GE (NW) KARANJA
NAVAL STATION KARANJA, URAN, RAIGAD, MAHARASHTRA
SPECIAL REPAIR TO INTERNAL WIRING AND CERTAIN E/M FITTING AND FIXTURE OF REGIMENTAL SHOP BLDG NO (P-440A), (P-440B), (T-68 AND S/PMT) NEAR SAILORS MD ACCN AND BLDG NO L (425), M (424) AND O (426) AT NAVAL STATION KARANJA
2022_MES_544684_1
8577/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (NW) KARANJA
SPECIAL REPAIR TO INTERNAL WIRING AND CERTAIN E/M FITTING AND FIXTURE OF REGIMENTAL SHOP BLDG NO (P-440A), (P-440B), (T-68 AND S/PMT) NEAR SAILORS MD ACCN AND BLDG NO L (425), M (424) AND O (426) AT NAVAL STATION KARANJA
8 documents required · 8 mandatory
₹500
Yes
GE (NW) KARANJA
₹88,060
Yes
20 Dec 2022
11 Aug 2022
8 Sept 2022
11 Aug 2022
6 Sept 2022
25 Aug 2022
11 Aug 2022 - 25 Aug 2022
Amount
Taking down carefully copper /aluminum point wiring ( light,fan,socket or power) complete, with wiring acessories such as bend boards Elbows only, ceiling fittings etc and removing material to store for safe coustody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. all as specified.
M & L for point wiring with 1.5 sqmm (nominal area) FRLS PVC insulated and unsheathed multistranded copper conductor cable ( using colour code as per IS) 1100 volts grade drawn through and including new casing capping (ISI marked) on wall surface with all accessories including sheet steel terminal / CI box with 3 mm thick hylam / masonite sheet top cover including 1.5 sqmm size PVC insulated unsheathed copper conductor multistranded cable for continuous earth conductor ( using green colour) to common earth and connecting to earth dolly, complete all as specified & directed for the following :- (a) One light / Buzzer point controlled by one switch 5 Amp, SP, one way 240 volts.
(b) One fan/exhaust fan point controlled by one switch
(c) One 5 pin socket outlet 5 Amps on same board
(d) One 5 pin socket outlet 5 Amps on independent board
(e) One light point controlled by 2 way switch SP, 5 Amp, 240 Volts
All as per item No 2 above but with 2.5 sqmm multi stranded copper conductor 1100 volts grade FRLS PVC insulated sheathed cable with FRLS PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continues earth on independent board.
S & F switch piano single pole one way, 6 Amp (ISI marked) all as complete all as specified and directed by Engineer-in-Charge.
S & F switch flush button, single pole two way, 6 Amp (ISI marked) complete all as specified and directed by Engineer-in-Charge
S & F switch socket combination 2 in 1, 3 pin, 6 Amp flush type (ISI marked) complete all as specified and directed by Engineer-in-Charge.
S & F socket outlet 2 in 1, 3 pin, 5 Amp flush type (ISI marked) complete all as specified and directed by Engineer-in-Charge.
S & F switch socket outlet 15 Amp, 5-in-1, controlled by one switch (ISI marked) all as per makes given in PS complete all as specified and directed by Engineer-in-Charge.
S & F ding dong door bell electric suitable for AC 230 volt, single pole complete a all as specified and directed by Engineer-in-Charge.
S & F bell push flush type 6Amp (ISI marked) all as specified and directed Engineer-in-Charge.
S & F ceiling rose, 3 phase/PVC/polycarbonate, isolated body, three terminals complete all as specified and directed.
S & F stepped type electronic fan 5 step regulator flush type for ceiling fan complete all as specified and directed by Engineer-in-Charge.
Supply and fixing surface and wall mounted LED batten of 20 W with polycarbonate housing & integrated electronic driver having THD<20% complete all as specified and directed by Engr-in-charge.
Supply and fix LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S & F replacement MCB SP 240 V, 50 Hz, 10 KA conforming to IS 8828 of rating 5 to 32 Amp, 'C' series complete all as specified and directed by Engineer-in-Charge.
S&F MCB double pole RCBO 240 volts AC 40 Amps (C-series) OF 100MA all as specified and directed by engr-in-charge
M&L for wiring for circuits/sub main wiring with FRLS PVC insulate sheathed 2 x 6 sqmm stranded copper conductor cable 1100 volts grade heavy duty drawn into new PVC conduit with 6 sqmm PVC insulated green copper cable for continues earth with suitable dia of PVC pipe with all accessories complete all as specified and directed by Engr-in-Charge.
S & F double door MCB DB made out of 18SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts 200 Amps rated bus bar 8 way double door open able, including taking out old unsv MCB DB any size/type.
Taking down exhaust fan, sealing cable end, dismentling blades and removing fan and blades to store complete all as specified and directed by engr-in-charge . Note :- Necessary cutting and chasing for making hole for exhaust fan rate will deemed to be included in the quoted rate.
Fixing only exhaust fan and connecting up including provision of cable from ceiling rose/connector to fan and fixing louvers shutters from outside of the bldg, arrangement for fixing the louvers will be made by contr complete all as specified and directed by Engr-in-charge.
Taking down ceiling fan and keeping in safe custody for reuse and refixing the same after duly painted and marking of MES number on ceiling fan of size 1200mm sweep complete with connected accessories as directed and specified by Engr-in-Charge.
Hanging only ceiling fan and connecting up including provision of cable from ceiling rose or conccetor to fan complete all as specified and directed by Engr-in-Charge.
Supply and fix LED decorative wall mounting chrome finish fixture with textured glass with 5 w led lamp MAKE-HAVELLS ct pt no-LHJC02108499 or equivalent in bajaj/CG
Supply and fixing LED building security light fitting with suitable size bracket/angle to fit security light of 60w IP 66 protection LED complete all as specified and directed by Engr-in-charge.
M&L for earthing complete with galvanised steel earth plate electrode size 600x600x6.0mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised iron strip 32X6 mm dia by means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion. Note : The unit rate includes for protection pipe and lead wire from top of earth plate up to 7.5 meter above ground level.
Supply and fix Meter Box consisting space to fix MCCB as Incomer and 09 nos meter and providing 09 nos MCB RCBO 40 Amps 100 mA, METER box double door fixed type wall mounted CRCA approved FACTROY MADE PTTA ADLEC, 2 mm thick sheet enclousure. The rates including taking down old meter and connecting in new panel with required wires with out any extra cost complete all as specified and directed.The panel should cosists of the following :- INCOMING (1) MCCB 100 AMP 4 P 25 Ka thermal magnetic based with o/c, s/c protection & ROH - 01 nos (2) Indicating lamps RYB-03 nos. OUT GOING :(1) 40 amp MCB RCBO 100 mA with enclosure-09 nos. (2) Space for refixing existing electrical meter - 09 nos. NOTE - Contractor should visit the site and to prepare panel as per size required to fit in below stair case complete all as specified and directed by Engr-in-charge
S & F replacement RCBO MCB 240 V 50 Hz 100mA confirming to IS 8828 of rating 40 Amp as per as in repairs all as specified and directed.
Supply, fixing, stringing and drawing submain wiring with 2 runs of single core 6 sqmm PVC insultaed, unsheathed multi stranded copper concuctor cable, 1100 Volts conforming to IS-694 1990 with ISI mark, drawn through and including PVC casing capping 25 mm size including one run of 6 Sqmm PVC insulted multistanded copper conductor cable, 1100 Volts grade conforming to IS -694, 1990 green colour for earth contuinity and connecting up to common earth dolly complete all as specified and directed. Note:- Two run of 6 Sqmm and one run of 6 Sqmm earth wire and casing & capping will be measured as one running metre
Supply, fixing, stringing and drawing submain wiring with 4 runs of single core 6 sqmm PVC insultaed, unsheathed multi stranded copper conductor cable, 1100 Volts grade conforming to IS-694 1990 with ISI mark, drawn through existing PVC conduit 25 mm bore/ stove enamelled steel conduit 25 mm bore / PVC casing capping 25 mm size including 2 Run of 6 Sqmm PVC insulted multistanded copper conductor cable, 1100 Volts grade conforming to IS -694, 1990 green colour for earth continuity and connecting up to common earth dolly complete all as specified and directed. Note:- Four runs of 6 sqmm cable, one run of 6 sqmm earth wire with pvc conduit 25mm will be measured as one running metre
S & F replacement MCCB distribution board VTPN, 4 ways, 415 Volts, 50 Hz, AC, double door made out of sheet metal phosphatised and painted with epoxy polyster based powder paints with 200 Amps rated bus bar and earth bar, ISI marked complete all as specified. Make : Havells or equivalent of L&T/Legrand/HPL.
S & F replacement MCCB 4 pole, thermal release range 100 Amps of breaking capacity 16 kA, 415 Volts, 50 Hz, Series complete all as specified
Supply and fix LED batten with 20W LED tube light in wall/surface connecting with all required accessories like PVC box base,flexible cable from ceiling rose etc Surface and wall mounted LED batten, engineering plastic housing with polycarbonate diffuser & integrated electronic driver as directed and specified by engr-in-charge. Make Bajaj CT PT NO- BCLSB 20W WH or equivalent in Havells,CG/C&S
S & F replacement TPN MCB 415 V 50 Hz 10 KA confirming to IS 8828 of rating40 TO 63 Amp all as specified and directed.
Supply and fixing LED flood light/ hibay light 200W with suitable size fixing arrangement, IP 66 protection LED make bajaj ct pt no-BGPPH 200W LED WH or equivalent in Havells, Benlo, Crompton etc.
Taking down unserviceable XLPE/PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminium conductor from wall through necessary arrengements of size 2 core 10 sqmm
Supply & fixing, jointing, connecting & testing in trenches/surface XLPE/PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminum conductor in trenches / ducts of size 2 core 10 Sqmm including necessary arrengement of saddle the cable on wall complete and all as specified and directed by Engineer-in-charge.
Supply and fix exhaust fan, steel body AC single phase, 230V of size 300mm sweep with, blades, and frame and louvers complete all as specified and directed. Note : Necessary cutting and chasing rate deemed to be included in quoted rate.
S & F triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB 63 Amps complete all as specified and directed.
Supply & fixing, jointing, connecting & testing in trenches XLPE/PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminum conductor in trenches / ducts of the following sizes including taking out cable cover & cable all as specified and directed :-
3.5 core 70 Sqmm
3.5 core 35 Sqmm
Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in soft/loose soil including taking out faulty cable/cable covers and GI pipe complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the Starting point.
M & L for dry river sand as sand cushioning for protection of UG cable including punning of sand in layers all as specified
Supply & laying un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm all as specified & directed.
Laying only un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm all as specified & directed.
M&L GI pipe light grade with all fittings complete laid in trenches all as specified for 50 mm bore of pipe
M&L GI pipe light grade with all fittings complete laid in trenches all as specified for 80 mm bore of pipe
somnath engineering corporation
M/s S.D Construction Co
R A Electric Co.
Shri Krishna Trading Corporation
shree arihant constrution
M/S R.S. CONTRACTOR & SUPPLIER
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .