Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.9 LAccepted-AOC 441 G F LIG FLATS PH 2 SEC 14 PKT 3 DWARKA NEW DELHI SECTOR 14 DWARKA DWARKA SOUTH WEST DELHI DELHI 110078 | SOUTH WEST DELHI | DELHI | 110078 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹38.4 L+₹3.6 L (10.3%)Rejected-Finance LODHI NAGAR NEAR TEACHERS COLONY GALI NO 4 MAHOLI ROAD MATHURA U P 281004 | MATHURA | MATHURA | UTTAR PRADESH | 281004 | L2 | Rejected-Finance L2 | |
| 3 | L3₹40.5 L+₹5.7 L (16.3%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹43.9 L+₹9.1 L (26.0%)Rejected-Finance | L4 | Rejected-Finance L4 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
22 Mar 2025, 6:00 pmClosed
GE E/M RR HOSPITAL DELHI CANTT-10
GE E/M RR HOSPITAL DELHI CANTT-10
CA No. GE/H-51/2024-25 NAME OF WORK REPAIR/REPLACEMENT OF LT PANEL FEEDER PILLARS DISTRIBUTION BOARDS AND ALLIED WKS AT AHRR UNDER GE E/M RR HOSPITAL DELHI CANTT-10
2024_MES_677412_3
GE/H-51/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M RR HOSPITAL
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE E/M RR HOSPITAL
₹90,000
Yes
3 Apr 2025
1 Mar 2025
24 Mar 2025
1 Mar 2025
22 Mar 2025
8 Mar 2025
Amount
Taking LT supply shutdown, disconnecting all electrical connection, taking down existing old / unservicable LT panel from its position incl all accessories and demolishing old plateform complete all as specified and directed. Note: Contractor shall be responsible for alternate arrangment of LT Supply with suitable capacity of LT cables if uninterrupted power supply is required as and when directed by Engr-in-charge. No extra cost will be paid to the contractor on this account.
Note for Srl item No 2 to 8 :- (i) The LT panel should be CPRI Test approved and drawing shall approved by GE before manufacturing of the same. (ii) The LT Panel manufacturer will stand warranty of 02 years for complete design, supply and inspection upto site service support. (iii) All live accessible parts shall be shrouded with 1mm thick polycarbonate / 3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used. (iv) All indication lamps shall be LED type. (v) 6A SP C Curve type MCBs shall be used as backup protections. (vi) All Incomer MCCBs shall be variable plug setting type with thermal magnetic up to 400 A rating and with microprocessor based releases above 400 A rating, line load reversibility, Ics = 100% Icu, & rotary handle. (vii) All Outgoing MCCBs shall be variable plug setting type with thermal magnetic line load reversibility, Ics = 100% Icu, & rotary handle. (viii) All MCCB shall be provided with Rotary handle, door interlocked and lockable in OFF position. (ix) All breaking Capacity for MCCB to be Ics=100%Icu and Icw for 1 sec. (x) Power cable entry from the top & Earth bus shall be part of the panel. (xi) All ammeter and Voltmeter should be programmable digital type.
S&F tap off box enclosure metal body type with provision of interlock to prevent removal when outgoing device is in ‘ON’ position and with provision of interlock to prevent turned 'ON' MCCB When the tap-off unit cover is ‘OPEN’, suitable for vertical aluminium busbar trunking upto capacity 800 Amps, 3 phase, 4 wire including suitable neutral link & glands and MCCB of ratings from 400 Amps, 4 pole, 36 kA, Ics=Icu Thermal magnetic release type complete must be compatible with existing BBT system complete all as per site requirement & as directed by Engr In Charge.
S&F tap off box enclosure metal body type with provision of interlock to prevent removal when outgoing device is in ‘ON’ position and with provision of interlock to prevent turned 'ON' MCCB When the tap-off unit cover is ‘OPEN’, suitable for vertical aluminium busbar trunking upto capacity 800 Amps, 3 phase, 4 wire including suitable neutral link & glands and MCCB of ratings from 250 Amps, 4 pole, 36 kA, Ics=Icu Thermal magnetic release type complete must be compatible with existing BBT system complete all as per site requirement & as directed by Engr In Charge.
M&L for laying, jointing and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm x 3.5 Core in trench/ on pole/ in duct complete all as specified and directed. Note:- 1. The cost of required thimbles / clamps / fastner and cable gland etc is included in quoted rate and no extra payment will be made for it.
All as per srl item No 11 here-in-before but 300 sqmm x 3.5 Core.
M&L in replacement of plate earthing complete with galvanized mild steel plate electrode 60cm x 60cm x 6.0 mm thick buried directly in ground vertically (in earth pit not less than 2.25m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5m below norm al ground level, the earth electrode surrounded by adequate quantity of clear coal dust and salt to a packed thickness of 15cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and revetted to earth plate at one end and connected to metallic bodies of equipments etc, GI earth strip encased in and including 40 mm bore GI medium grade pipe with all fittings from upper edges of earth plate to body of equipment fixed with and including 32 x 6 mm flat iron clamps,bolts, nuts and washer and also including providing 20 mm bore GI pipe medium grade from bottom of earth plate to ground level for watering complete with earth pit in PCC 1:2:4 type B-O using 12mm graded crushed stone aggregate and RCC cover, funnel, wire mesh including necessary excavation & earth work, etc as shown on electrical plate No 3 of SSR Part I complete all as specified and directed. Note: (i) Rate included for Adequate quantity of charcoal dust, common salt and Testing commissioning including checking of earth continuity and earth result complete all as specified and as directed. (ii) Rates for Main earthing lead from earth electrode to test point upto 7.5 metre will deemed to be included in quoted rates. (iii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
M & L for 32x6mm galvanised iron strip as Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required & complete as specified.
ISHWAR ENTERPRISES (BID ID -3268489)
PRASAD ENTERPRISE (BID ID -3268074)
JS ENGINEERING ENTERPRISES (BID ID -3267906)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .