Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC | L1 | Accepted-AOC work awarded to L1 agency | |
| 2 | L2₹10.3 L+₹44,590 (4.54%)Rejected-Finance P 27 1 RASHTRAGURU AVENUE DUM DUM KOLKATA 700028 | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L2 | Rejected-Finance FINANCIAL BID FOR L2 BIDDER REJECTED | |
| 3 | L3₹10.7 L+₹88,503 (9.01%)Rejected-Finance | L3 | Rejected-Finance FINANCIAL BID FOR L3 BIDDER REJECTED | |
| 4 | L4₹10.9 L+₹1.1 L (11.0%)Rejected-Finance PLOT NO 28 BRAHMESHWAR BAG TANKAPANI ROAD BHUBANESHWAR 751018 | KHORDHA | ODISHA | 751018 | L4 | Rejected-Finance FINANCIAL BID FOR L4 BIDDER REJECTED | |
| 5 | L5₹11.2 L+₹1.4 L (13.9%)Rejected-Finance 9 AMARNATH INDUSTRIAL PAR K OPP MAIZE PRODUCT ODHAV SINGARVA ROAD ODHAV AHMEDABAD GUJARAT 382415 | AHMADABAD | GUJARAT | 382415 | L5 | Rejected-Finance FINANCIAL BID FOR L5 BIDDER REJECTED |
Tender Value
₹13.7 L
EMD Value
₹27,310
Closing Date
28 Jan 2020, 6:00 pmClosed
AGM Engg Elect
3rd floor DGCA building BPI airport bhubaneswar
Supply and Laying of HT LT cables and allied Electrical works at B P I Airport Bhubaneswar
2020_AAI_40697_1
AAI/BBSR/AGMEE-I/ENIT-20/19-20
Open Tender
Electrical Works
Item Rate
90 days
Bhubaneswar airport
As per NIT criteria
3 documents required · 3 mandatory
₹1,180
Airports Authority of India
₹27,310
5 Mar 2020
21 Jan 2020
3 Feb 2020
22 Jan 2020
28 Jan 2020
22 Jan 2020
22 Jan 2020 - 27 Jan 2020
Amount
Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor power cable conforming to IS 7098 (Part 1) amended upto date.
3.5C X 240 Sq.mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5C X 240 Sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated PVC sheathed / XLPE power cable of 1.1 KV grade of following sizes on cable tray as required.
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) on cable tray
Laying of one number PVC insulated and PVC sheathed power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required.
Above 185 sq mm and upto 400 sq mm
Supplying of double wall corrugated high density polyethylene ( DWC HDPE) pipe conforming to IS:14930 (part-2) with latest ammendment, complete with accessories like couplers, bends, tees etc.
OD 90 mm / ID 76 mm nominal
Laying of HDPE duct. in the soil work upto 750 mm deep, back filling & making good the same as per site requirement. a)90 mm dia (OD-90 mm & ID-76 mm nominal).
Supply of 3 x 185 sq mm, 11 KV (E) grade Aluminium conductor XLPE insulated, PVC sheated, Armoured power Cable conforming to IS 7098(Part-II) 2011 ammended up to date and confirming to the technical specifications enclosed
3.0 x 185 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV grade of following size direct in ground including excavation, sand cushioning,protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 11 KV grade as required.
3C X 185 Sq.mm
Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium conductor power cable conforming to IS 7098 (Part 1) amended upto date.
4C X 25 Sq.mm
3.5C X 35 Sq.mm
Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Copper conductor power cable conforming to IS 7098 (Part 1) amended upto date.
3C X 1.5 Sq.mm
Supply of Three phase 4 wire KWH counter type energy meter CT operated base ,240V,5-10 A , class accuracy 1.0.
Supply of wire wound type metering CT 100/5A, with minimum 5VA burden, class accuracy 1.0, for connecting to energy meter.
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
8 way (4 + 24), Double door
Supplying and fixing 6 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing of 40A rating 415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Four Pole
Supply of recess mounted , 15 Watt circular type led fitting of Size range 160-180 mm dia with LED drive having output & minimum lumens 110lumens/watt i/c necessary electronic driver, LED lamp suitable to operate with 230V AC,50Hz power supply as per tender specifications complete as required.
Installation, testing and commissioning of pre-wired, fluorescent/ LED fittings of all types, complete with all accessories and tube etc. and connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Youngmen Traders
FOCUS POINT
M/S DURGA SUPPLY AGENCIES
RVD INFRA SOLUTION PVT.LTD.
Manish Electricals
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .