| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.3 LAccepted-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹47.3 L Quoted ₹47.4 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹49.8 LRejected-Finance 37 222 BUNDU KATRA AGRA UP | AGRA | UP | ₹49.8 L | L2 | Rejected-Finance OTHER THAN LOWEST |
| 3 | L3₹49.8 LRejected-Finance | ₹49.8 L | L3 | Rejected-Finance OTHER THAN LOWEST |
| 4 | L4₹52.4 LRejected-Finance | ₹52.4 L | L4 | Rejected-Finance OTHER THAN LOWEST |
| Sl No | Description | Qty | Unit | M/S JPS Electrical Engineer & Contractor L4 | PD GUPTA AND COMPANY L2 | shyam construction L3 | Vijay Electricals L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply ,install,commissioning and testing totally enclosed (silent operation with canopy,CPCB-IV compliant ),static type Diesel Engine driven,liquid cooled, Generating set of 58.5 KVA capacity with AMF Panel accommodated within accoustic enclosure (at 0.8 lagging P.F) , 415V, 50 Hz, 3 Phase system & for 0.85 Load factor complete all as specified. | 1 | Each | 10,49,009 ₹10.5 L | 12,80,000 ₹12.8 L | 11,60,000 ₹11.6 L | 11,40,000 ₹11.4 L |
| 1.01(a) Diesel Engine :- Diesel Engine shall be 4 stroke liquid cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at ambient temprature of 50°C ,50% RH & at 1000m above MSL, turbo charged, electronic governor, conforms to BS:5514/ISO 3046, BS 649, IS 10000 with capacity of 10% overload for one hour in every 12 Hours of contineous operation. The engine shall have noise limit of 75 dB(A) at 1 metre (or complied with CPCB and Environmental norms as notified by GoI time to time), Emission limit ( NOx + THC or NOx + NMHC or RHC <= 4.0 g/kW-hr, CO <= 3.5 g/kW-hr , PM <=0.2 g/kW-hr and Smoke limit <=0.7 m¯¹ as applicable to diesel engine) notified by Min of Env vide GSR 281(E) dt 07 Mar 2016(and amendment thereof ,if any). The OEM shall undertake Type approval and conformity of production certificate for emission standard for engine from agencies approved by GoI. Copy of the same shall be produced. The engine shall be engraved clearly as DIESEL on the cylinder block and a conformance label meeting the following requirement shall be affixed :- (a) Name and address of manufactuter of engine (b) Statement that the engine or product conforms to Env(Protection) Rules, 1986 (c) Type approval certificate number (d) Date of manufacture of engine (e) Rated speed and corresponding gross power in kW. The follwing accessories shall be as under :- | |||||||
| 1.02(a1) Air Intake System (i) Air intake manifold. (ii) Dry type air cleaner | |||||||
| 1.03(a2) Exhaust System (i) Turbocharger (ii) Dry exhaust manifold with Residential silencer and catalytic converter | |||||||
| 1.04(a3) Cooling system (i) Engine water pump (ii) Radiator with Fan (iii) Coolant additive concentrate | |||||||
| 1.05(a4) Lubricating system (i) Oil pan (ii) Engine mounted lube oil pump (iii) Lube oil filter | |||||||
| 1.06(a5) Starting System (i)12/24 v DC Starter Motor, Voltage regultors (ii)12/24v DC Alternator for Battery charging (iii) 12V suitable maintenance free battery of suitable numbers | |||||||
| 1.07(a6) Engine mounted microprocessor based (preferably) Instrument panel with digital display for the following :- (i) LED indicating lamps - for Genset running, remote start, shutdown, warning , manual, auto and stop (ii) Data Logs - engine run time and controller on time (iii) Start/Stop switch with Key (iv) Indication/Display of - for water temp, lub oil pressure, Lub oil temp, Battery charging, RPM, Over speed, Low lub oil trip , Engine hours. (v) Engine and alternator Data - staring battery voltage, Engine running Hrs, Engine temp, Engine oil pressure, Alternator voltage, current, KVA, frequency, KWH shall be displayed | |||||||
| 1.08(b) Protection to Genset (i) Low lube oil pressure warning/shutdown (ii) High engine temp warning/shutdown (iii) Low coolant temp warning (iv)Sensor failure indication (v)Low/High battery voltage warning (vi)Weak battery warning (vii)Fail to start shutdown (viii)Cranking lockout (ix)High/Low AC Voltage shutdown (x) Under/Over frequency shutdown (xi)Loss of sencing volatge shutdown | |||||||
| 1.09(c) Others (i) AVM Pads (ii) First fill of lubricanting oils (iii) Flywheel with housing (iv) Residential silencer | |||||||
Updated dates
Tender Value
₹49.8 L
EMD Value
₹99,660
Closing Date
20 Nov 2025, 6:50 pmClosed
GE Bharatpur
GE Bharatpur
PROVN OF STAND BY DG SET INCLUDING WIRING ARRANGEMENT FOR SEC HOSP PROVN OF HEAVY DUTY EXHAUST FANS FOR SINGLE LIVING ACCN SPL REPAIRS REPLACEMENT OF UNSV STREET LIGHTS INTO SOLAR STREET LIGHT FROM ESH No 78 TO ESH No 85 AND BETWEEN SMIRCH AND PINAKA
2025_MES_732562_2
8532/E8
Open Tender
Civil Works
180 days
GE Bharatpur
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE Bharatpur
₹99,660
Yes
23 Dec 2025
31 Oct 2025
22 Nov 2025
31 Oct 2025
20 Nov 2025
6 Nov 2025
1 Nov 2025 - 5 Nov 2025
Amount
Supply ,install,commissioning and testing totally enclosed (silent operation with canopy,CPCB-IV compliant ),static type Diesel Engine driven,liquid cooled, Generating set of 58.5 KVA capacity with AMF Panel accommodated within accoustic enclosure (at 0.8 lagging P.F) , 415V, 50 Hz, 3 Phase system & for 0.85 Load factor complete all as specified.
(a) Diesel Engine :- Diesel Engine shall be 4 stroke liquid cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at ambient temprature of 50°C ,50% RH & at 1000m above MSL, turbo charged, electronic governor, conforms to BS:5514/ISO 3046, BS 649, IS 10000 with capacity of 10% overload for one hour in every 12 Hours of contineous operation. The engine shall have noise limit of 75 dB(A) at 1 metre (or complied with CPCB and Environmental norms as notified by GoI time to time), Emission limit ( NOx + THC or NOx + NMHC or RHC <= 4.0 g/kW-hr, CO <= 3.5 g/kW-hr , PM <=0.2 g/kW-hr and Smoke limit <=0.7 m¯¹ as applicable to diesel engine) notified by Min of Env vide GSR 281(E) dt 07 Mar 2016(and amendment thereof ,if any). The OEM shall undertake Type approval and conformity of production certificate for emission standard for engine from agencies approved by GoI. Copy of the same shall be produced. The engine shall be engraved clearly as DIESEL on the cylinder block and a conformance label meeting the following requirement shall be affixed :- (a) Name and address of manufactuter of engine (b) Statement that the engine or product conforms to Env(Protection) Rules, 1986 (c) Type approval certificate number (d) Date of manufacture of engine (e) Rated speed and corresponding gross power in kW. The follwing accessories shall be as under :-
(a1) Air Intake System (i) Air intake manifold. (ii) Dry type air cleaner
(a2) Exhaust System (i) Turbocharger (ii) Dry exhaust manifold with Residential silencer and catalytic converter
(a3) Cooling system (i) Engine water pump (ii) Radiator with Fan (iii) Coolant additive concentrate
(a4) Lubricating system (i) Oil pan (ii) Engine mounted lube oil pump (iii) Lube oil filter
(a5) Starting System (i)12/24 v DC Starter Motor, Voltage regultors (ii)12/24v DC Alternator for Battery charging (iii) 12V suitable maintenance free battery of suitable numbers
(a6) Engine mounted microprocessor based (preferably) Instrument panel with digital display for the following :- (i) LED indicating lamps - for Genset running, remote start, shutdown, warning , manual, auto and stop (ii) Data Logs - engine run time and controller on time (iii) Start/Stop switch with Key (iv) Indication/Display of - for water temp, lub oil pressure, Lub oil temp, Battery charging, RPM, Over speed, Low lub oil trip , Engine hours. (v) Engine and alternator Data - staring battery voltage, Engine running Hrs, Engine temp, Engine oil pressure, Alternator voltage, current, KVA, frequency, KWH shall be displayed
(b) Protection to Genset (i) Low lube oil pressure warning/shutdown (ii) High engine temp warning/shutdown (iii) Low coolant temp warning (iv)Sensor failure indication (v)Low/High battery voltage warning (vi)Weak battery warning (vii)Fail to start shutdown (viii)Cranking lockout (ix)High/Low AC Voltage shutdown (x) Under/Over frequency shutdown (xi)Loss of sencing volatge shutdown
(c) Others (i) AVM Pads (ii) First fill of lubricanting oils (iii) Flywheel with housing (iv) Residential silencer
(d) Alternator - Synchronous alternator copper wounded rated 58.5KVA, 415 Volts, 1500 RPM, 3 Phase , 50 Hz, AC Supply with 0.8 lagging power factor at 50 degree c, 50% RH and at 1000 m MSL, brushless type, self exicited, SPDP encl, contineous duty, sel regulated through AVR conforming to IS:4722 with Class F/H insulation. The salient feature are as under : (a) Permanent lubricating bearing (b) Permissible overloading of 10% for one hour in every 12 hrs of contineous operation (c) Permissible unbalancing capability minimum 25% per phase
(e) ACCOUSTIC ENCLOSURE FOR DG SET :- Supply and fixing accustic enclosures suitable for 58.5 KVA capacity diesel Generator set duly fabricated of channel and CRCA sheet 16SWG of required size having doors , insulation sides and top by minral rock wool confirming to IS-8183 of adequate thickness accoustic louvers /outlet. ventilation system etc . complete as per manufacturers instructions with wiring and lighting arrangements duly painted of three coats of dulux gloss synthetic enamalled paint over a primer coat or as directed of suitable size all as required at site and comprising of the following :-
(i) Base: MS channel fabricate MS channel made out of 5 mm thick MS sheet of ISMC suitable section . (ii) Structure heavy duty rectangular MS box channel . (iii) Doors fabricated from MS CRCA 2 mm thick air tight with neoprene rubber gasket and gun metal heavy duty spring loaded locks . (iv) Out side cover: Made out of CRCA sheet 2 mm thick. (v)Accustic insulation ( side &Top ) sound proofing minerla rock wool slab thickness 100mm of density 96Kg/m3 confirming to IS 8183 , covered by fire Resistant fiber tissue as per manufacturer recommandation .Test report from original manufacturer to be submitted before incorporation in the work for authenticity of material . (vi) Inside cover : CRCA perforated sheet 0.6mm thick powder coated (vii) Inspection port : Aluminium frame with double walled glass fixed type sealed with neoprene rubber gasket for viewing instrument panel (viii) Sheet metal shall be eleven tank pretreated and powder coated.
(f) AMF CONTROL PANEL:- As per manufacturer's design with the following options: (a) Start/ stop settings including delay and timing setting duly programmable. (b) programmable timing for idle running . (c) Auto/ manual option. (d) Self starting kiks for three times or as per programme . (e) Alarm for any fault with buzzer and indicating lamp . (f) One main supply voltage monitor . (g) One alternator supply voltage monitor . (h) One set of DC control relays and timers. (j) One set of control relays for the automatic control system .
(g) FOUNDATION:- RCC Fuoundation M 20 ( or as per manufacturer design) ,250 mm overall height, 100mm above floor level and 150 mm below floor level of required size. (Make of Engine :-Cummins/Kirloskar oil engine/ /Greaves Cotton/Perkins/Caterpillar (FGW) (Make of Alternator :Kirloskar electric/Stamford/Jyoti/BHEL/CROMPTON GREAVES
(h) Acoustic Louvers / Attenuators at Air inlet/outlet :-The acoustic louvers provides excellent sound attenuation and good weather protection. Single blade and chevron blade louvers are manufacturefrom 16 SWG CRCA sheet top section with an acoustic in fill of resin bonded mineral rock wool has a density of 96 Kg/m3 .The under section is formed from 18 SWG CRCA performed sheet after covering with resistance tissues to prevent fire migration or by means of acoustic lined ducts. Make:- Jackson/Greaves Power/Cummins/KIRLOSKAR GREEN
(j) FUEL TANK :- One No of sheet metal steel tank made out of 3.0 mm thick MS sheet of suitable capacity of hold diesel sufficient for 12 hours running at full load, tank shall be fitted with in canopy as per manufacturer's design including the following:- (i) Level indicator to indicate level of diesel in tank. (ii) Drain plug with 2.0 mtrs pipe for drain oil. (iii) fuel strainer. (iv) Pipe for fuel. (v) Air vent. (vi) Mannually operated one no. fuel pump.
(k) INSPECTION PORT :- Aluminium box frame with double welded glass fix type sealed with EPDM/neoprene rubber gasket, for viewing instrument panel. NOTE :- (a) Generating set will be placed on suitable foundation as recommended by manufacturer and cost thereof shall be included on the prices quoted . (b)Tools shall be supplied as per manufacturer,s instructions and cost thereof shall be included in the price quoted . (c) DG Set shall be placed at the site directed by Eng-in-charge which can be upto 20 meter from the road. (d) Testing of DG set shall be done as per relivant clause of PS.
Supply and lay XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade (earthed) cross sectional area 120 Sqmm, 3.5 core incl suitable size of lugs for connection in LT Panel complete all as specified. Note : The earth work, GI pipe & Clamp for suitable size to hold the cable on wall shall be measured and paid separately under respective item of Sch A
All as per Item No 2 above but Cable of size 70 Sqmm 3.5 Core complete all as specified.
Excavation in trenches in soft/loose soil not exc 1.5mtr wide and not exc. 1.5mtr depth for laying of UG Cable/foundation etc complete all as specified.
Returning filling in soft/loose soil including spreading levelling watering and well ramming in layers n exc 25cm each layer complte all as specified.
Removal of excavated surplus soft/loose soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified.
M&L for sand cushioning for under ground cable with layer of fine river dry sand 80 mm thick before laying of cable and 150 mm thick after laying of cable in trenches complete all as specified. Note:- Punned thicness of sand will be measured and paid.
M&L for cable protection bricks common burnt clay sub class B bricks for protectioon of UG Cable laid in trenches complete all as specified.
M&L for 80 mm bore GI tube light grade laid under road/culvert/drain fixed to pole wall with help of flat iron clamps etc for cable protection and making good surface of road with PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) complete all as specified.
M&L for 50 mm bore GI tube light grade laid under road/culvert/drain fixed to pole wall with help of flat iron clamps etc for cable protection and making good surface of road with PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) complete all as specified.
Material and labour for design ,supply, fabrication, Installation, testing and commissoning Factory made LT panel at outdoor type totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz AC supply system, fully compartmentalized, both side openable, made out of 3 mm thick CRCA sheet, protection of enclousure IP-54 as per IS: 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size(minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following complete all as specified.
Busbar Chamber: -Electrically grade shrouded copper bus bar of capacity 250 Amps for each phase and 125 Amps for neutral and current density 0.8A/Sqmm , including interconnection of all switch gears, fixed on DMC insulators and provision of extension.
(Outgoing) Consist of separate compartment for each MCCB.- (a) MCCB 63 Amp, 415 Volts, 04 Pole 50Hz, 25/30 KA with adjustable thermal magnetic release in built instantaneous protection, Ics = 100 % Icu(1 sec) - 03 Nos (01 X Spare). (b) MCB TPN 40Amp - 01 Nos Note :- MCCB/MCB should be mounted vertically in panel
Material & labour for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground. ( earth pit not less than 2.25 mtr depth below ground level at any type of strata ) with top edge of the earth plate not less than 1.5mtr below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all around the plate. connected by 25x4mm GI strip as earth lead by means of brass nuts and bolt,thimbles check nuts, washers including concrete chamber of PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320x320x80mm size (1:2:4) Type B1 using 20mm graded stone aggregate rainforced with XPM all as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified including and provision of GI strip upto 7.5 mtrs long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, medium grade, including all exavation and earth work and connecting the earthing strip to panel, including testing on completion complete all as specified. (DG Set-04 Nos, Lt Panel-01) Note:- (i) RCC pit cover shall be precast of RCC(1:2:4) type B1, 80mm thick rainforced with XPM weighing not less than 4kg/sqm. (ii) Cost of additional GI strip more than 7.5 mtrs will be measured and paid seperately under relevant items.
M&L point wiring complete with 1.5 Sqmm single core multistranded copper conductor of 1100 volts grade PVC pre insulated FRLS and unsheathed cable enclosed in and including PVC casing and caping double locked box type with all PVC accessories such as Tee, bend, collar, elbow, square junction box etc fixedon the surface of wall/ceiling by means of PVCsleeved/dash fastners with cadmium plated screws including suitable size of PVC boards for mounting fittings like switches, sockets, fan regulator etc including 1.5 Sqmm insulated FRLS unsheathed copper earth continuity conductor to common earth and connedcted to earth dolly for fan point complete all as specified.
Supply & fix exhaust fans Steel body AC single phase 230/ 240 V of size 450 mm sweep copper winding heavy duty with louver complete all as specified.
Material and labour for cutting suitable holes in existing masonary wall and fixing suitable size hume pipe for fixing of exhaust fan 450 dia and making good disturbed surfaces with cement mortar (1:4) and finished to match existing surface complete all as specified.
S&F ceiling rose surface bakelite three terminal ISI marked including suitable size of PVC board complete all as specified.
S&F switch piano flush button single pole one way 6 Amps 230 volt grade complete all as specified.
M&L concealed submain wiring complete with 4 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 4 Sqmm copper cable for earth continuity conductor in and including drawn through PVC conduit size not less than 20 mm dia with all PVC accessories. Note: Three runs of 4 sqmm and PVC conduit pipe shall be measured as one length only.
Distribution board factory made and tested made of sheet metal enclosure powder coated suitable for mounting the MCB 415/240 volt of the8 way SPN with 200 amps rated busbar 240 volts (double door type) complete all as specified.
S&F MCCB, MCB with GI hardware fixed in DB's of the undermentioned type and rating.
(a) MCB SP 240 volts 6-32 Amps C Curve
(b) MCB SPN 32 Amps, 240 volt C Curve
Supply and fixing of Lithium base Energy efficient integrated Solar street light of 30 watt in Aluminium Die casting body ,corrosion resistance,built in high efficiency solar panel and long life lithium ferro phosphate battery with high efficiency microprocessor based charge controlar Automatic dusk to input voltage 12.8 V with minimum 30 AH battery capacity ,Driver efficiency .85%,PV module minimum output capacity 60 W/h Mono itself will be used to sense the ambient light to switch ON/OFF the Lamp from outside from Light fittings and controled from Pole controlling switch,inbuilt MPPT charge controller,IP65,both PIR and fixed dimming available,4500 lumens (at full brightness) with grater than 150 lumen per watt,5700ANSI,,CRI.70,moptical used, Metal core PCB,Low voltage cutoff ,high power LED,wide beam Angle(135/85 degree) with PIR Sensor LED Life 50000 hrs (LM80 cerified LED),weight less than 15 kg with Green/Red indicator with with battery rating 12.8V-BIS standard along with 5 year warranty covered ,fixing on PCC Pole including alternate strip of 0.25 metre each with yellow / black (zebra painting)synthetic enamel paint upto 1.5 meter height with dismenttling & taking out old street light along with bracket of complete all as specified. Make : Orient / Havells / Phillips
Supply, install, test and commissioning factory made THERMOPLASTIC/HDPE CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of size 280 x 170 x 105 mm depth each, with flat iron clamps of size 30 x 6mm, nuts and bolts with MCB SP 6 Amp-01 complete all as specified.
S & F in replacement 4 sqmm solid conductor 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed twin core cable flat or circular from junction box to fitting complete all as specified.
S&F 20 mm dia Unplasticised PVC pipes of pressure rating 10 Kgf/cm2 fixed on pole with MS clamps made out 25 x 3 mm thick MS flat with the size of pole , nut, bolt etc complete all as specified.
Supply and fix Voltage stabilizer with digital display for showing input or output voltage for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified.
S&F single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one single pole MCB 20A complete all as specified.
S&F MCB 240V SPN 40A having rupturing capacity 10kA complete all as specified.
S&F MCB 240V SP 16 having rupturing capacity 10kA complete all as specified.
Supply, install,commissioning and testing of commercial Air curtain unit for prevention of dust and conditioned air losses, single phase, 220 V, 50 HZ, made out of MS/CRCA sheet of minimum thickness 18 gauge finished with two coats of red oxide primer and final coat of synthetic enamel paint (oven baked) with MS -CRC 18 gauge square perforated suction grills, Aluminium alloy fans and single phase electric motor, nozzles etc complete with fittings and accessories so as to produce 1 - 1.5 m/sec air velocity at floor level for door opening 34''x78'' complete all as specified.
PD GUPTA AND COMPANY (BID ID -3473221)
shyam construction (BID ID -3478686)
M/S JPS Electrical Engineer & Contractor (BID ID -3469937)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
tender8532.pdf
Tender Documents • 1.76 MB
BOQ_826358.xls
BOQ • 0.77 MB
Download all tender documents and submit your bid