Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.9 LAccepted-AOC 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹83.8 L+₹34.8 L (71.1%)Rejected-Finance BLOCK C 14 GROUND FLOOR PLOT 618 624 BHIVANDIWALA TERRACE JAGANNATH SHANKARSHETH MARG DHOBI TALAO NEAR KALBADEVI POST OFFICE MUMBAI 400002 | MUMBAI | MAHARASHTRA | 400002 | L2 | Rejected-Finance Other than being lowest |
Tender Value
₹63.5 L
EMD Value
₹1.2 L
Closing Date
9 Mar 2024, 6:00 pmClosed
CWE (NW) Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar Colaba Mumbai 05
PROVISION OF AFDS IN VICTUALING STORE INCLUDING COOL AND COLD ROOM CLOTHING STORE MEDICAL STORE ROOM AND CSD CANTEEN IN A09 BUILDING MANOR HOUSE AT INS ANGRE AND PROVISION OF AUTO FIRE DETECTION S SYSTEM AFDS FOR BLDG P222 C NO40 41 BEF FOUNDRY P
2024_MES_639819_1
8318/CWE(NW)MUMBAI/E8
Open Tender
Civil Works
Item Rate
180 days
GE (NW) Kunjali
Class C category c(vi)
7 documents required · 7 mandatory
₹1,000
Yes
GE (NW) Kunjali
₹1.2 L
Yes
28 Mar 2024
30 Jan 2024
11 Mar 2024
30 Jan 2024
9 Mar 2024
20 Feb 2024
30 Jan 2024 - 19 Feb 2024
Amount
Supply, installation, Testing & Commissioning of Microprocessor based 2 loop capacity , Networkable analogue addressable type fire alarm control panel with min.600 character LCD display, The panel should be equipped with sufficient numbers of 1 loop with up to 10 to 15% spare capacity with each loop shall have a capacity of minimum 99 detectors and 99 analogue addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire so PA System shall automatically come in announcement mode as per tender specificaiton.
Supply, installation, Testing & Commissioning of LANDLINE FIRE ALARM AUTO DIALER WITH sms and Memory Available To Store 10 Phone Numbers dialling facility to reach the fire brigade to get the intimation about the location of the area Builtin Emergency Speech Dialer with 8 Numbers & 1/ 2 Messages,NO/NC contacts for both fire and fault, Automatic changeover arrangement to standby supply with battery charger with low battery indication,Fault/ failure indication such as MAINS FAIL, short, open, Battery FAIL etc,Micro-Controller Based System,Both Dialling Modes can be used (Pulse/Tone),Recorded Message Playback Speaker Provision Available complete all as specified and as directed.
Supply, installation, Testing & Commissioning of Microprocessor based Repeater Networkable analogue addressable type fire alarm control panel with min.600 character LCD display,Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire PA System shall automatically come in announcement mode complete all as specified and as directed.
Supply, Installation, testing and commissioning addressable Manual call point (Pull down/Break Glass Type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be underwritters laboratories listed, semi flush type complete all as specified and directed.
Supply, installation, Testing & Commissioning of Addressable monitor modules for Sprinkler Flow Switch and Door Holders complete all as specified and directed by Engineer-in-Charge.
Supply,installation, Testing & Commissioning of addressable electronic hooter with built in amplifier unit with two tone generator of 100 meter range complete all as specified and directed by Engineer-in-Charge.
Supply, installation, Testing & Commissioning of Analogue addressable Multi Criteria (Optical +thermal) detector with mounting based LED for AFC (Above Celling & below celling) complete all as specified and directed by Engineer-in-Charge.
Supply, installation, Testing & Commissioning of Conventional Beam detector complete as required for hall & indoor open area complete all as specified and directed by Engineer-in-Charge.
Supply, installation, Testing & Commissioning of Addressable control modules for AHU, Access control Integration & stairs Pressurization Fan Hooters / Sounders / Strobes etc.complete all as specified and directed by Engineer-in-Charge.
Supply and fixing fault isolator module with automatic resetting arrangement complete all as specified and directed by Engineer-in-Charge.
Supply & laying 1.5 sqmm 6 core FRLS PVC insulated and sheathed armoured solid copper conductor cable , XLPE Insulated with galvanized steel strip, electric power cables (heavy duty) 1100 Volts grade, laid in duct / along pole/wall etc including making connection using aluminium thimbles/lugs and cable gland complete all as specified and directed by Engineer-in-Charge.
Supply, installation, Testing & Commissioning of Response indicator for Above celling detectors & Cabin Detectors complete all as specified and directed by Engineer-in-Charge.
Supply, installation, Testing & Commissioning of GUI based main network software capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems; and / or sensors locations. The GUI software shall be located in control room in one of the blocks and shall monitor all the blocks panel connected with each other along with workstation complete all as specified and directed by Engineer-in-Charge.
Supply & fixing fire alarm control panel complying with BS EN 54-5 loop with 99 detectors & 99 Modules & upto 200 dectors and modules (per each loop) complete all as specified and directed by Engineer-in-Charge.
Supply & fixing Detectors complying with and type certified to EN -45 Addrssable type multi senser (heat and smoke) detector photoelectric/ Optical with base self built intellgence as per IS:11360 complete all as specified and directed by Engineer-in-Charge.
Supply & fixing Detectors complying with and type certified to EN -45 Addrssable type heat detector photoelectric/ Optical with base with rate of rise cum fixed temperature as per IS : 2175 complete all as specified and directed by Engineer-in-Charge.
Supply& Fixing addressable manual call point resettable type complete all as specified and directed by Engineer-in-Charge.
Supply & fixing addressable electronic sounder cum srobe complete all as specified and directed by Engineer-in-Charge.
Supply & fixing remote response indicators complete all as specified and directed by Engineer-in-Charge.
Supply & laying PVC armoured cable 1.5 sq mm copper conductor 2 core complete all as specified and directed by Engineer-in-Charge.
Supply and laying Cable glands suitable for 2 core 1.5 Sq copper conductor armoured cable complete all as specified and directed by Engineer-in-Charge.
Supply and fixing junction box of size not less than 4x4 inch with connector encloser, 3 terminal/ PVC/ polycarbonate, isolated body including taking out old one.
Supply & fixing Addressable control module complete all as specified and directed by Engineer-in-Charge.
Supply & fixing Addressable monitor module complete all as specified and directed by Engineer-in-Charge.
Supply & fixing Addressable type Flame detectors with UV/IR detection capacity( add up cost of module to be a complete set, the type of module shall be relay type module) complete all as specified and directed by Engineer-in-Charge.
AGRAWAL ASSOCIATES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .