of range : 0 - 450 A flush type 96x96MM size complete all as specified and directed.
S&F in replacement of old unserviceable digital Voltmeter for measuring alternating current voltage of range : Range 0-500 V flush type 96x96MM complete all as specified and directed.
S&F in replacement of old unserviceable indoor resin cast ring type current transformer of ratio 800/5 Amps, accuracy - 15VA, Class - 5P10 complete all as specified and directed.
M&L for painting to electric control panel of E/M installations by cleaning the existing old paint with the help of mechanical tools such as wire brush, scraper and sand paper from the surface of panel and painting the prepared surface with two coat of synthatic enamel paint of approved shade complete all as specified and directed.
M & L for mild steel sheet for repair to electric panel doors, bus bar cover and accessories mounting supports for alignment with front door with 2 mm thick MS sheet duly painted with two coats of synthetic enameled paint over one coat of red oxide primer including necessary cutting, welding and fixing complete all as specified and directed.
Material and Labour for earthing complete with Steel earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron strip of 25x4 mm by means of GI nuts, bolts and washers. Strip shall be laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a) GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly be tightened on GI watering pipe and embeded in PCC earth pit with open top suitable for watering of earth pits) (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel TMT bar 75mm centre to centre with 2 Nos MS handles of 12mm dia mild steel TMT bars suitable for carrying of pit cover.
S&F in repairs, Breaker control switch (Trip-Neutral-close), TNC with 2NO + 2NC SPR RTN complete all as specified and directed.
S&F in replacement old unserviceable Rotary Type A/M Switch, 1 Pole, 2 Way with Off complete all as specified and directed.
S&F Flush head Push Button Green/Red colour with 1 NC Block, complete all as specified and directed.
S&F in replacement multi function meter having LCD Display,96 x 96 sq.mm Flush mounted case, accuracy class 1.0 capable of measuring Instantaneous, Average, Maximum and Total Current from 50A to 6000A and voltage from 120V AC to 300V AC Phase to Neutral, Phase to Phase Voltage, Instantaneous, Average, Maximum and Total Active Power KW, Instantaneous, Average, Maximum and Total Reactive Power KVAR, Instantaneous, Average, Maximum and Total Apparent Power KVA, Instantaneous and Total Power Factor, Frequency complete all as specified and directed.
S&F in repairs instrument Cooling fan , 3000 RPM, 230 Volts 50 Hz complete within the panel including cutting a suitable size hole on the panel body and wiring with 1.5 Sqmm copper conductor cable and MCB SPN 6 Amps complete all as specified and directed.
S&F in repairs capacitor cooling Exhaust fan 230 volts complete all as specified and directed.
S&F in replacement LED indicator - R/Y/B/G 240 V AC complete all as specified and directed.
S&F in repairs MCB TP 63 Amps 10 KA 'C' Series 415 Volts complete all as specified and directed.
S&F in repairs MCCB 125 Amps 3 pole, 415 V, breaking capacity 16 KA & connected accessories complete as specified and directed
S&F in repairs MCCB 160 Amps, 3 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete as specified and directed.
S&F in repairs MCCB 200 Amps, 3 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete as specified and directed.
S&F in repairs MCCB 250 Amps, 3 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete all as specified and directed..
S&F in repairs MCCB 350 Amps, 3 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete all as specified and directed.
S&F in repairs MCCB 400 Amps, 4 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete all as specified and directed.
S&F in repairs MCCB 630 Amps, 4 Pole, 415 V, Adjustable type, with breaking capacity 50 KA including spreader terminals & connected accessories complete all as specified and directed.
S&F in repairs ON load changeover switch with phase Barriers & Handle with door interlock kit is integral part of the Changeover Switch ,with SS enclosure 400 Amps, 4 Pole, 415 V, AC, 50 Hz complete all as specified and directed.
M&L for repairing / servicing the existing unserviceable Air Circuit Breaker of 800 Amp capacity L&T/Crompton make for proper functioning (tripping) on overload and earthfault by replacing the wornout parts, tighting all cable ends incuding replacing the unserviceable lugs etc, cleaning the dust by blower complete all as specified and directed Note:- (i) Wornout/unserviceable parts of ACB will be paid & measured separately under respective item of schedule. (ii) The servicing of ACBs will be done only through authrised rep of OEM.
Supply only Lockable trip push button (LTPB) kit of 800 Amps Air circuit breaker complete all as specified and directed.
Supply only contact spring complete all as specified and directed.
Supply only moving contact complete all as specified and directed.
Supply only Door interlock complete all as specified and directed.
M&L for repairs to main electrical panel at sub stations by tightning the all loose connections of the cable ends & replacing the damaged/unserviceable /burnt aluminium lugs of required sizes, insulating/secure the weak insulated portion of cable ends inside the panel by taping with good quality of insulation tape, clean the dust by air blower complete all as specified and directed.
Dismantling and Taking Out old unserviceable LT Panel and Supply, installation, Commissioning and testing LT panel board of size 1800mmx1500mmx500mm (approximate) as approved for 3 phase, 4 wire, 415 Volts ,AC , 50 Hz supply, Indoor cubical type Double door, dust and vermin proof, pedestal mounting type suitable for Indoor applications having suitable shape/ size, made out of 3.15 mm thick MS sheet with using 40mm x 40mm x 5mm angle iron frame and supports, duly finished with powder coated using two coats of synthetic enamel paint of approved colour over a coat of red oxide primer all over steel surfaces complete with separate compartment of suitable shape and size with shutter and locking arrangement for each switchgear and including PCC work for fixing panel legs. Bus bar of aluminium conductor suitable shape and size for 3 phase rating of 800 amps and for neutral 600 Amps rating including taking out end connectinons of the existing cables and fixing the cable with the panel using new lugs and glands of suitable size, separate cable alley for outgoing cables including following switchgear & controls,CPRI approved, complete all as specified and directed
Dismantling and Taking Out old unserviceable LT Panel and Supply, installation, Commissioning and testing LT panel board of size 1500 x 1200 x 300 mm (Approx) for 3 phase, 4 wire, 415 Volts, AC, 50 Hz supply, Outdoor cubical type, dust and vermin proof, pedestal mounting type suitable for Outdoor applications having suitable shape/ size canopy on top, made out of 3.15 mm thick MS sheet with using 40mm x 40mm x 5mm angle iron frame and supports, duly finished with powder coated of approved colour over a coat of red oxide primer all over steel surfaces complete with separate compartment of suitable shape and size with shutter and locking arrangement for each switchgear and including PCC work for fixing panel legs 45 cm above ground level and Bus bar of aluminium conductor suitable shape and size for 3 phase rating of 800 amps and for neutral 600 Amps rating including taking out end connectinons of the existing cables and fixing the cable with the panel using new lugs and glands of suitable size, separate cable alley for outgoing cables including following switchgear & controls complete all as specified and directed.
Disconnecting, taking out and removing old existing unserviceable underground, LT cable of any description and in any position complete including taking down protection pipe,PCC Cover/Bricks etc complete all as specified and directed for the following sizes:
10 Sqmm to 70 Sqmm any core
95 Sqmm to 150 Sqmm any core
185 Sqmm to 300 Sqmm any core
Relaying ony old serviceble cable , jointing and testing any description and any size laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed for the following :-
35Sqmm to 70 Sqmm any core
95 Sqmm to 150 Sqmm any core
185 Sqmm to 300 Sqmm any core
Supply, laying, jointing and testing XLPE/ PVC insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed for the following sizes :-
35 Sqmm 3.5 core
50 Sqmm 3.5 core
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
150 Sqmm 3.5 core
Excavation in trenches in soft/loose soil not exceeding 1.5 metre deep and not exceeding 1.5 metre width and getting out including forming bottom surface to required slope/gradient for laying cables/protection pipes etc including removing cable covers carefully & stacking properly for re-use complete all as speccified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed.
Removal of surplus excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed
M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed. Note:-Punned thickness shall be measurement & paid.
Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed.
Disconnecting & Taking out old unserviceable joints and Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables complete all as specified and directed.
10 Sqmm to 16 Sqmm 2 core
25 Sqmm to 50 Sqmm 3½ core
70 Sqmm to 120 Sqmm 3½ core
150 Sqmm to 185 Sqmm 3½ core
240 Sqmm to 300 Sqmm 3½ core
Supply & fix in repair Busbar chamber 6 way with aluminium busbars for MCCBS upto rating 400 amps for three phase four wire system having separate earth link complete all as specified and directed.
Dismantling & disconnecting connection taking out old unserviceable items and checking the serviceability of different spares / components / parts of security light fittings (HPSV, HPMV, Metal Halide fittings etc, any wattage/capacity) of any description and in any position, replacement of un-serviceable/damaged/ broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position, cleaning acrylic/glass cover connecting to electric supply and its testing on installation etc and taking out the old existing LED street light fitting / security light fitting / Flood light fitting and electric connections by removing carbon ,cut cable connection and re connect after repair of any description and in any position from poles / walls / pillars etc. complete and unserviceable LED street light depositing in MES storeyard and collect any type street light and fixing all as directed by Engineer-in-Charge complete all as specified and directed .
NOTES FOR SCH `A’ ITEM NO 66 :- (i) Fixing charges for Spare Parts of the new & old replaced part(s) is deemed to be included in the rates quoted by the contractor for above item and cost of new parts shall be measured and paid separately as supply only against respect items of BOQ. (ii) Necessary T&P i.e. ladder, tools,Vehicles etc required for checking and making the light fittings in serviceable conditions, its fixing in position and testing shall be arranged by the contractor at his own cost for checking and fixing of street light fittings/security light fittings of any description on poles / on walls / on pillars etc i.e. in any position at site. (iii) Contractor’s quoted rates for BOQ item No 66 is deemed to included for inspection/checking the serviceability of the fittings in position or by taking down as per site requirement, removing the damaged unserviceable / broken parts, fixing the new parts as required, fixing the fittings in same position or the other, connecting the fittings with electric source and testing of fittings as directed. (iv) The contractor or his representative shall daily report to JE E/M and receive the complaints and job card of U/S street lights on each working day and details his electirician for repair/rectification and make the street lights in serviceable condition. .
Supply only for replacement of Old unserviceable eixting following parts for HPSV/ LED light fittings complete all as specified and directed:-
Supply only HPSV Tubular Clear Lamp (SON LUX-T),70 SON-T Watts
Supply only HPSV Tubular Clear Lamp (SON LUX-T),150 SON-T Watts
Supply only HPSV Tubular Clear Lamp (SON LUX-T),250 SON-T Watts
Supply only Ballast (Choke) , 70 Watts,SON/MH open construction heavy duty VPIT copper wound
Supply only Ballast (Choke) for HPSV fittings, 150 Watts,SON/MH open construction heavy duty VPIT copper wound
Supply only Choke for HPSV fittings, 250 Watts,SV/MH Sleek open construction heavy duty VPIT copper wound
Supply only Electronic igniter suitable for 70/150/250/400W HPSV/Metal Halide fittings
Supply only porcelain holder’s screw or pin type for 70 Watt fittings for any type and any description
Supply only porcelain holders screw or pin type for 150/250/400 Watt fittings for any type
Supply only Driver 45 W of existing
Supply only Driver 60 W of existing
Supply only Driver 90/100 W of existing
S&F in repair energy saving, IP66 environmental friendly, long life, exclusive innovative die-cast aluminium flood light with high power LEDs as light source,.120 W suitable for highlighting architectural facade high mast and general purpose lighting . including cable 1. sqmm 3 core copper conductor and PVC conduit pipe 15 mm bore heavy duty ISI marked duly claimed with pole at 2 place complete all as specified and directed from light fitting to over head line.
S&F in replacement of old unserviceable eixting Light Fitting and new Energy saving, environmental friendly, long life , Exclusive innovative die -cast aluminium IP65 street light luminaire with high power LED as light source 90 W LED 6000K with1 sqmm 3 core copper conductor cable and PVC conduit pipe 15 mm bore heavy duty ISI marked duly clamped with pole at 2 place from light fitting to over head line in replacement with existing HPSV /MH light fittings of wattage any type any description make complete all specified and directed.
S&F in repair New generation energy saving and environmental friendly long life LED Street Light made up of pressor die cast aluminium housing with high power LED as 60W lighting source and lens embedded PC cover having Top opening separate driver compartment with IP 66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device.60W LED including cable 1.5 sqmm 3 core copper conductor and PVC conduit pipe 15 mm bore heavy duty ISI marked duly clamped with pole at 2 place complete all as specified and directed from light fitting to over head line.
S&F in repair new Automatic street light Control Switch with INFRARED SENSOR based NATURE switch & voltage monitoring System (VMS) on light iux ievel.suitable power Contactor,MCB and support Termite should be enclosed in pole/wall mountable enclosure made of Rust proof, Electric shock proof, Termite proof and Termite proof and FR grade special moulding compound (Sintex make SMC junction box ) conforming to IP54. The contactors, MCBs and circuit wiring should suitable enough to take load of 25 kw equally distribution over Three phase 415 Volts A/C complete all as specified and directed.
S&F in repair new generation, Post-top energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as Light source, 20W,RUBY (CLEAR)- IP 65 protection including cable 1.5 sqmm 3 core copper conductor and PVC conduit pipe 15 mm bore heavy duty ISI marked, complete all as specified and directed.
S&F in repair, MCB TPN, 63 Amps (`C’ series) having current rating 10 KA complete all as specified and directed.
S&F in repair MCCB 125 Amps , 4 pole, 415 volt AC supply, having breaking capacity 16 KA with adjustable load setting including sheet metal enclosure for MCCB Complete all as specified and directed.
S&F in repair new PVC insulated sheathed stranded Aluminium conductor cable twin core 4 Sqmm size for connecting from Over head conductor to street light fittings with connector etc complete all as specified and directed.
S&F in repair new PVC insulated sheathed stranded Aluminium conductor cable twin core 6 Sqmm size for connecting from Over head conductor to street light fittings with connector etc complete all as specified and directed.
Disconnecting and taking out existing MS boxes of any description and in any position on poles or fixed in the plinth of poles and supplying and fixing in position new PVC (Synthetic ) boxes of size 280mm X 170mm X 115mm depth, made out with Synthetic. The box shall be provided with and including 10 cm long aluminium bus bar of size 20x3 mm size 2 Nos mounted on porcelain insulators including one No. MCB SP of ‘C’ series, 5/6 Amps and connecting the bus bars to cables with using suitable GI nut, bolts and washers and aluminium lugs etc fixed on pole using 30x5 mm FI clamps, nuts, bolts & washers etc complete all as specified and directed. Note :- The contractors quoted rates for the above items are deemed to include for fixing the Synthetic box in position with suitable MS clamps and/or necessary PCC as per site requirement.
Supplying ,Laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminium conductor cable 25 Sqmm 2 core 1100 volts grade, laid in trenches/ducts, floors, fixed to pole/ walls etc. including taking down complete all as specified and directed.
All as per ser item No. 78.00 above but 16 Sqmm 2 core.
All as per ser item No. 78.00 above but 10 Sqmm 2 core.
Disconnecting & Taking out old unserviceable joints and Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for 10 Sqmm to 16 Sqmm any core complete all as specified and directed.
Disconnecting existing LT over heated or burnt cable terminal Joint for LT aluminium conductor cable of size 10 to 25 Sqmm of any core at existing panel/ board/feeder pillar box /overhead lines etc., cutting out over heated / burnt / unserviceable end portion of cable, stretching / opening cable to suitable required length from available rings etc and fixing and connecting the cable in position properly by providing suitable new aluminium lugs and suitable GI nuts, bolts & washers etc complete all as specified and directed.
All as per ser item No. 82.00 above but LT aluminium conductor cable of size 35 to 70 Sqmm of any core.
Surface excavation over the areas around the poles/feeder pillars boxes/ sub stations not exceeding 15mm depth including cleaning the bushes and vegetation and levelling including removal of surplus soil in soft/hard dense soil complete all as specified and directed
Trimming/cutting of all trees branches and cleaning of buses upto 3.0 mtr distance both side from nearest conductor/Earth Wire at LT overhead line including cleaning of site and depositing of material upto 250 mtr distance complete all as specified and directed
Dismantling & taking down of existing worn out / unserviceable aluminium conductor, steel reinforced (ACSR) of any description /size & in any position from existing LT/HT Poles/Lines complete all as specified and directed
M&L for supply and fixing in replacement of aluminium conductor, steel reinforced (ACSR) of any size/ description on LT poles/lines including stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers,clamps, connections etc including connecting, commissioning and testing complete all as specified and directed
Supply, fixing, connecting & testing and replacement of sheet metal enclosures SPN 4 way DBs for using MCBs / MCB isolators without bus bar with and including one MCB SPN 16 Amp complete all as specified and directed.
Supply, fixing, connecting & testing and replacement of sheet metal enclosures SPN 2 way DBs for using MCBs / MCB isolators without bus bar with and including one MCB SPN 16 Amp complete all as specified and directed.
S&F MCB single pole & Neutral 63 Amps, 10 KA ,240 Volts complete all as specified and directed
S&F MCB single pole 6 to 32 Amps, 10 KA , 240 Volts complete all as specified and directed
Dimantling old unserviceable cross arms and Supply, fabrication and fixing for mild steel such as cross arms, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts & bolts, washers of any description of LT over head line poles/ street light poles complete all as specified and directed
Supply and erecting steel tubular swaged pole (410 SP-31) 09 mtr long, complete with cast iron base plate, pole cap/final taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including painting complete all as specified and directed. Note - PCC & earthwork required shall be measured & paid separately
M&L for cement concrete 1:3:6 type C-2 (using 40 mm graded stone aggregates) as in sub base foundation etc complete all as specified and directed.
M&L for cement concrete 1:2:4 type B-1 (using 20 mm graded stone aggregates) for coping of poles with all necessary form work complete all as specified and directed.
Dismantling & disconnecting connection taking out old unserviceable items and checking the serviceability of different spares / components / parts of High mast light fittings (HPSV, HPMV, Metal Halide fittings etc, any wattage/capacity) of any description and in any position, replacement of un-serviceable/damaged/ broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position, cleaning acrylic/glass cover connecting to electric supply and its testing on installation etc complete all as specified and directed
M/s Mahesh Engineering Works
Mukesh Enterprises
M/s Anupam Construction Co.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .