Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.5 LAccepted-AOC | ₹46.5 L Quoted ₹47.2 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹48.0 LRejected-Finance 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | ₹48.0 L | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹49.9 LRejected-Finance H 13 GEETANJALI PARK WEST SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | ₹49.9 L | L3 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | Saini Enterprises L2 | J.P. Enterprises L3 | M/s Salasar Telecom L1 |
|---|---|---|---|---|---|---|
| 1.00Disconnecting worn out LT incoming and out going cable connections from servo voltage stablizers of following capacity after taking shut down from Engr-in-charge and follow all safety precaution, taking out from substation/ power house at various locations under GE (AF) Subroto Park with help of suitable crane and transporting to approved workshop and removing the top plate taking out the plate and worn out part from the tank with help of chain pulley & repairing / servicing / overhauling and replace worn out part complete and back after completion of repair work and installing at original location, reconnecting including testing commissioning complete all as specified and directed. Note-(i) Rewiding of LT coil any type/ material, dehydration of oil will be measured and paid seperately under relevant item of the schedule. (ii) Spare part shall be measured and paid seperately as supply only and cost of fixing and connection of spare shall be deemend to included in the quoted rate of the above items.and reassembled after repair including LT cables connection again and testing, commissioning for smooth functioning. | ||||||
| 1.01 | Servo voltage stablizers upto 100 KVA capacity | 2 | Each Job | 6,000 ₹12,000 | 7,500 ₹15,000 | 24,500 ₹49,000 |
| 1.02 | Servo voltage stablizers 125 KVA to 630 KVA capacity | 3 | Each Job | 8,000 ₹24,000 | 10,000 ₹30,000 | 34,200 ₹1.0 L |
| 2.00Replacement of following unserviceable accessories in the existing. 630 KVA 3 phase servo voltage stablizer inter connection of the same part including testing & commissioning etc as reqd for smooth operation of stablizer | ||||||
| 2.01 | Microprocessor based electronic control card | 3 | Each | 4,000 ₹12,000 | 3,800 ₹11,400 | 26,600 ₹79,800 |
| 2.02 | A.C. synchronous motor 10 Kg | 2 | Each | 3,500 ₹7,000 | 3,800 ₹7,600 | 10,300 ₹20,600 |
| 2.03 | R.C. Net work | 3 | Each | 300 ₹900 | 200 ₹600 | 615 ₹1,845 |
| 2.04 | Carbon Brush | 9 | Each | 250 ₹2,250 | 200 ₹1,800 | 324 ₹2,916 |
| 2.05 | Voltmeter 0-433 volt | 2 | Each | 650 ₹1,300 | 700 ₹1,400 | 1,360 ₹2,720 |
| 2.06 | Ampere Meter | 1 | Each | 800 ₹800 | 900 ₹900 | 1,555 ₹1,555 |
Updated dates
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
6 Dec 2025, 6:00 pmClosed
GE (AF) SUBROTO PARK
GE (AF) Subroto Park, Delhi Cantt Delhi-110010
As described in Bill of quantities
2025_MES_731729_2
GE/SP/TOKEN-43/2025-26
Open Tender
Electrical and Maintenance Works
180 days
GE (AF) SUBROTO PARK
As per NIT and tender documents
9 documents required · 9 mandatory
₹500
GE (AF) SUBROTO PARK
₹96,000
Yes
19 Feb 2026
15 Nov 2025
9 Dec 2025
15 Nov 2025
6 Dec 2025
24 Nov 2025
Amount
Servo voltage stablizers upto 100 KVA capacity
Servo voltage stablizers 125 KVA to 630 KVA capacity
Replacement of following unserviceable accessories in the existing. 630 KVA 3 phase servo voltage stablizer inter connection of the same part including testing & commissioning etc as reqd for smooth operation of stablizer
Microprocessor based electronic control card
A.C. synchronous motor 10 Kg
R.C. Net work
Carbon Brush
Voltmeter 0-433 volt
Ampere Meter
Control Wiring
Small Gear (16 Teeth)
Micro Switch
Dimmer E Point
Variac for 630 KVA Servo Stabilizer
Replacement of following unserviceable accessories in the existing. 300 KVA 3 phase servo voltage Stablizer inter connection of the same part including testing & commissioning etc as reqd for smooth operation of stablizer
Microprocessor based electronic control card
A.C. synchronous motor 10 Kg
R.C. Network
Carbon Brush
Ampere Meter digital type of suitable rating
Control Wiring
Small Gear (16 Teeth)
Micro Switch
Lower / Riser Switch
Dimmer Stopper
Dimmer E Point
Variac for 300 KVA Servo Stabilizer
Replacement of following unserviceable accessories in the existing. 225 KVA 3 phase servo voltage stablizer inter connection of the same part including testing & commissioning etc as reqd for smooth operation of stablizer
Microprocessor based electronic control card
A.C. synchronous motor 10 Kg
Dimmer E Point
Carbon Brush
R.C. Net work
Main Big Gear (162 Teeth)
Control Wiring
Ampere Meter digital type
Voltmeter 0-433 volt Digital type
Micro switch
Replacement of following unserviceable accessories in the existing. 200 KVA 3 phase servo voltage stablizer inter connection of the same part including testing & commissioning etc as reqd for smooth operation of stablizer
Microprocessor based electronic control card
Dimmer E Point
A.C. synchronous motor 10 Kg
R.C. Network
Main Big Gear (162 Teeth)
Small Gear (16 Teeth)
Replacement of following damaged accessories in the 150 KVA existing phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Control transformer
A.C. synchronous motor 10 Kg
R.C. Network
Carbon Brush
Dimmer E Point
Replacement of following damaged accessories in the 100 KVA existing phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Dimmer E Point
A.C. synchronous motor 10 Kg
R.C. Network
Carbon Brush
Replacement of following damaged accessories in the 75 KVA exisitng phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Control transformer
A.C. synchronous motor 10 Kg
R.C. Network
Control Wiring
Carbon Brush
Dimmer E Point
Replacement of following damaged accessories in the 30 KVA existing phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Control transformer
A.C. synchronous motor 3 Kg
R.C. Network
Voltmeter digital type 0-433 volt
Multifunction Meter
Control Wiring
Carbon Brush
Dimmer E Point
Variac for 30 KVA Servo stablizer
Replacement of following damaged accessories in the 20 KVA existing phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Control transformer
A.C. synchronous motor 3 Kg
R.C. Network
Carbon Brush
Replacement of following damaged accessories in the 7.7 KVA existing phase servo voltage stablizer inter connection of the same part including Testing & commissioning etc as required for smooth operation of stablizer
Microprocessor based electronic control card
Control transformer
A.C. synchronous motor 3 Kg
R.C. Network
Carbon Brush
Control Wiring
M& L for Dehydration/ Filtration of the transformer oil of automatic voltage regulator & servo voltage stablizer by pass switch with the help of dehydration machine at site to 50 KV dielectric strength etc. complete all as specified and directed
Supply & Filling in replacement transformer Oil (ISI mark) having Die Electric strength not less then 40KV on 4 mm Gap in the existing phase voltage stabilzer complete all as specified and directed
Design, supply, install, testing and commissioning in replacement of factory made LT Panel Indoor type cubical enclosure compartmentalized external and internal mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc.The enclosure shall be made of 2.00 mm thick stainless steel sheet SS 316 sheet. The fixing of double doors shall be on SS hinges with anti-theft provision. All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 316. Sliding handle and locking arrangement front and rear both side. Enclosure shall be suitable for AC supply system 415 volts, 3 phase, 4 wire, 50 Hz. Degree of protection shall be IP-54. The enclosure shall have provision of cable entry. Cable entry from bottom side including internal wiring with PVC insulated solid, copper wire, 1100 volts grade. The panel shall consist of 1200 Amps rating TPN aluminium bus bars and shall be provided with colour coded heat shrinkable sleeves. The panel shall be provided with separate compartments for each switch gear, including instrumentation such as Multi Function meter, phase indicating lamps etc with double stud hinged door, front & rear openable with locking arrangement including interlocking with switch gears and suitable for 1100 Volts grade, 3 Phase, 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10KA. The panel shall be fixed with angle iron frame made of angles of size 50mm X 50mm X 6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B-1 (using 20mm graded stone aggregate), 600 mm above ground level and comprising the following: Incoming:- (a) ACB 800 Amps 4 Pole, 50 kA, 50Hz at 440 Volts with Microprocessor based release Manual drawout type ( MDO ) with overload, Short circuit, instanteneous Protection including neccessary bus bar for connection incoming cables complete- 1 set (b) Digital Multifunction Meter to measure KWh, PF, VLL, VLN, W, VA ,V, I including CT and PT complete with all electrical connection - 01 No (c) LED type Phase indicator lamps (R, Y, B) - 1 Set Outgoings:- (a) MCCB 500 Amps 4 pole rupturing capacity 36 KA at 415 volt, with RHOM and Ics = 100% Icu - 01 Nos (b) MCCB 400Amp,4 pole rupturing capacity 36 KA at 415 volt, with RHOM andIcs = 100% Icu - 01 Nos (c) MCCB 200 Amp,4 pole rupturing capacity 25 KA at 415 volt, with RHOM and Ics = 100% Icu - 03 Nos (d) Control MCB 6 Amps SP-03 Nos Note for item No 14 : (i) Rates are inclusive for fixing of suitable size cable gland if required in existing or new cable, CT/ PT and elctrcal connection complete to function multi functional meter. (ii) Danger notice plate must be fixed on panel . (iii) The manufacturer should have Govt. approved certificates:- (a) Panel should be according to IEC-61439, CPRI certificate Degree of protection IP-54. (b) IS/ IEC : 61439 (Part-I & Part-II) 2011 and all necessary certification as per relevant IS/IEC codes
Supply, laying, jointing and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strips armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminum conductor of size 300 sq mm 3.5 core with necessary cable glands at end, aluminium lugs for connector including taking out of old cable complete all as specified and directed.
Material and labour as in repair for Design, development, supply, testing & commissioning of EHCC certified ground tubular effective Tripod type chemical earthing system ( CPRI tested for 15 KA current capacity for LT line) highly anti-corrosive, long life electrode with and including adequate protective coating to withstand severe wear conditions in the earth pit of the standard size comprising of 50mmx6mmx200mm earthing electrode strip both side 2 nos, qty 3 nos strip size 25mmx3mmx3000mm both side 2 nos and primary conductor and hollow Copper coated tube of dia 76mm x 3mtrs long as secondary conductor to install with suitable connection terminal conforming of IS 3043:1987 (latest revised) specifications, highly conductive packing material to be filled in earth pits for providing uniform, low resistivity anticorrosive, hygroscopic medium around the earth system for improving the efficiency of current dissipation 225 kg strip compound Bags minimum or sufficient quantities required as per site complete including HDPE earthing pit cover size 300mmx300mmx260 mm suitable cover, material and labour including testing after completion and result should be less than five Ohm complete all as specified and directed by Engineer-in Charge.
Saini Enterprises (BID ID -3482597)
J.P. Enterprises (BID ID -3485425)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.85 MB
BOQ_828593.xls
BOQ • 0.57 MB
Tendernew43.pdf
Tender Documents • 1.35 MB
Download all tender documents and submit your bid