Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.7 LAccepted-AOC | ₹10.7 L Quoted ₹11.5 L | 1 | Accepted-AOC Accepted |
| 2 | 2₹12.3 L+₹79,617 (6.93%)Rejected-AOC | ₹12.3 L+₹79,617 (6.93%) | 2 | Rejected-AOC Rejected |
| 3 | 3₹12.7 L+₹1.2 L (10.7%)Rejected-AOC 1ST FLOOR GURJEET MARKET DHANGU ROAD | ₹12.7 L+₹1.2 L (10.7%) | 3 | Rejected-AOC Rejected |
| 4 | 4₹12.9 L+₹1.4 L (11.9%)Rejected-AOC | ₹12.9 L+₹1.4 L (11.9%) | 4 | Rejected-AOC Rejected |
| 5 | 5₹12.9 L+₹1.4 L (12.2%)Rejected-AOC 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹12.9 L+₹1.4 L (12.2%) | 5 | Rejected-AOC Rejected |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
30 Oct 2019, 6:00 pmClosed
GE Basoli
GE Basoli Pin-184152
REPAIR AND MAINTENANCE OF LT OH LINE LT UG CABLE/AB CABLE LT PANELS LT SWITCH GEARS AT MADHOPUR STATION UNDER GE BASOLI
2019_MES_283238_1
GE/BAS-38/2019-20
Open Tender
Civil Works
Item Rate
180 days
GE Basoli
As Per Tender documents
8 documents required · 8 mandatory
₹500
GE Basoli
₹30,000
GE Basoli Pin-184152
20 Feb 2020
19 Sept 2019
31 Oct 2019
19 Sept 2019
30 Oct 2019
3 Oct 2019
26 Sept 2019
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5mtr in depth for foundation of pole and laying of UG cable and getting out in any type of soil complete all as specified and directed.
Excavation in trenches not exceeding1.5 mtr wide and depth exceeding 1.5mtr but not exceeding 3.0 metre for foundation of pole and getting out in any type of soil complete all as specified and directed.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm completed all as specified and directed.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5M above the starting point completed all as specified and directed.
Material and labour for Sub Class 'B' brick covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified and directed.
Material and labour for sand cushioning to under ground cable 8 cm before laying the electric cable and 15 cm after laying the cable as specified in SSR 1991 of part -I complete all as specified and directed.
Material and labour for plain cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) as in coping of pole, as in benching including weathering slightly chamferred angles and finished exposed surfaced even and smooth including necessary form work, complete all as specified and directed.
Material and labour for plain cement concrete 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation & filling of pole, complete all as specified and directed.
Material and labour for prestressed concrete pole, 9.0 metres long, 102mm x 172mm at top and 102mm x 279mm at bottom,class 10 complete all as specified and directed . Note :- Earth work and PCC work shall be measured and paid separately under respective items.
Supply and fix for aluminium conductor steel re-inforced (ACSR) including G.I binding wire for LT lines on concrete poles, stretching without kinks and bends, binding with binding wire complete all as specified and directed.
Restretching of existing loose OH,LT ACSR conductor wire including GI wire along the span of poles for sagging within the permissible limit,(five/four/two wireline), including binding/rebinding/joining with Aluminium winding wire in case of breakge of condouctor, size of winding wire shall not be less than 2 sqmm complete all as specified and directed by Engr-in-charge. Note : (i) No extra cost is admissible on the account of jointing in case the conductor breaks during stretching.
Material and labour for trimming /cutting tree branches with clear space upto 2 metre from the over head conductor all around for LT distribution system ,complete all as specified and directed. Note : contractor shall take electric shutdown befor start work from main station and start line after triming of tree and informed to the JE/Engineer-In-Charge
Supply and Fix for structural steel work as in cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections, including , nuts, bolts, washers, welding , bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one priming coat of red oxide, one under coat , one finishing coat of aluminium paint and epoxy coating, complete all as specified and directed.
Supply and Fix for Pin type poly carbonate Insulator including one galvanised mild steel spindle, two galvanised iron washerrs,and one galvanised iron nut, 100 mm height, 65 mm dia ,suitable for 1100 Volt complete all as specified and directed.
Supply and Fix for shackle type, polycaronate Insulator incl one galvanised mild steel spindle, two galvanised iron washers,and one galvanised iron nut, 100 mm height, 115 mm dia ,suitable for 1100 Volt complete all as specified and directed.
Supply and fix in repair for Stay assembly complete with stay rod 20 mm accessories all as shown in Electrical plate No. 1 of SSR Part-I including galvanised steel wire stranded stay strand of size 7/4mm with loop type insulator stay clamps, (excavation and PCC work shall be measured and paid seperately) complete all as specified directed.
Material and labour for renewal of Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level. connecting to the Galvanised iron earth wire 4.0mm dia by means of bolls, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) reinforeed with XPM weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering , perforated at bottom 1.75 metre long placed on top edge of earth plate. charcoal and common salt filled 150 mm thick all around the earth plate test point made out of 40x8mm FI galvanised with fixing arrangement, funnel wire mesh and earth work in any type of soil returing filling in and removal of surplus soil to a distance not exceeding 50 mtr all as per electical plate 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion.
Material and labour for renewal of Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level. connecting to the Galvanised iron earth strip of size 32x6mm by means of bolls, nuts, check nuts and washers of galvanised iron and earth strip protected by provision of GI light grade pipe 40mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) reinforeed with XPM weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering , perforated at bottom 1.75 metre long placed on top edge of earth plate. charcoal and common salt filled 150 mm thick all around the earth plate test point made out of 40x8mm FI galvanised with fixing arrangement, funnel wire mesh and earth work in any type of soil returing filling in and removal of surplus soil to a distance not exceeding 50 mtr all as per electical plate 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
Material and labour for Painting of pole with two coats of sythetic enemal paint upto 1.5 metre above the ground level with black and yellow colour alternatively 30 cm intervel from bottom of pole of 9 metre RCC/Steel tubular Poles including numbering all as directed and painting of M.S cross arms madeout of angle iron/MS Channel and clamp in position fixed to RCC/Steel tublar pole 9 metre long with two coats of aluminium paint over a coat of red oxide primer including scraping existing painted surface complete all as specified and directed.
Material and labour for Painting of steel tubular pole 9 metre long in position with two coat of aluminium paint over a coat of red oxide primer after scraping the existing painted surface complete all as specified and directed.
Material and labour for painting of MS cross arms as existing site made out of angle iron /MS channe and clamp in position fixed to PCC/steel pole 9 metre long with two coat of aluminium paint over a coat of red oxide primer after scraping existing painted surface. complete all as specified and directed.
Supply and fix in repair for MCCB,four pole, suitable for 440 Volts, 400 Amps, 50 C/S, 37 KA, ICS=100% ICU with fixed of thermal magnetic release, fixing to the existing panel board matching with the existing slots, including any alteration required and with extention links properly connected to the bus bar complete all as specified and directed.
All as per item No 22 above but 320 amps, 36 KA
All as per item No 22 above but 200 amps, 36 KA
All as per item No 22 above but 200 amps, TP 25 KA
All as per item No 22 above but 160 amps, TP 25 KA
All as per item No 22 above but 100 amps,TP 16 KA
Supply and fix in repair for MCB TPN 32 amps, 10 KA, 'C' Series 440 volts complete all as specified and directed.
Supply and fix in repair for cable end joint kit for 1100 volt, out door type joint complete with all jointing material and accessories suitable for 3.5 core cable of size 50 sqmm to 185 sq mm complete all as specified and directed.
Supply and Laying in trenches or passing through pipe or fixing to pole/wall UG cable XLPE, insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade,120 Sq mm X 3.5 core cross section area complete all as specified and directed.
All as per item No 30 above but 95 Sq mm X 3.5 core
All as per item No 30 above but 70 Sq mm X 3.5 core
All as per item No 30 above 50 Sq mm X 3.5 core
All as per item No 30 above 25 Sq mm X 3.5 core
All as per item No 30 above 16 Sq mm X 4 core
All as per item No 30 above 16 Sq mm X 2 core
All as per item No 30 above 10 Sq mm X 2 core
Material and labour for Applying one coat synthetic enamel paint on the exterior surface of the out door panel /indoor panels with approved make and colour (both side has to be spary painted over the doors) complete all as specified and directed.
Supply, fixing and testing indication lamps with showing red, yellow and blue in colour of 22.5mm dia to monitor on panel board suitable for 240V AC supply as per existing at site, complete all as specified and directed.
Supply and fix in repair for GI light grade tube of size 40 mm dia for laid in trenches/ wall for protection of cable/earthing strip complete all as specificifide and directed.
Supply and fix for DWC high densiy polyethylene pipes having dia 63/50 as per site requirement having corrugation on the wall and plain surface on the inner wall conforming to IS: 14930(Part I & II) for protection of underground cable laid along pole/along wall/in PCC on GL/roof and including all fittings as required at site including taking down the old unserviceable pipe complete all as specified and directed.
Supply and fix for DWC high densiypolyethylene pipes having dia 90/76 as per site requirement having corrugation on the wall and plain surface on the inner wall conforming to IS: 14930(Part I & II) for protection of underground cable laidalong pole/along wall/in PCC on GL/roof and including all fittings as required at site including taking down the old unserviceable complete all as specified and directed.
Supply and fix in repair for Main switch in sheet steel enclosure with front handle of capacity 100 Amps , four pole , 415 Volts complete all as specified and directed.
Supply and fix in repair for APFC relay 8 stage with single CT input CSPF-100-08 of make C&S and equivalent in make Make- L&T/ EPCOS/ Seimens) complete all as specified and directed.
Supply and fix in repair for replacement shunt capacitor 5.0 KVAR complete all as specified and directed . Make L&T/ C&S/ABB/Legrand/ Epcos/HPL
Supply and fix in repair for replacement shunt capacitor 20 KVAR complete all as specified and directed . Make L&T/ C&S/ABB/Legrand/ Epcos/HPL
Supply and fix in replacement APFC Sheet metal encloure out door type having provision for fixing the MCCB, indicaotors lamps, capacitor as on required basis connection with appropriate size of cable and also having provisions to fixed on pole or on wall using MS clamps and necessary nuts bolts and washers complete all as specified and directed. Note :- MCCB/ capacitors/ indicators /cable shall be measured and paid seperately
Supply and fix in repair for of GI strip of earthing and making proper earth testing point from pole ,panels and transformer of size(32x6mm) complete all as specified and directed.
Material and labour for Continuous earth wire/guard cradle horizontal/rectangular fabricated with 4mm dia galvanized mild steel, binding wire complete all as specified and directed .
Material and Labour for Three phase electronic energy meter with LCD display with silent feature accuracy long range integrated rating 40-200 amps with front transparent unbreakable glass protected by wire cage and cabinet complete all as specified and directed.
Material and Labour for Three phase electronic energy meter with LCD display with silent feature accuracy long range integrated rating 10-60amps with front transparent unbreakable glass protected by wire cage and cabinet complete all as specified and directed.
Relaying of existing serviceable old bricks retrieved during excavation of old existing LT cable, providing protection of the electric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified and directed.
Dismantling and Taking down old U/S PCC LT pole of any size including earth work , removing the PCCetc complete all as specified and directed.
Dismantling and taking down old existing ACSR conductor any type from existing HT/LT pole complete all as specified and directed.
Dismantling of earth wire/ stay wire complete all as specified and directed.
Dismantling of steel work (brackets, clamps, channels including disc and pin insulators,nut & bolts) from existing LT/HT pole complete all as specified and directed.
Dismantling insulators any type, any size complete all as specified and directed.
Taking out the old unsv cable for repair in trenches or passing through pipe/fixed to pole/ wall XLPE insulated 120/95 Sqmm X 3.5 core armourned heavy duty electric cable complete all as specified and directed.
Taking out the old unsv cable for repair in trenches or passing through pipe/fixed to pole/ wall XLPE insulated 70/50/35 Sqmm X 3.5 core armourned heavy duty electric cable complete all as specified and directed.
Taking out the old unsv cable for repair in trenches or passing through pipe/fixed to pole/ wall XLPE insulated 25/16/10 Sqmm X 3.5/4/2 core armourned heavy duty electric cable complete all as specified and directed.
G.M. ENGINEERING SERVICES
Vijay Kumar Contractor and Engineers
M/S Vijay Punj Constructions
kailu construction co
KALSI CONSTRUCTION CO
Sudharshan Kumar Chopra
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .