| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 LAccepted-AOC | L1 | Accepted-AOC Quoting Lowest rate | |
| 2 | L2₹6.7 L+₹11,000 (1.66%)Rejected-Finance | L2 | Rejected-Finance Quoting Higher Rate | |
| 3 | L3₹7.0 L+₹34,730 (5.24%)Rejected-Finance | L3 | Rejected-Finance Quoting Higher Rate |
| Sl No | Description | Qty | Unit | P.S.Enterprise L1 | Hipotronics Engineers L3 | IRP Enterprise L2 |
|---|---|---|---|---|---|---|
| 1.00 | Topology, IGBT BASED DSP CONTROLED | 1 | Nos | 6,63,000 ₹6,63,000 Lowest | 6,97,730 ₹6,97,730 | 6,74,000 ₹6,74,000 |
| 1.01Rating of UPS(KVA/KW): 30 KVA / 24KW (Make: Switching AVO,Emerson,Power One, APC, NUMERIC) | ||||||
| 1.02Input Voltage: 310----400----415 VAC 165-288 Volt /Phase(selectble) | ||||||
| 1.03Input Frequency: 45 to 65 Hz | ||||||
| 1.04Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output | ||||||
| 1.05Back feed Protection: UPS should have back feed protection | ||||||
| 1.06Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer | ||||||
| 1.07Output Voltage: 230 VAC | ||||||
| 1.08Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3% | ||||||
| 1.09Output Frequency: 50 Hz +/- 0.1% | ||||||
Tender Value
Refer Docs
EMD Value
₹12,000
Closing Date
27 Jan 2023, 3:00 pmClosed
Superintending Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Construction of 100 beded COVID Hospital at Prafulla chandra Govt. Medical College , Arambagh........... Arrangement of UPS.
2022_WBPWD_439343_1
WBPWD/SEWEC /HED /NIQ-129 /2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Hooghly
Please refer Tender documents.
5 documents required · 5 mandatory
₹12,000
Office of the Superintending Engineer, Western Ele
7 May 2026
29 Dec 2022
30 Jan 2023
29 Dec 2022
27 Jan 2023
31 Dec 2022
29 Dec 2022 - 30 Dec 2022
30 Dec 2022
Amount
Topology, IGBT BASED DSP CONTROLED
Rating of UPS(KVA/KW): 30 KVA / 24KW (Make: Switching AVO,Emerson,Power One, APC, NUMERIC)
Input Frequency: 45 to 65 Hz
Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output
Back feed Protection: UPS should have back feed protection
Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer
Output Voltage: 230 VAC
Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3%
Output Frequency: 50 Hz +/- 0.1%
Output Power Factor: 0.8
Crest Factor: 3:1
THDu: < 2% (linear load), < 5%(non linear load)
Waveform: Pure Sine Wave
Birdge: Microprocessor based and IGBT Technology
Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 30 sec
Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms
Overall Efficiency: 92%
Battary Rack: With power coated MS angle with suiteble dimention and gadge.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary acessiress.
Battery : 12 V, Mono Block batteries. SMF VRLA
DC Bus : Minimum 192V or above, 30 mim back up required (Minimum 28666VAH) Battery. Battery Make: Exide/Amar Raja(Quanta)
Protection: Multi Protection-Over Temperature Protection with 8 Sensors, Overload, Battery Under Voltage, Fan Failures ,Short Circuit. Four Circuit Breakers, Providing Full Protection When Fault, Strong Overload Capability. Surge Protector at Panel Input & EB Input. PV Reverse Polarity, Input Low & High Voltage, Output Low & High Voltage cut off. Glass cartridge Fuse on Control Circuits MCB at Input Panel,
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip
Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current
Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch
Termination: Input, Battery, Output & Bypass
Enclosure: IP 20
Operating Temp: 0 to 40 Deg C
Humidity: Upto 95% Rh (non-condensing)
Cooling: Forced Air
Noise: < 55 dB
Cold Start : Provided
CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture)
ISO 9001: 2015, ISO 14001: 2015, ISO 45001:2018,ISO 50001;2018 , ISO:20000-1:2011,ISO:27001:2013, ROHS
Warranty:One Year on UPS & two yers on batteries on site against any Manufacturing defects
IRP Enterprise
Hipotronics Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 15.44 MB
new2911.pdf
Tender Documents • 0.51 MB
BOQ_872431.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .