| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.3 LAccepted-AOC EAST DIGHI TANK OLD LIC COMPOUND GAYA BIHAR 823001 | GAYA | BIHAR | 823001 | ₹9.3 L Quoted ₹9.5 L | 1 | Accepted-AOC Being lowest |
| 2 | 2₹13.3 L+₹3.9 L (40.9%)Rejected-Finance WZ 484 M S BLOCK HARI NAGAR NEW DELHI 110064 | NEW DELHI | NEW DELHI | DELHI | 110064 | ₹13.3 L+₹3.9 L (40.9%) | 2 | Rejected-Finance NOT BEING LOWEST. |
| 3 | 3₹14.4 L+₹4.9 L (51.9%)Rejected-Finance | ₹14.4 L+₹4.9 L (51.9%) | 3 | Rejected-Finance NOT BEING LOWEST. |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
25 Jan 2021, 6:00 pmClosed
Garrison Engineer Gaya
Garrison Engineer Gaya Paharpur Mil Stn Gaya Bihar-823001
Day to day maint of internal electrification, fittings and fixtures of Md Accn at Mil Stn Gaya under AGE EM Gaya of GE Gaya
2020_MES_408092_1
8029/GE/E-8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer Gaya Paharpur Mil Stn Gaya Bihar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE GAYA
₹40,000
Yes
2 Mar 2021
30 Dec 2020
26 Jan 2021
30 Dec 2020
25 Jan 2021
12 Jan 2021
Amount
Taking down carefully aluminum point wiring (light/fan/socket power) complete , including fixture and fitting such as switches, ceilling roses, pendants, regulators, socket, light fittings etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per condition seperately) and making good disturbed surfases of walls, floors, etc.
Taking down main switches/DB's alongwith existing board incl removing the same from site and making good to the disturbed surface of walls including two coats of painting to match with existing surface, floor, etc
Taking down existing sub main wiring of any type and description including removal of teak wood batten/pipe etc complete.
Taking down unservesable / Burnt, Under ground/service cable of any type & size.
M&L Point wiring concealed type/surface conduit/casing and caping with 1.5sq mm PVC insulated unsheathed single core multithreaded copper conductor cable 1100 volts grade incl 1.5Sq mm PVC insulated sheathed copper conductor cable as earth continuity conductor drown through in and incl PVC rigid conduit/suface conduit/casing and caping not less than 20mm dia with its accessories pressed steel terminal box made of primer incld 3mm thick ISI marked laminated sheet cover for fixing switches/socket/regulators etc for the following: - make-plaza/polycab/KEI
One light/fan/bell point controlled by one No piano type switch 5 AMPS single pole one way
One socket outlet 5/3 pin 5 AMPS controlled by one switch on the same board.
One socket outlet 5/3 pin 5 AMPS controlled by one switch on independent board.
M&L 3 pin socket outlet point 15 Amps indipendent, with cables of size 2.5 sq mm multistranded, PVC insulated seathed copper conductor cable, and 1.5 sq mm earth continuity conductor in PVC conduit med grade.
S &F Switch Piano Flush button single pole one way 5 Amp
S &F Switch socket comb 2 in 1, 3 Pin 5 Amp flush type ISI Marked .
S &F Switch socket comination multipurpose 2 in 1,5 and 15 Amp Flush type ISI Marked
S &F Lamp hoder insulated body with back plate for batten fittings
S &F Ceiling rose , 3 phase / PVC/ polycarbonate, isolated body.
S&F Socket outlet 3/5 pin 5Amp flush type.
S &F Socket type electronic stepped fan regulator flush type on the existing phenolic laminated sheet etc.
M&L in replacement of modular white cover plate with frame 1/2 module. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular white cover plate with frame 3 module (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular white cover plate with frame 8 module (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular metal flush box for 1/2 module .(Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular metal flush box for 3 module (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular metal flush box for 8 module (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of Modular switch piano type 10 Amps one way single pole 240 volts A.C complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of Modular switch piano type 20 Amps complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of Modular socket outlet 10 Amps 5 pin 240 Volts multi socket for cell phone pin or 2 pin+ 3 pin complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular socket outlet 20 Amps 6 pin 240 Volts twin socket heavy duty complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of modular bell push large piano type single pole one way 240 volts A.C complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of bell ding dong/ bell musical single phase 230 volts all as specified. Make-Anchor/Havells/Bajaj
M&L in replacement of modular type single phase motor starter 240 volt grade up to 25 Amps .(Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of Modular ceiling fan regulator suitable electronic rotary step type 100 Watt 1 module complete all as specified and directed. (Make-Crabtree/legrand/Indo Asian (Glint))
M&L in replacement of AC wiring Concealed/surface wiring with two single core pvc insulated unsheathed FR copper conductor 1100 volt grade multistranded of size 4 sqmm and incl drawn through and including non metalic rigid pvc conduit and couduit accesssories of 20 mm external dia and conduit accessories of ISI marks medium grade including 2.5 sqmm copper wire for earth continuity wire and connected of common earth dolly. Make of Wire :polycab /Havells/ Plaza . Note:- One run of conduit two run of 4 sq mm copper conductor & one run of 2.5 sq mm copper conductor is measured as one unit.
S&F Panel light fitting 18/20 watt LED size 300X300X70, LED fitting ,including LED in warm white/white as directed , 230 volt energy saving , enviromental friendly , long life, corrosion resistant , impact proof, surface mounting IP-65luminaire with PC Housing in opal finish suitable for wet location with britness LEDs with all accessories internally prewired and including connected with twin core twisted flexible wire copper conductor cable with suitable size complete all as specified and directed. Make-Phillips/ Havells/ Syska.
S/F sheet metal enclousure for MCB DB single pole and neutral 8 way with 200 Amps rated bus bar 240 volts double door type. Make-HAVELLS/LEGRAND/Indo Asian
S&F sheet metal enclosure distribution board with hinged cover IP 43 protection metal door epoxy powder coated/made of insulating meterial like, ploystyrene, double door 4 way TPN with suitable rated bus bar for (vertical operation) incorporation of MCCB 4 pole 100 Amps 25 KA complete all as specified and directed.Make-HAVELLS/LEGRAND/Indo Asian Note : MCCB's,MCB's,Isolators shall be measured and paid separately.
S&F MCB SP 5 to 30 Amps 240 volts . Make-HAVELLS/LEGRAND/Indo Asian
S&F MCB SPN capacity 40 to 60 Amps 240 volts all as spfd .Make-HAVELLS/LEGRAND/Indo Asian
S&F MCCB 4 pole, 125 Amps with breaking capacity 16 KA, 415 volts complete all as specified and directed. Make : Havells/ Legrand/Indo Asian
M&L Sub main wiring with two single core pvc insulated of size 6 sqmm unsheathed copper conductor 1100 volt grade multistranded and incl drawn through and including non metalic rigid pvc conduit and couduit accesssories of 25 mm external dia and conduit accessories of ISI marks medium grade including 4.0 sqmm copper wire for earth continuity wire and connected of common earth dolly.make-Plaza/ Polycab/ Havells Note:- One run of conduit two run of 6 Sq mm copper conductor & one run of 4 sq mm copper conductor is measured as one unit.
M&L Earthing complete with galvanized earth plate electrode 600mmx 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below ground level connected to galvenised earth lead wire of 4 mm dia by means of nuts, bolts, washers of galvanized iron or steel all as shown in electrical plate No 5 and testing on completion including adequate charcoal dust comman salt necessary excavation & earth work PCC(1:3:6) type C-1 pit with precast RCC Cover slab 40 mm thick in PCC(1:2:4) type B-0 reinforced with 6 mm dia MS bars @ 100 mm c/c both ways with funnel wire mesh and 20 mm dia GI pipe medium grade as watering pipe complete all as spfd and as directed. connected to earthing pit point all as specified and as directed.
Comprehensive maintenance of internal electrification at zone A area of OTA Gaya for attending day to day complaints such as switch, socket, fan regulator, holder, PVC casing & caping, tube lights etc. all as directed by eng-in -charge .
S&F in replacement of AC single phase static energy meter of accuracy class 1.0, 240V, 50 Hz with Backlit LCD display of rating 10-60A (measures and dispalys KWH, V, Current I, KW, pf last siz month history of KWH, MD in KW) with special features like TOD, temper logging, optical communication port display in absence of power and transperent hinge type box including fixing with wall transparent hinge type acrelic box and proper connection complete all as spfd and directed by Engr-in-Charge. Cat Part No SPPL1521120002ME03 Make-L&T/HPL/Seimens. Notes :- Old u/s Electrical Energy Meters are deposited in MES store yard.
Supply and Fix PVC 20 mm casing N caping of 2 mtrs length. (Make- Plaza/ Jindal/ Modi)
Supply and Fix Batten holder angular type 2 pin. Make- Havells/Anchor and equivalent.
Supply and Fix Switch socket combination 5 Amps complete all as specified and directed. Make: Anchor/ Havells/ Plaza
Supply and Fix 5/6 amp 3 pin plug tops complete all as specified and directed. Make- Havells/Anchor/ Plaza
Supply and Fix 15/16 amp 3 pin plug tops complete all as specified and directed. Make- Havells/Anchor/ Plaza
Supply and Fix Copper conductor stranded FR PVC insulated 1.5 Sqmm Single Core Roll of 90 mtr. Make Polycab/Havells/plaza
Supply and Fix Copper conductor stranded FR PVC insulated 2.5 Sqmm Single Core Roll of 90 mtr. Make Polycab/Havells/plaza
Supply and Fix Copper conductor stranded FR PVC insulated 4 Sqmm Single Core Roll of 90 mtr. Make Polycab/Havells/plaza
Supply and Fix tube in replacement of its existing ballast with LED tube 20 watt (T-8) with aluminium exusion in 'D' shaped having larger diameter and including single core copper solid wire internally all as directed and specified by Engr-in-charge. Product code-HLPT81420 (CW) of HPL or equivalent Havells/ Bajaj Note-Old Ballast and old rod are department property
Supply and Fix ceiling Fan condensor 2.5 MFD
Supply and Fix ceiling Fan condensor 3.15 MFD
Supply and Fix Battery 12 volt 80 AH (MAKE Exide,Amaron)
Supply and Fix Nails (Chinese) 1" (Type 17),1.5",2",2.5",3", Each of 1 Kg as specified and diredted by Engr-in-charge
Supply and Fix Machine Screw 1"(30/7), 1.5"(35/8),3/4" Each 3 Packets as specified and directed by Engr-in-charge
Supply and Fix Twin core Flexible wire 23/0076 Roll of 90 mtrs. Make Polycab/Havells/plaza
Supply and Fix PVC Tape insulation of width 1.8 cm and 7 Mtrs length.Make - Anchor/ SSK
Supply and Fix Copper conductor stranded FR PVC insulated 6 Sqmm Single Core Roll of 90 mtr. Make Polycab/Havells/plaza
Supply and Fix PVC box suitable for 15 Amp/05 Amp Socket Size 7x4
Supply and Fix batten suitable for T8 retofit LED tube 18/ 20 watt with alluminium exusion in 'D' shaped having large diameter all as directed and specified by Engr-in-charge.Make- Havells/ Phillips/ Syska/Crompton
Supply and laying in replacement of service wire 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with tape and overall PVC sheathed 16 Sqmm two core nominal cross section in completed .Make-polycab/Havells/KEI
Supply & laying XLPE insulated, armoured, heavy duty elecric cable with alluminium conductor, 1100 volt grade cross sectional area 25 Sqmm 4 core.Make-polycab/plaza/finolex
Excavation in trenches not exceeding 1.5 mtrs wide & not exceeding 1.5 mtr in depth in soft or loose soil & getting out complete all as spfd & directed.
Returning filling including spreading levelling watering & well Ramming in layers not Exc 25 cm complete all as spfd & directed.
M&L Bricks common burnt sub class B designation for protection of cable complete all as spfd & directed.
M&L Natural local river sand for cable protection.
Removing excavated materialn not exceeding 50 mtr & deposited where direceted at a level not exceeding 1.5 mtr above the ground level.
M&L GI tubing 40 mm dia light grade with all fittings laid in trenches/making GI bracket of security lights/provn for ceiling fan ponit including bending of suitable size/support of UG cable as required at site as directed by Engr-in-Charge.
MS HARI MOHAN GUPTA
M/S MAGADH CONSULTANT
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .