Ex Engineer (ENV) PCMC
Ex. Engineer (ENV) PCMC Main Building
Invitation of Quotation Notice for Tank mounted double membrane gas storage dome for Akurdi 30 MLD ISBR STP
2026_PCMCP_1326137_1
Quotation Notice-ENV/11/2026-27
Open Tender
Civil Works - Others
Item Rate
PCMC Area
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
7 Aug 2026
7 Aug 2026
14 Aug 2026
7 Aug 2026
13 Aug 2026
7 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Work Name | |||||
| 1.01 | Providing and Supplying, Erection and Commissioning for following :
Double membrane gas storage facility on digester top mounted principle, without bottom membrane, complete with
supporting belt structure and filing-level meter of following specifications: -
useable volume 300 m³
operating pressure 3,5 mbar
membrane tank diameter 14.80 m or 15m
membrane tank height above tank 3,5 m
diameter at anchoring 14.80 m or 15m
tank outer-diameter 14.80 m
tank height above foundation 8.0 + 0.9 m (refer drawing enclosed)
max. gas temperature 55 °C
max. gas production 250 m³/h
max. gas withdrawal 250 m³/h
anchor forces under an angle of 53,1° 6,5 kN/m
consisting of: | - | Per Unit | - | - |
| 1.02 | 1. One external membrane made of double-sided PVC-lined polyester material, UV and
microbial resistant, abrasion resistant, made from welded fabric cuts, short-term tensile
strength approx. 4000 N/5 cm, total weight approx. 900 g/m², colour grey.
Material tests: Colour fastness test acc. to DIN EN ISO 105-B04; light fastness better
than 7 (1 = worst value; 8 = best value). Repeated bending test acc. to DIN 53359,
grade 0 (scale 0 – 4; 0 = no damage). Cold resistance acc. to DIN 53361, grade 0
(scale 0 – 4; 0 = no damage). Flame-resistant acc. to DIN 4102 class B1. | - | Per Unit | - | - |
| 1.03 | 2. One internal membrane made of double-sided PVC-lined polyester material, UV and microbial resistant, abrasion resistant, made from welded fabric cuts, short-term tensile
strength approx. 4000 N/5 cm, total weight approx. 900 g/m², colour grey.
Material tests: Colour fastness test acc. to DIN EN ISO 105-B04; light fastness better than 7 (1 = worst value; 8 = best value). Repeated bending test acc. to DIN 53359, grade 0 (scale 0 – 4; 0 = no damage). Cold resistance acc. to DIN 53361, grade 0 (scale 0 – 4; 0 = no damage). Flame-resistant acc. to DIN 4102 class B1 | - | Per Unit | - | - |
| 1.04 | 3. One support-air blower ATEX approved, EEx-e-II-T3, power supply (max.) 0,18kW, 3 x 400 V, 50 Hz, air supply up to 180 m³/h with 3,5 mbar counter pressure. | - | Per Unit | - | - |
| 1.05 | 4. One air inflation system consisting of one non return flap and one adjustable counterweighted
pressure regulation valve, mounted between air blower and gas holder,
including a flexible air hose.
Pressure regulation valve – NW 200 mm
made of stainless steel V2A (1.4301) | - | Per Unit | - | - |
| 1.06 | 5. combined safety valve as liquid trap with filling level indicator; filling medium glycol, density 1,113 kg/dm³, made of PE.
Max. pressure rise at over pressure: 2 mbar
Max. pressure rise at vacuum: -1 mbar
Max. blow off capacity: 400 m³/h
Connecting flange DN 160 mm | - | Per Unit | - | - |
| 1.07 | 6. steel-profile clamping rail made of hot galvanized steel, complete with anchors, ready for mounting on a reinforced concrete tank. | - | Per Unit | - | - |
| 1.08 | 7. filling level meter
analog outputs: 4 – 20 mA
measuring range: 0 – 22,5 m
operating temperature: -20°C....+80°C
permissions ATEX. | - | Per Unit | - | - |
| 1.09 | 8. inspection window consisting of a locking ring and an acrylic glass panel, ø 550mm. | - | Per Unit | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.55 MB
Qotation11.pdf
Tender Documents • 1.53 MB
BOQ_2271053.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .